Loading...
Meridian Charter HS CZC 02-008 • HUB OF TRE S Mayor ROBERT D. CORRIE A URE VALLEY A Good Place to Live LEGAL DEPARTMENT Council Member< CITY OF MERIDIAN I~oR)xx4-4a6a PUBLIC WORKS CHARLES ROUNTREE 33 EAST IDAHO BUILDING DEPARTMENT GLEi\'N BENTLEY 1~IERIDIAN, IDAHO 83(rl2 RON ANDERSON Phone (208) 888-4433 • Fax (208) 887-4813 PLANNING AND ZONING KEITH BIRD DEPARTMENT I,_OR)Rx1-ii 11 CERTIFICATE OF ZONING COMPLIANCE* Date: May 26, 1999 Owner: Meridian Joint School District #2 Address: Locust Grove, north of Ustick Proposed Use: Charter High School Zoning: Comments: Property is subiect to terms of recorded development agreement. All sis7nal?e is subiect to desi>?n review and requires separate permits. No signs a is permitted in the ACHD ri h~ t_of-w~. No portable signs or temporar~gnage permitted. Parking requirements are met bX the plan. Development Agreement Sections 4.1.7 (reg_arding location of the driveways and 4.1.8 (regardm~; bicycle and pedestrian access) have been met as per the ACHD letter dated 5/10/99. The proposed fencing shown on sheet S-1 meets the requirements of section 4.1.9 of the development agreement. An under round, pressurized irri atg ion system must be installed to all landscaped areas, including all grass areas of the site. All trees must be planted as per the approved landscape plan. All drive aisles must be at least 25 feet wide. The low berm along the Hollister's driveway as shown on the landscape plan (sheet S-4) is missing on the gradin pg} lan (sheet S-31, and shall be built as per the landscape plan. The Landscape Plan is not to be altered without prior written approval of the Planning & Zoning Department. No field changes to the site/landscape plan are permitted; prior written approval of all changes is required. Lighting_shall not cause glare or impact the traveling public or nei hg boring residential development. Building facades shall be built as per the plans as represented in the public hearings. `~~ The landscape/site plans dated April 7, 1999 and Revised May 12, 1999 are approved. Shari Stiles Planning & Zoning Administrator *Receipt of a Certificate of Zoning Compliance does not indicate compliance with requirements of other departments/agencies, including, but not limited to, Ada County Highway District, Central District Health Department, affected irrigation district(s), Meridian Sewer, Water, Building or Fire Departments, etc. This certificate shall expire one (I) year from the date of issuance if work has not begun. r -• ~ w~ ~../ J r J t' .i R a z ~ W ~ ~ C ~ ~ . ~ ~. m{ ~ .I~ 8 ~ `a ~Im. _V ~ b a' u ~ a~ I W v_o I ~ ~ W ~ ~ { ~ 2 7V D A { a311d~dNn s u ~Y g~ { p~~ 8X °oQ {[~ ~~ O .... SC92tt 3 OL 10.00 S ~i~css ; ~ ~~ s ~/ ~ c U e Q~ i ~ // ~ 4 I I II l~ ~lo ~K ~~ i ~~ + 1 ~f / a f ~ i~ ' $ L ~~ < ~ ~~ ~ ~N ~~ I /% ~ 1 as il!$ ~ ~ t" ~~ I ~ 1 ~~ r' - ^ x.csAlaoo w I II XI a II o ~ II ~ o f II W .. ~ ~~ + II S OI 41 'J ~I c`~ 6 ~I ~ r z Z s ~p~ !I I ~ W d II ' I W L Il O (/S f1 I I ~ ~_ 1 ~ II W I ~ 11 K ~ I W II _~ I o ~ W ~ v I I ~ ~ 8 a~ II Z 5 w I °` II ~ Z ~ y II d ~ ~ I I I I If I 'j f II ~ ' II ~ I I I I I yn .n .o u~ a fwesf ~ _ _ r. 3 _ _ Lf'[S8 $ ~_ ~~tf,f~0 ~~ ~ _ _ _ _ ~ ~ ~ Lfi'tf191 /l~1t.0600 N N g 9 avoa 3noa~ isn~o~ rW~-0 0 C 5 Q m (n O J W ~.. 1SLJ G N N H Z O µUy~~I' N' ~' W 0! v i/~ 0019 888 80Z %t'3 9T=0T Q33- 86/ZO/Zt i~1`~'~'` sa Fyn ~~~, TO: FROM: DATE: RE: Mr. & Mrs. James R. Hollister Ada County Assessor's Office June 11, 1998 Tax Parcel Number Change Dear Mr. & Mrs. Hollister: .• RECD J UN 1 ~ 1998 This letter is to inform you that the Ada County Assessor's Office Land Records Division has processed a deed which splits parcel numberS0532315315/S0532325405/S0532315316. You were listed as the owner of this parcel for tax year 1998. This deed {or other action) has created these new parcel numbers for tax year 1999: PARCEL # NEW OWNER ACRES S0532315317 James R. & Karen L. Hollister .598 S0532325406 Joint Scfiool District No 2 40.549 S0532315320 James R. 8 Karen L. Hollister 10.019 For tax year 1998, assessment notices and tax bills will go out on parcel #50532315315/S05323254051S0532315316 as itwas before the split. We suggest that you change your records accordingly and notify your escrow holder of these changes. if you have any questions, please feel free to contactMark Perfect of the Ada County Assessor's Land Records Division, at (208) 364-2378. Very truly yours, ROBERT H. MCQUADE Ada County Assessor By: Mark Perfect Deputy Assessor RHMlmec cc: Ada County Treasurer's Office James R. & Karen L. Hollister Joint School District No 2 James R. 8 Karen L. Hollister , _ \` ~~ 'M ~ ~ CU ~%5~7 ~5 ~ OL~~ WARRANTY DEED FOR VALUE RECEIVED, HOLLISTER PROPERTIES L.P., Grantor, does hereby grant, bargain, sell and convey unto JOINT SCHOOL DISTRICT NO. 2, Grantee, whose address is 911 N. Meridian Road, Meridian, Idaho 83642, that certain real property particularly described in Exhibit A attached hereto. TO HAVE AND TO HOLD the said premises, with their appurtenances, unto the said Grantee, its heirs, successors and assigns forever. The said Grantor does hereby covenant to and with the said Grantee that it is the owner in fee simple of said premises and that it is free and clear from all encumbrances, except as set forth above, AND THAT IT WILL WARRANT AND DEFEND the same from all lawful claims whatsoever, SUBJECT, HOWEVER, TO easements, restrictions, reservations, assessments and encumbrances of record, AND FURTHER SUBJECT TO easements that would be revealed by a physical inspection of said real property. IN WITNESS WHEREOF, Grantor has hereunto executed this Warranty Deed this fs~~ H- day of April, 1998 . GRANTOR: HOLLISTER PROPERTIES L.P. gy : ,~L ene 1 Partner PENINSULA !MAN EMENT COMPANY, an Idaho oration, James R. Hollister, President WARRANTY DEED, p. 1 ~, ~ .. • • STATE OF IDAHO ) ss. County of Ada ) On this day of April, 1998, before me, the undersigned Notary Public in and for said State, personally appeared JAMES R. HOLLISTER, known or identified to me to be the President of PENINSULA MANAGEMENT COMPANY, which is the General Partner of HOLLISTER PROPERTIES, LP., and acknowledged to me that he executed the same for Hollister Properties, L.P. IN WITNESS WHEREOF, I have h t my hand and affixed my official seal the day and r in this c tific to firs above written. 9n~~h~~ ~~I ~, , NOTARY PUBLIC, tate of a o o ~ ~pTq~ ~= p'~ Residing at B ise s = ~' ; My Commission Expires: ~ Residing at Meridian, ID °nsm Exp 10/28/99 WARRANTY DEED, p. 2 ^~ -•-,- •A PARCEL OF LAND L~TED IN THE SOUTHWEST QUARTER O~ECTION 32, TOWNSHIP 4 NORTH „ RANGE 1 EAST, OF THE BOISE MERIDIAN, ADA COUNTY, IDAHO, BEING ..MORE PARTICULARLY DESCRIBED .AS FOLLOWS: COMMENCING AT THE NORTHWEST CORNER OF THE SOUTHWEST .QUARTER (WEST 1/4 CORNER) OF SECTION 32, TOWNSHIP 4 NORTH, RANGE 1 EAST, BOISE MERIDIAN, THE REAL POINT OF BEGINNING OF THIS DESCRIPTION; THENCE NORTH 89 DEGREES 54'10" EAST 1990.54 FEET TO THE NORTHEAST CORNER OF THE WEST HALF OF THE NORTHEAST QUARTER OF THE SOUTHWEST QUARTER OF SAID SECTION 32; THENCE SOUTH 0 DEGREES 01'20" EAST 728.57 FEET TO A POINT ON THE EAST LINE OF SAID WEST HALF ; THENCE SOUTH 89 DEGREES 48'44" WEST 604.48 FEET. TO A POINT; THENCE SOUTH 0 DEGREES 00'57" EAST 225.95 FEET TO A POINT;. THENCE SOUTH 89 DEGREES 50'05" WEST 1386.36 FEET TO A POINT ON THE WEST. LINE OF SAID SECTION 32; THENCE NORTH 0 DEGREES 00'11" WEST 957.12 FEET TO THE REAL POINT OF BEGINNING OF THIS DESCRIPTION. EXCEPT ANY PORTION LYING WITHIN THE RIGHT OF WAY FOR LOCUST GROVE ROAD. SUBJECT TO' THE FOLLOWING: 1. GENERAL TAXES FOR THE YEAR 1997, WHICH ARE LIENS, OF WHICH THE FIRST HALF HAS BEEN PAID. THE SECOND HALF OF WHICH tVILL NOT BECOME DELINQUENT UNTIL JUNE 20TH. _ PAS ~` ~~ AFFECTS 242S0532325405 S667.75 PARCEL I 242S0532315315 53257.04 PARCEL II 2. GENERAL TAXES FOR THE YEAR 1998 , WHICH ARE LIENS, ARE NOT YET DUE AND PAYABLE. 3. ANY, RIGHT OR INTEREST IN ANY MINERAL, MINERAL RIGHTS, OR RELATED MATTERS, INCLUDING BUT NOT LIMITED TO OIL, GAS, COAL, AND OTHER HYDROCARBONS. 4. REAL PROPERTY TAXES WHICH MAY BE ASSESSED LEVIED AND EXTENDED ON ANY "SUBSEQUENT AND/OR OCCUPANCY ROLL'~WITH RESPECT TO IMPROVEMENTS OOMPLETED DURING THE YEAR V-'HICH ESCAPED ASSESSMENT ON THE REGULAR ASSESSMENT ROLL, WHICH ARE lIOT YET DUE AND PAYABLE. 5. LIENS AND ASSESSMENTS OF THE FOLLOWING DISTRICT AtiD THE RIGHTS AND POWERS THEREOF AS PROVIDED BY LAW. NO DELINQUENCIES APPEAR IN THE COUNTY RECORDER'S OFFICE. DISTRICT: SETTLERS IRRIGATION DISTRICT (344-2471) 6. AN EASEMENT CONTAINING. CERTAIN TERMS, CONDITIONS AND PROVISIONS AFFECTING A PORTION•OF SAID PREMISES AND FOR THE PURPOSES STATED HEREIN. FOR: JAMES R. HOLLISTER A!!D KAREN L. HOLLISTER, HUSBAND AND WIFE IN FAVOR OF: PARCEL II RECORDED: JUNE 28, 1991 INSTRUMENT NO.: 9135286 l AFFECTS": COMMENCING AT THE NORTHWEST CORNER OF THE NORTHWEST 1/4 OF THE SOUTHWEST 1/4; THENCE SOUTH 0 DEGREES 00'11' EAST 444.12 FEET TO THE REAL' POINT OF BEGINNING OF THIS EASEMENT. THENCE NORTH 89 DEGREES 50'05,' EAST 1,327.00 FEET TO A POINT OF CURVATURE; EXHIBIT A TO WARRANTY DEED L~ THENCE ALONG A CURVE TO THE RIGHT 496.52 FEET, SAID CURVE HAVING A RADIUS OF 350.00 FEET, A CENTRAL ANGLE OF 81 DEGREES 16'53", TANGENTS OF 300.42 FEET, AND A CHORD OF 455.92 FEET Nd-IICH BEARS SOUTH 49 DEGREES 31'28" EAST TO A POINT OF REVERSE CURVATURE; THENCE ALONG A CURVE TO THE LEFT 15.95 FEET, SAID CURVE HAVING A RADIUS OF 20.00 FEET,.A CENTRAL ANGLE OF 45 DEGREES 42'15', TANGENTS OF 8.43 FEET AND A CHORD OF 15.53 FEET WHICH BEARS SOUTH 31 DEGREES 44'10' EAST TO A POINT OF REVERSE CURVATURE; THENCE ALONG A CURVE TO THE RIGHT 126.31 FEET, SAID CURVE HAVING A RADIUS OF 50.00 FEET, A CENTRAL ANGLE OF 144 DEGREES 44'09", TANGENTS _ OF 157.31 AND A CHORD OF 95.30 FEET WHICH BEARS SOUTH 17 DEGREES 46'18" WEST TO A POINT; THENCE SOUTH 0 DEGREES 44'56" EAST 10.00 FEET TO A POINT; THENCE ALONG A CURVE TO THE LEFT 151.41 FEET, SAID CURVE HAVING A RADIUS OF 60.00 FEET, A CENTRAL ANGLE OF 144 DEGREES 35'11", TANGENTS OF 187.93 FEET AND A CHORD OF 114.32 FEET WHICH BEARS NORTH 17 DEGREES 42'18" EAST TO A POINT OF REVERSE CURVATURE; THENCE ALONG A CURVE TO THE RIGHT 7.98 FEET, SAID CURVE HAVING A RADIUS OF 10.00 FEET, A CENTRAL ANGLE OF 45 DEGREES 42'15", TANGENTS OF 4.21 FEET AND A CHORD OF 7.77 FEET WHICH BEARS NORTH 31 DEGREES 44'10" WEST TO A POINT OF REVERSE CURVATURE; THENCE ALONG A CURVE TO THE LEFT 510.71 FEET, SAID CURVE HAVING A RADIUS OF 360.00 FEET, A CENTRAL ANGLE OF 81 DEGREES 16'53", TANGENTS OF 309.00 FEET AND A CHORD OF 468.95 FEET WHICH BEARS NORTH 49 DEGREES 31'28" WEST TO A-POINT OF TANGENCY; THENCE SOUTH 89 DEGREES 50'05" WEST 1326.97 FEET TO A POINT ON THE WEST LINE OF SAID SW 1/4; THENCE SOUTH 0 DEGREES 00'11" EAST 10.00 FEET TO THE REAL POINT OF BEGINNING OF THIS EASEMENT. 7, AN. EASEMENT CONTAINING CERTAIN TERMS, CONDITIONS AND PROVISIONS AFFECTING A PORTION OF SAID PREMISES AND FOR THE PURPOSES STATED HEREIN. FOR: A RIGHT OF WAY AND EASEMENT TO CONSTRUCT AND MAINTAIN A GAS DI STRIBUTION LINE IN FAVOR OF: INTERMOUNTIAN GAS COMPANY RECORDED: DECEMBER 31, 1991' INSTRUMENT NO.: 9200739 $. AN EASEMENT CONTAINING CERTAIN A PORTION OF SAID PREMISES AND FOR: INTERMOUNTIAN GAS COMPANY IN FAVOR OF: A RIGHT OF WAY AND GAS DISTRIBUTION LINE RECORDED: JANUARY 6, 1992 INSTRUMENT NO.: 9200740 TERMS, CONDITIONS AND PROVISIONS AFFECTING FOR THE PURPOSES STATED HEREIN. EASEMENT TO CONSTRUCT AND MAINTAIN A 9. SUBJECT TO RIGHTS OF WAY AS DISCLOSED BY AVAILABLE MAPS. FOR: NOURSE LATERAL LOCATION: NORTHERLY BOUNDARY 10. SUBJECT TO TENANTS RIGHT OF POSSESSION. PIONEER TITLE J. EOfS~E,1Df~!~0~~ ~~~~ ~~ a ~ ~~~ ~: ~~~ R~PD£D-FEQU£5T aF F££ D£Pll7Y 9035491 • AFFIDAVIT OF LEGAL INTERE~ STATE OF IDAHO COUNTY OF ADA I ~, v<<"i 5'~"~nC ~v1V1'C~~ ~ TDi /~'4' SG~t.oo~ ~ t5'~r+G~' Z ~ ~ ~ ~ /'''C~"'~C i 0.Yl tloAC' (name) (address) being first duly sworn upon /~e''"' ~,~' a"` -Z~ ~.~'`~° oath, depose and say: (city) (state) 1. That I am the record owner of the property described on the attached, and I grant my permission to: ./~e~-~ dean Ch~-~ r , 3~'on ~ . ~~ ru s `~ Vro v~ (~ me) (address) to submit the accompanying application pertaining to that property. Dated this 2. I agree to indemnify, defend and hold the City of Meridian and it's employees harmless from any claim or liability resulting from any dispute as to the statements contained herein or as to the ownership of the property, which is the subject of the application. Z Z+tid day of Fe,~~ a r~ , 200z- r (Signature SUBSCRIBED AND SWORN to before me the day and year first above written. '~~fffffffl/f~ ~ d-~~ •.• ~N D ~SC.~$r'•,~ Notary Public Idaho ~•~ ~~•.•''~ •••.~Gc''~ Residing at Mer;~.~a~-- ~~~.g~b 3 Z zoo ~.~ ~ ~ : My Commission Expires: ~ 3 .k i G • :• ~'UBti1 •~ O ~: ••.,~ a Tg o~ i~?.. Re>>. 2/1/U2 CONTENTS OF CZC APPLICATION (Incomplete applications will not be processed) An application for a Certificate of Zoning Compliance shall be filed with the Planning and Zoning staff by the owner of the property or the applicant of the proposed use. The application shall contain the following information: / 1. Completed and signed CZC application form. 2. The last deed of record for the subject property. / 3. Notarized Affidavit of Legal Interest (attached). ~ 4. Four (4) copies of a detailed site plan, drawn to a scale of not less than 1"=50'. Also include an 8'/i" x 11" reduction. , 5. Three (3) copies of the landscape design in compliance with the Landscape Ordinance, ~ drawn to a scale of not less than 1"=50'. See attached landscape submittal requirements. ,/ 6. Three (3) copies of irngation performance specifications in compliance with the Landscape Ordinance. N/A 7. Written approval or a stamped site plan from Sanitation Service Company (SSC) indicating that the designs of the trash enclosure and access drive are acceptable. No GE-I A N ~I G PRoM r;x IsTIN ~ N f A 8. A calculations table that shall list the number of parking stalls, building size, lot size, landscaping, open space, setbacks, fencing, screening and coverage. N o G hl A ~! C.1 G F(LflM ~S<ls'(INI~ 9. A written statement from the applicant detailing the proposed use(s) of the property. Please list as many details as possible. N o -~' ~: ~ rJ T 12 ~ S I ~(' G I s ,A p P R-n X. ^ ,/ 10. A fee of $60.00. ~ q~0 AGtz-G~~i . ~(iG~ No T~5 ~ 2 o N 51 T~ I~ ~ A -J F~ ~- ~ 15'(A N G L 'fo No R-'f-N A N t~ ACRD Acceptance: Applicant shall be responsible for meeting the requirements of ACRD as they pertain to this application. All impact fees, if any, shall be paid prior to the issuance of a building permit. If any changes must be made to the site plan to accommodate the ACRD requirements, a new site plan shall be submitted to the City of Meridian Planning & Zoning Department for approval prior to the issuance of a building permit. 2 2e~,. 2/1/0? aroa'Nwakaw ,ru~~ ~-•.~„ z'on iowaa ioorae uaor ~;."~ ~".,~; ' M' Nowaav woodssv~ ~b~~aaea~~n , lOOH~S F+JIi NVI~ ~m~~~~p=~~ _ ammaabm~~ Y W JJ ~7 0 avav 3n. J ~ 3 $ W 0 N k po gg w ~ ~~ '`Zg~~~ w kPa"g o: w ~ g ~¢~ g z ~ ~~:~ ~4x~ w ~®§z6 ffy4~~~~ Hwy ~ ~~u~$~@ 9 4~4 IY ~~ ~ 1 I ~~s ~® I ~~~ ~ I I i = i ~, ;~-r_ $~~ `J ~ ~ ~~_ I i ~ ~ ~ ~ I ~ i ~ ~ ~ ~ ~' ~-~ - ~ ~~ I ~ ~~ IIII ~ /i i~' t I I I I I I I~ I I I I ~ ~~ I~ I ~ I I I~ I I i x i ~ g t '~ 4 4 4 ',IP ~ g3~ 4 4 8 ai 00000 0 0 0 0 0000 O 9~ K E • • SECTION 02810 -IRRIGATION SYSTEMS PART1-GENERAL 1.1. RELATED DOC[.~MENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section. Items and / or irrigation systems /components not specified herein are described on the Drawings and are required to be provided under the provision of this Specification Section. 1.2. SUMMARY A. This Section includes valves, piping, sprinklers, specialties, accessories, controls, and wiring for landscaping irrigation systems. B. The irrigation system for this project shall be designed by the irrigation system contractor to meet the requirements specified herein and to irrigate the areas indicated on the Drawings. (See Paragraph 3.7.A. belo~.v) The irrigation system design shall meet the requirements of all agencies having jurisdiction over the Work. The Contractor shall provide all items necessary to meet all requirements of such agencies at no additional cost to the Owner. 1.3. DEFINITIONS A. Supply Piping: Piping from water source to connection to irrigation system pressure piping. Piping is under same pressure as water supply. Piping in this category is not included in this Section. B. Mainline Pipe: Piping downstream from pump or supply that supplies water to irrigation system valves. C. Pressure Piping: Piping downstream from supply piping to and including control valves. Piping is under irrigation system pressure. Piping in this category includes pressure regula±ors, water meters, and backflow preventers, when used. D. Lateral Piping: Piping downstream from control valves to irrigation system sprinklers, emitters, devices, and drain valves. Piping is under pressure (less than pressure piping) during flow. IRRIGATION SYSTEMS 02810 - 1 . i • E. Isolation valves: Manual valves that are located in main line that allows owner to isolate portions of the mainline from the rest of the system. F. Control Valve /Zone Valve: Manual or automatic (electrically operated) valve for control water flow to irrigation system zone and / or zone laterals. G. Quick coupler: A coupler off the main line that allows hose connection to the Irrigation System. H. Drain Piping: Downstream from circuit piping drain valves. Piping is not under pressure. I. Drain Valve: Manual or automatic (pressure operated) drain valve for draining of irrigation system circuit piping. 1.4. SYSTEM PERFORMANCE REQUIREMENTS A. Minimum Water Coverage With equal precipitation rates: Not less than: 1. Grass Areas: 100 percent. 2. Other Planting Areas: 100 percent. B. Components and Installation: Capable of producing piping systems with the following minimum working pressure ratings except where indicated otherwise. 1. Pressure Piping: 150 psig (1035 kPa). 2. Circuit and Drain Piping: 100 psig (690 kPa). C. Heads and nozzles shall be laid out and adjusted to provide proper spray and equal precipitation rates over the entire planted area of the project. 1.5. SUBMITTALS A. General: Submit the following according to the Conditions of the Contract and Division 1 Specification Sections. B. Product data including pressure rating, rated capacity, settings, and electrical data of selected models for the following: 1. Valves, including general-duty, underground, manual and automatic control types, and valve boxes. 2. Sprinklers and Nozzles. IRRIGATION SYSTEMS 02810 - 2 3. Controls, including controller wiring diagrams. 4. Wiring. C. Wiring diagrams for electrical controllers, valves, and devices. D. Shop drawings showing the complete irrigation system, including plan layout and locations, types, sizes, capacities, and flow characteristics ofeach and all imgation system components. Include water meters, backflow preventers, valves, piping, sprinklers and devices, accessories, controls, and wiring. Show areas of sprinkler spray and over spray. Such shop drawings shall be newly drafted originals and shall not be in the form of `marked up' drawings from the Contract Documents. E. Coordination drawings showing piping and major system components. Indicate interface and spatial relationship between piping, system components, adjacent utilities, and proximate structures. F. Maintenance data for inclusion in "Operating and Maintenance Manual" for the following: 1. Backflow preventers, including instructions for testing. 2. Automatic control valves. 3. Sprinklers. 4. Controllers. 1.6. QUALITY ASSURANCE A. Comply with requirements of utility supplying water for prevention of backflow and backsiphonage. B. Comply with requirements of all agencies having jurisdiction over irrigation systems. C. Installer Qualifications: Engage an experienced Installer who has completed irrigation systems similar in material, design, and extent to that indicated for Project that have resulted in construction with a record of successful in-service performance. D. Listing/Approval Stamp, Label, or Other Marking: On equipment, specialties, and accessories made to specified standards. E. Listing and Labeling: Equipment, specialties, and accessories that are listed and labeled. IRRIGATION SYSTEMS 02810 - 3 1. The Terms "Listed" and "Labeled": As defined in "National Electrical Code," Article 100. 1.7. PROJECT CONDITIONS A. Perform site research, research public utility records, and verify existing utility locations. Verify that irrigation system piping may be installed in compliance with original design and referenced standards. B. Site Information: Reports on subsurface condition investigations made during design of the Project are available at the office of the Architect for informational purposes only; data in reports is not intended as representations or warranties of accuracy or continuity of conditions (between soil borings). Owner assumes no responsibility for interpretations or conclusions drawn from this information. 1.8. SEQUENCING AND SCHEDULING A. Coordinate irrigation systems work with landscape work specified in Division 2 Section "Landscape Work." PART 2 -PRODUCTS 2.1. MANUFACTURERS A. Manufacturers: Subject to compliance with requirements, provide products by one ofthe following: 1. Gate Valves for Underground Installation: a. American Darling Valve Div., American Cast Iron Pipe Co. b. Clow Valve Co. Div., McWane, Inc. c. Kennedy Valve Div., McWane, Inc. d. Stockham Valves & Fittings, Inc. e. Waterous Co. f. Leemco g. Harco 2. Valves for above ground and Pit Installation: IRRIGATION SYSTEMS 02810 - 4 a. Grinnell Supply Sales Co., Grinnell Corp. b. Jomar International, Ltd. c. Kitz Corp. of America. d. Lunkenheimer Co. e. Milwaukee Valve Co., Inc. f Nibco, Inc. g. Hammond Valve Div., Prairie Manufacturing Corp. h. Red-White Valve Corp. i. Stockham Valves & Fittings, Inc. j. Walworth Co. k. Watts Regulator Co. 1) Wm. Powell Co. 3. Automatic Control Valves: a. Rain Bird Sprinkler Mfg. Corp. 4. Control Valve Boxes a. Ametek by Plymouth Products Div., AMETEK. b. Applied Engineering Products. c. Brooks Products, Inc., Polyplastics Div. d. Carson Industries, Inc. e. DFW/I~I by Hefco Plastics, Inc. f. National Diversified Sales, Inc. g. Pepco Water Conservation Products, Inc. h. Quazite Div., Morrison Molded Fiber Glass Co. IRRIGATION SYSTEMS 02810 - 5 5. Sprinklers: a. Rain Bird Sprinkler 1~1fg. Corp. 6. Controllers: a. Rain Bird Sprinkler Mfg. Corp. B. Products by other manufacturers are subject to approval prior to bidding. 2.2. P1PES AND TUBES A. Refer to Part 3 Article "Piping Applications" for identification of systems where pipe and tube materials specified below are used. B. Polyvinyl Chloride (PVC) Plastic Pipe: Schedule 40. C. Polyvinyl Chloride (PVC) Plastic Pipe: 4" `Twinseal' IPS Pressure rated gasketed PVC 1120 Sloped to drain, bed in sand. 2.3. JOINING MATERIALS A. Refer to Division 15 Section "Basic Mechanical Materials and Methods" for joining materials not included in this Section. B. Solvent Cement: ASTM F 656 primer and ASTM D 2564 solvent cement in color other than orange. 2.4. VALVES A. General: Valves are for general-duty and underground applications. Refer to "Valve Applications" Article for locations of various valve types specified in this Article. Refer to "Control Valves" Article for control valves and accessories and "Backflow Preventers" Article for backflow preventer valves. B. Valve Boxes: High impact, high-density structural foam polyethylene with overlapping top cover and UV inhibitors. Size according to device. C. Bronze, Non-rising Stem Gate Valves, 2 Inches (50 mm) and Smaller: MSS SP-80, Type 1, solid wedge; non-rising, copper-silicon-alloy stem; Class 125, body and screw bonnet of ASTM B 62 cast bronze, with threaded or solder joint ends. Include polytetrafluoroethylene (PTFE)-impregnated packing, brass packing gland, and malleable-iron hand wheel. IRRIGATION SYSTEMS 02810 - 6 D. Bronze, Rising-Stem Gate Valves, 2 Inches (50 mm) and Smaller: MSS SP-80, Type 2, solid wedge; rising, copper-silicon-allo~• stem; Class 125, body and screw bonnet of ASTM B 62 cast bronze, with threaded or solder joint ends. Include polytetrafluoro- ethylene (PTFE)-impregnated packing„ brass packing gland, and malleable-iron hand wheel. 2. ~. CONTROL VALVES A. Description: Manufacturer's standard control valves for laterals, of type and size indicated, and as follows: Manual Control Valves: MSS SP-S0, Class 125, globe valves. 2. Automatic Control Valves: `Rainbird' 150 / 200-PESB-NP-HAN. 3. Manual Drain Valves: MSS SP-80, Class 125, gate valves, on offset reducers. B. Control Valve Boxes: High Impact, high density structural foam polyethylene with overlapping top cover and UV inhibitors. Size according to device. 1. Drainage Backfill: Cleaned gravel or crushed stone, graded from 3 inches (75 mm) maximum to 3/4 inch (19 mm) minimum. 2.6. SPRINKLERS A. Description: Manufacturer's standard sprinklers designed to provide uniform coverage over entire area of spray shown on Drawings at available water pressure, as follows: 1. Pop-up, Rotary Spray: `Rainbird' Falcon 6504 Rotor. Model Number F4-FC or PC-SS-NP with `Rain curtain' Nozzle and purple non-potable cap. Type sized per system requirements. Install with Rainbird TSJ-12 Unitized swing joint These heads to be used in areas that will accommodate large radius(See drawings for installation details). 2. Pop-up Rotary Spray: `Rainbird' 5000 series Rotor. Model number 5004 - FC or PC-N with `Rain curtain' Nozzle and purple non-potable cap. Type sized per system requirements. With Rainbird TSJ-12 Unitized swing joint These heads to be used in other grass areas without large radius issues. (See Drawings for installation details). 3. Bubbler: `Rainbird' 1400 Series Umbrella Pattern with built in pressure regulator. IRRIGATION SYSTEMS 02810 - 7 4. Pop-Up, Spray: `Rainbird' 1800-PRS Series. Pop up Spray with Built-In Pressure regulator. 5. Quick Coupler valve (QC): `Rainbird' 44NP with stainless steel straps in separate valve box. (See Drawings for details). '.7. AUTOI~'IATIC CONTROL S~'STE~~1 A. Description: Low-voltage controller system, made for control of irrigation system automatic control valves. Controller operates on 120 volts a.c. building power system, provides 24 volts a.c. power to control valves, and includes stations for at least the number of control valves indicated. B. Use existing Controller for new and modified zones. C. Wiring: UL 493, solid copper conductor, insulated cable, suitable for direct burial. 1. Feeder Circuit Cables: Type UF, No. 12 AWG minimum, between building and controllers. 2. Low-Voltage, Branch Circuit Cables: Type UF, No. 14 AWG minimum, between controllers and automatic control valves. Jacket color is other than feeder-circuit-cable jacket color. Furnish cables with jackets of different colors for multiple cable installation in same trench. 3. Splicing Materials: Pressure-sensitive thermoplastic tape and other materials required to make specified connections. 2.8. IDENTIFICATION A. Refer to Division 2 Section "Earthwork" for plastic underground warning tapes. PART 3 -EXECUTION 3.1. EXAMINATION A. Investigate and determine available water supply water pressure and flow characteristics. 3.2. PREPARATION A. Set stakes to identify proposed sprinkler locations. Obtain Architect's approval before excavation. IRRIGATION SYSTEMS 02810 - 8 ~ ~ 3.3. EARTHWORK A. Conform to Excavation, trenchin„ and backfilling requirements specified in Division 2 Section "Earthwork." B. Conform to Underground warning tape installation requirements specified in Division 2 Section "Earthwork." 3.4. SLEEVES AT PAVING AND CONCRETE A. Install piping and control wiring in sleeves where crossing sidewalks, roadways, and parking lots. 1. Install piping sleeves prior to installing asphalt paving and / or concrete work. 3.5. PIPING APPLICATIONS A. Refer to Part 2 of this Section for detailed specifications for pipe and fittings products listed below. Use pipe, tube, fittings, and joining methods according to the following applications. Piping in pits and above ground may be joined with flanges instead of joints indicated. B. Use pipe, tube, fittings, and joining methods according to the following applications. C. Piping upstream of the zone control valves to the pump (irrigation mainline), use the following: 1. Polyvinyl Chloride (PVC) plastic pipe: 4" `Twinseal' IPS Pressure rated, gasketed, PVC 1120 -sloped to drain, bed in sand. D. Piping from the zone control valves to the sprinkler heads, (lateral lines) use the following: Polyvinyl Chloride (PVC) plastic pipe: Schedule 40. E. Drain Piping: Polyvinyl Chloride (PVC) plastic pipe: ASTM D 2241; PVC 1120, SDR 26,160 psig (1100 kPa) minimum pressure rating, with plain ends. F. Sleeves: ASTM D 1785, Schedule 40, polyvinyl chloride (PVC) plastic pipe; ASTM D 2466, Schedule 80, PVC plastic, socket-type fittings; and solvent-cemented joints. 3.6. JOINT CONSTRUCTION IRRIGATION SYSTEMS 02810 - 9 • A. Threaded Joints: Thread pipes with tapered pipe threads according to ASME B1.20.1, apply tape or joint compound, and apply wrench to valve ends into which pipes are being; threaded. B. Polyvinyl Chloride (PVC) Piping Solvent-Cemented Joints: Construct joints according to ASTNI D 2672 and AST~~I D 28~~. Handling of Solvent Cements, Primers, and Cleaners: Comply with procedures in ASTM F 402 for safe handling when joining plastic pipe and fittings with solvent cements. 3.7. PIPING SYSTEMS -COMMON REQUIREMENTS The Contractor shall design the irrigation system in accordance with this Performance Specification. The design shall show sizes, locations, and arrangements of all piping systems valves, heads, etc. The Contractor shall calculate friction loss, water hammer, and flow requirements and size piping and head spacing accordingly. 2. `Rainbird Falcon' 6504 Rotors shall be used in field areas, and at any location large enough to allow the use of the 50' Radius. 3. Provide isolation valves in appropriate areas so they may serve their function most efficiently. 4. Provide quick coupler valves per details on the Drawings to provide hose hook up and blow out connections. 5. All lateral piping shall be Schedule 40 PVC. 6. Irrigation subcontractor shall provide the first year winterizing of the system as a part of this Contract. 7. Refer to plans, details, and notes on the Drawings for additional design criteria and information. 8. On zones with rotors, do not place part circle rotors and full circle rotors on the same zone. Do not put pop-ups and rotors on the same zone. 9. Provide components having pressure rating equal to or greater than system operating pressure. 10. Install piping free of sags and bends. IRRIGATION SYSTEMS 02810 - 10 ~ ~ 1 1. Locate groups of pipes parallel to each other, spaced to permit valve servicing,. 12. Install fittings for changes in direction and branch connections. 13. Piping Connections: EYCept as otherwise indicated make piping connections as specified below. l . Provide unions, adjacent to supply side of each valve. 2. Provide flanges, adjacent to flanged valves and at final connection to each piece of equipment having flanged pipe connection. 3. Provide dielectric fittings to connect piping of dissimilar metals. 3.8. PIPING INSTALLATION A. Install underground polyvinyl chloride (PVC) plastic pipe according to ASTM D 2774. B. Lay piping on solid subbase, uniformly sloped without humps or depressions. 1. Install polyvinyl chloride (PVC) plastic pipe in dry weather when temperature is above 40 deg F (4 deg C). Allow joints to cure at least 24 hours at temperature above 40 deg F (4 deg C) before testing, unless otherwise recommended by manufacturer 2. Hand water covered trenches to ensure proper trench settings. C. Minimum Cover: Provide following minimum cover over top of buried piping: 1. Mainline Pressure Piping: Minimum of 24 inches below finished grade. Mainline shall run under Badly Lateral pipe in sleeve provided. 2. Lateral Circuit Piping: 18 inches (300 mm). 4. Sleeves: 24 inches (600 mm). D. Install piping and wiring under sidewalks and paving in sleeves. E. Provide underground warning tapes full length of all pressure piping. 3.9. VALVE APPLICATIONS A. Valve types both manual & automatic to be used are as follows: IRRIGATION SYSTEMS 02810 - 11 ~ ~ 1. Below grade (underground) 1~'lanual Valves 3 Inches (80 mm) and Lar,er: AWWA, gate valves, nonrising stem, with stem nut and valve box. 2. Below grade (underground) Automatic Valves >Rainbird= 200-PESB-NP-H.aN. .10. VALVE INSTALLATION A. Valves: Install underground valves in 10" circular valve boxes or large rectangular valve boxes. B. Control Valves: Install in valve control valve boxes, per detail on drawings. Arrange for easy adjustment and removal. Install union on downstream side. 3.11. SPRINKLER INSTALLATION A. Sprinklers: Flush circuit piping with full head of water and install sprinklers after hydrostatic test is completed. 1. Install lawn sprinklers at manufacturer's recommended heights. 2. Install shrubbery sprinklers at heights indicated. 3. Locate part-circle sprinklers to maintain a minimum distance of4 inches (100 mm) from walls and 2 inches (50 mm) from other boundaries, unless otherwise indicated. 3. Adjust heads for proper spray and equal precipitation rates in entire system. 3.12. AUTOMATIC CONTROL SYSTEM INSTALLATION A. Install controllers according to manufacturer's written instructions and as indicated. B. Install control wiring in same trench with mainline piping. 3.13. CONNECTIONS A. Connect piping to sprinklers, devices, valves, control valves, specialties, and accessories. B. Connect water supplies to irrigation systems. Include backflow preventers on potable water supplies. C. Minimum requirements for electrical installations are specified in Division 16. IRRIGATION SYSTEMS 02810 - 12 D. Ground systems according to Division 16 Section "Grounding." 3.1=1. FIELD QUALITY CONTROL A. Testing: Perform hydrostatic test of piping and valves before backfilling trenches. Piping may be tested in sections to expedite work. Cap and subject the piping system to a static water pressure of 50 psig (34~ kPa) above the operating pressure without exceeding pressure rating of piping system materials. Isolate test source and allow to stand for 4 hours. Leaks and loss in test pressure constitute defects that must be repaired. 2. Repair leaks and defects with ne~v materials and retest system or portion thereof until satisfactory results are obtained. 3.15. CLEANING AND ADJUSTING A. Flush dirt and debris from piping before installing sprinklers and other devices. B. Adjust automatic control valves to provide flow rate of rated operating pressure required for each sprinkler circuit. C. Carefully adjust lawn sprinklers so they w-i11 be flush with, or not more than 2 inch (13 mm) above, finish grade after completion of landscape work. D. Adjust settings of controllers and automatic control valves. 3.16. COMMISSIONING A. Starting Procedures: Follow manufacturer's written procedures. If manufacturers prescribe no procedures, proceed as follows: Verify that specialty valves and their accessories have been installed correctly and operate correctly. 2. Verify that specified tests of piping are complete. 3. Check that sprinklers and devices are correct type. 4. Check that damaged sprinklers and devices have been replaced with new materials. 5. Check that potable water supplies have correct type backflow preventers. IRRIGATION SYSTEMS 02810 - 13 .~ 6. Energize circuits to electrical equipment and devices. 7. Adjust operating controls. B. Operational Testing: Perform operational testing after hydrostatic testing is completed, backfill is in place, and sprinklers are adjusted to final position. 3.17. DEMONSTRATION A. Demonstrate to Architect that system meets coverage requirements and that automatic controls function properly. B. Train the Owner's personnel in the operation and maintenance of equipment, sprinklers, specialties, and accessories. C. Schedule demonstration and training meetings at least seven (7) days' in advance of such demonstration and training. 3.18. AS BUILT DRAWINGS A. The Contractor shall maintain complete and accurate as built drawings indicating exact piping runs, valve and head locations, zoning details, etc. for the irrigation system as installed. Such as built drawings shall be submitted as a condition of Substantial Completion of the Work. END OF SECTION 02810 IRRIGATION SYSTEMS 02810 - 14 • SECTION 02810 -IRRIGATION SYSTEMS PART 1 -GENERAL 1.1. RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section. 1. Items and / or irrigation systems /components not specified herein are described on the Drawings and are required to be provided under the provision of this Specification Section. 1.2. SUMMARY A. This Section includes valves, piping, sprinklers, specialties, accessories, controls, and wiring for landscaping irrigation systems. B. The irrigation system for this project shall be designed by the irrigation system contractor to meet the requirements specified herein and to irrigate the areas indicated on the Drawings. (See Paragraph 3.7.A. below) The irrigation system design shall meet the requirements of all agencies having jurisdiction over the Work. The Contractor shall provide all items necessary to meet all requirements of such agencies at no additional cost to the Owner. 1.3. DEFIlVITIONS A. Supply Piping: Piping from water source to connection to irrigation system pressure piping. Piping is under same pressure as water supply. Piping in this category is not included in this Section. B. Mainline Pipe: Piping downstream from pump or supply that supplies water to irrigation system valves. C. Pressure Piping: Piping downstream from supply piping to and including control valves. Piping is under irrigation system pressure. Piping in this category includes pressure regulators, water meters, and backflow preventers, when used. D. Lateral Piping: Piping downstream from control valves to irrigation system sprinklers, emitters, devices, and drain valves. Piping is under pressure (less than pressure piping) during flow. IRRIGATION SYSTEMS 02810 - 1 • E. Isolation valves: 1~lanual valves that are located in main line that allows owner to isolate portions of the mainline from the rest of the system. F. Control Valve /Zone Valve: Manual or automatic (electrically operated) valve for control water flow to irrigation system zone and / or zone laterals. G. Quick coupler: A coupler off the main line that allows hose connection to the Irrigation System. H. Drain Piping: Downstream from circuit piping drain valves. Piping is not under pressure. I. Drain Valve: Manual or automatic (pressure operated) drain valve for draining of irrigation system circuit piping. 1.4. SYSTEM PERFORMANCE REQUIREMENTS A. Minimum Water Coverage With equal precipitation rates: Not less than: 1. Grass Areas: 100 percent. 2. Other Planting Areas: 100 percent. B. Components and Installation: Capable of producing piping systems with the following minimum working pressure ratings except where indicated otherwise. 1. Pressure Piping: 150 psig (1035 kPa). 2. Circuit and Drain Piping: 100 psig (690 kPa). C. Heads and nozzles shall be laid out and adjusted to provide proper spray and equal precipitation rates over the entire planted area of the project. 1.5. SUBMITTALS A. General: Submit the following according to the Conditions of the Contract and Division 1 Specification Sections. B. Product data including pressure rating, rated capacity, settings, and electrical data of selected models for the following: 1. Valves, including general-duty, underground, manual and automatic control types, and valve boxes. 2. Sprinklers and Nozzles. IRRIGATION SYSTEMS 02810 - 2 3. Controls, including controller wiring dia~,rams. 4. Wiring. C. Wiring diagrams for electrical controllers, valves, and devices. D. Shop drawings showing the complete imgation system, including plan layout and locations, types, sizes, capacities, and flow characteristics of each and all irrigation system components. Include water meters, backtlow preventers, valves, piping, sprinklers and devices, accessories, controls, and wiring. Show areas of sprinkler spray and over spray. 1. Such shop drawings shall be newly drafted originals and shall not be in the form of `marked up' drawings from the Contract Documents. E. Coordination drawings showing piping and major system components. Indicate interface and spatial relationship between piping, system components, adjacent utilities, and proximate structures. F. Maintenance data for inclusion in "Operating and Maintenance Manual" for the following: Backflow preventers, including instructions for testing. 2. Automatic control valves. 3. Sprinklers. 4. Controllers. 1.6. QUALITY ASSURANCE A. Comply with requirements of utility supplying water for prevention of backflow and backsiphonage. B. Comply with requirements of all agencies having jurisdiction over irrigation systems. C. Installer Qualifications: Engage an experienced Installer who has completed irrigation systems similar in material, design, and extent to that indicated for Project that have resulted in construction with a record of successful in-service performance. D. Listing/Approval Stamp, Label, or Other Marking: On equipment, specialties, and accessories made to specified standards. E. Listing and Labeling: Equipment, specialties, and accessories that are listed and labeled. IRRIGATION SYSTEMS 02810 - 3 1. The Terms "Listed" and "Labeled": As defined in "National Electrical Code," Article 100. 1.7. PROJECT CONDITIONS A. Perform site research, research public utility records, and verify existin; utility locations. Verify that irrigation system piping may be installed in compliance with original design and referenced standards. B. Site Information: Reports on subsurface condition investigations made during design of the Project are available at the office of the Architect for informational purposes only; data in reports is not intended as representations or warranties of accuracy or continuity of conditions (between soil borings). Owner assumes no responsibility for interpretations or conclusions drawn from this information. 1.8. SEQUENCING AND SCHEDULING A. Coordinate irrigation systems work with landscape work specified in Division 2 Section "Landscape Work." PART 2 -PRODUCTS 2.1. MANUFACTURERS A. Manufacturers: Subject to compliance with requirements, provide products by one ofthe following: 1. Gate Valves for Underground Installation: a. American Darling Valve Div., American Cast Iron Pipe Co. b. Clow Valve Co. Div., McWane, Inc. c. Kennedy Valve Div., McWane, Inc. d. Stockham Valves & Fittings, Inc. e. Waterous Co. f. Leemco g. Harco 2. Valves for above ground and Pit Installation: IRRIGATION SYSTEMS 02810 - 4 a. Grinnell Supply Sales Co., Grinnell Corp. b. Jomar International, Ltd. c. Kitz Corp. of America. d. Lunkenheimer Co. e. Milwaukee Valve Co., Inc. f. Nibco, Inc. g. Hammond Valve Div., Prairie Manufacturing Corp. h. Red-White Valve Corp. i. Stockham Valves & Fittings, Inc. j. Walworth Co. k. Watts Regulator Co. 1) Wm. Powell Co. 3. Automatic Control Valves: a. Rain Bird Sprinkler Mfg. Corp. 4. Control Valve Boxes a. Ametek by Plymouth Products Div., AMETEK. b. Applied Engineering Products. c. Brooks Products, Inc., Polyplastics Div. d. Carson Industries, Inc. e. DFW/HPI by Hefco Plastics, Inc. f. National Diversified Sales, Inc. g. Pepco Water Conservation Products, Inc. h. Quazite Div., Morrison Molded Fiber Glass Co. IRRIGATION SYSTEMS 02810 - 5 L~ 5. Sprinklers: a. Rain Bird Sprinkler Mfg. Corp. 6. Controllers: a. Rain Bird Sprinkler Mfg. Corp. B. Products by other manufacturers are subject to approval prior to bidding. 2.2. PIPES AND TUBES A. Refer to Part 3 Article "Piping Applications" for identification of systems where pipe and tube materials specified below are used. B. Polyvinyl Chloride (PVC) Plastic Pipe: Schedule 40. C. Polyvinyl Chloride (PVC) Plastic Pipe: 4" `Twinseal' IPS Pressure rated gasketed PVC 1120 Sloped to drain, bed in sand. 2.3. JOINING MATERIALS A. Refer to Division 15 Section "Basic Mechanical Materials and Methods" for joining materials not included in this Section. B. Solvent Cement: ASTM F 656 primer and ASTM D 2564 solvent cement in color other than orange. 2.4. VALVES A. General: Valves are for general-duty and underground applications. Refer to "Valve Applications" Article for locations of various valve types specified in this Article. Refer to "Control Valves" Article for control valves and accessories and "Backflow Preventers" Article for Backflow preventer valves. B. Valve Boxes: High impact, high-density structural foam polyethylene with overlapping top cover and UV inhibitors. Size according to device. C. Bronze, Non-rising Stem Gate Valves, 2 Inches (50 mm) and Smaller: MSS SP-80, Type 1, solid wedge; non-rising, copper-silicon-alloy stem; Class 125, body and screw bonnet of ASTM B 62 cast bronze, with threaded or solder joint ends. Include polytetrafluoroethylene (PTFE)-impregnated packing, brass packing gland, and malleable-iron hand wheel. IRRIGATION SYSTEMS 02810 - 6 ~ ~ D. Bronze, Rising-Stem Gate Valves, 2 Inches (~0 mm) and Smaller: MSS SP-80, Type 2, solid wedge; rising, copper-silicon-alloy stem; Class 125, body and screw bonnet of AST1~4 B 62 cast bronze, with threaded or solder joint ends. Include polytetrafluoro- ethylene (PTFE)-impregnated packing, brass packing gland, and malleable-iron hand wheel. 2.~. CONTROL VALVES A. Description: Manufacturer's standard control valves for laterals, of type and size indicated, and as follows: Manual Control Valves: MSS SP-80, Class 125, globe valves. 2. Automatic Control Valves: `Rainbird' 150 / 200-PESB-NP-HAN. 3. Manual Drain Valves: MSS SP-80, Class 125, gate valves, on offset reducers. B. Control Valve Boxes: High Impact, high density structural foam polyethylene with overlapping top cover and UV inhibitors. Size according to device. Drainage Backfill: Cleaned gravel or crushed stone, graded from 3 inches (75 mm) maximum to 3/4 inch (19 mm) minimum. 2.6. SPRINKLERS A. Description: Manufacturer's standard sprinklers designed to provide uniform coverage over entire area of spray shown on Drawings at available water pressure, as follows: Pop-up, Rotary Spray: `Rainbird' Falcon 6504 Rotor. Model Number F4-FC or PC-SS-NP with `Rain curtain' Nozzle and purple non-potable cap. Type sized per system requirements. Install with Rainbird TSJ-12 Unitized swing joint These heads to be used in areas that will accommodate large radius(See drawings for installation details). 2. Pop-up Rotary Spray: `Rainbird' 5000 series Rotor. Model number 5004 - FC or PC-N with `Rain curtain' Nozzle and purple non-potable cap. Type sized per .system requirements. With Rainbird TSJ-12 Unitized swing joint These heads to be used in other grass areas without large radius issues. (See Drawings for installation details). 3. Bubbler: `Rainbird' 1400 Series Umbrella Pattern with built in pressure regulator. IRRIGATION SYSTEMS 02810 - 7 ~ ~ 4. Pop-Up, Spray: `Rainbird' 1800-PRS Series. Pop up Spray with Built-In Pressure regulator. 5. Quick Coupler valve (QC): `Rainbird' 44NP with stainless steel straps in separate valve box. (See Drawin,s for details). 2.7. AUTOiVIATIC CONTROL SY'STENI A. Description: Low-voltage controller system, made for control of irrigation system automatic control valves. Controller operates on 120 volts a.c. building power system, provides 24 volts a. c. power to control valves, and includes stations for at least the number of control valves indicated. B. Use existing Controller for new and modified zones. C. Wiring: iII.493, solid copper conductor, insulated cable, suitable for direct burial. 1. Feeder Circuit Cables: Type IIF, No. 12 AWG minimum, between building and controllers. 2. Low-Voltage, Branch Circuit Cables: Type IJF', No. 14 AWG minimum, between controllers and automatic control valves. Jacket color is other than feeder-circuit-cable jacket color. Furnish cables with jackets of different colors for multiple cable installation in same trench. 3. Splicing Materials: Pressure-sensitive thermoplastic tape and other materials required to make specified connections. 2.8. IDENTIFICATION A. Refer to Division 2 Section "Earthwork" for plastic underground warning tapes. PART 3 -EXECUTION 3.1. EXAMINATION A. Investigate and determine available water supply water pressure and flow characteristics. 3.2. PREPARATION A. Set stakes to identify proposed sprinkler locations. Obtain Architect's approval before excavation. IRRIGATION SYSTEMS 02810 - 8 ~ ~ 3.3. EARTHWORK A. Conform to Excavation, trenching, and backtilling requirements specified in Division 2 Section "Earthwork." B. Conform to Underground warning tape installation requirements specified in Division 2 Section "Earthwork." 3.4. SLEEVES AT PAVING AND CONCRETE A. Install piping and control wiring in sleeves where crossing sidewalks, roadways, and parking lots. 1. Install piping sleeves prior to installing asphalt paving and / or concrete work. 3.5. PIPING APPLICATIONS A. Refer to Part 2 of this Section for detailed specifications for pipe and fittings products listed below. Use pipe, tube, fittings, and joining methods according to the following applications. Piping in pits and above ground may be joined with flanges instead of joints indicated. B. Use pipe, tube, fittings, and joining methods according to the following applications. C. Piping upstream of the zone control valves to the pump (irrigation mainline), use the following: 1. Polyvinyl Chloride (PVC) plastic pipe: 4" `Twinseal' IPS Pressure rated, gasketed, PVC 1120 -sloped to drain, bed in sand. D. Piping from the zone control valves to the sprinkler heads, (lateral lines) use the following: 1. Polyvinyl Chloride (PVC) plastic pipe: Schedule 40. E. Drain Piping: Polyvinyl Chloride (PVC) plastic pipe: ASTM D 2241; PVC 1120, SDR 26,160 psig (1100 kPa) minimum pressure rating, with plain ends. F. Sleeves: ASTM D 1785, Schedule 40, polyvinyl chloride (PVC) plastic pipe; ASTM D 2466, Schedule 80, PVC plastic, socket-type fittings; and solvent-cemented joints. 3.6. JOINT CONSTRUCTION IRRIGATION SYSTEMS 02810 - 9 ~ ~ A. Threaded Joints: Thread pipes with tapered pipe threads according to ASME B 1.20.1, apply tape or joint compound, and apply wrench to valve ends into which pipes are being threaded. B. Polyvinyl Chloride (PVC) Piping Solvent-Cemented Joints: Construct joints according to ASTNI D 2672 and AST1~1 D 2555. Handling of Solvent Cements, Primers, and Cleaners: Comply with procedures in ASTM F 402 for safe handling when joining plastic pipe and fittings with solvent cements. 3.7. PIPING SYSTEMS -COMMON REQUIREMENTS 1. The Contractor shall design the irrigation system in accordance with this Performance Specification. The design shall show sizes, locations, and arrangements of all piping systems valves, heads, etc. The Contractor shall calculate friction loss, water hammer, and flow requirements and size piping and head spacing accordingly. 2. `Rainbird Falcon' 6504 Rotors shall be used in field areas, and at any location large enough to allow the use of the 50' Radius. 3. Provide isolation valves in appropriate areas so they may serve their function most efficiently. 4. Provide quick coupler valves per details on the Drawings to provide hose hook up and blow out connections. 5. All lateral piping shall be Schedule 40 PVC. 6. Irrigation subcontractor shall provide the first year winterizing of the system as a part of this Contract. 7. Refer to plans, details, and notes on the Drawings for additional design criteria and information. 8. On zones with rotors, do not place part circle rotors and full circle rotors on the same zone. Do not put pop-ups and rotors on the same zone. 9. Provide components having pressure rating equal to or greater than system operating pressure. 10. Install piping free of sags and bends. IRRIGATION SYSTEMS 02810 - 10 ~ ~ 1 1. Locate groups of pipes parallel to each other, spaced to permit valve servicing. 12. Install fittings for changes in direction and branch connections. 13. Piping Connections: Except as otherwise indicated make piping connections as specified below. 1. Provide unions, adjacent to supply side of each valve. 2. Provide flanges, adjacent to flanged valves and at final connection to each piece of equipment having flanged pipe connection. 3. Provide dielectric fittings to connect piping of dissimilar metals. 3.8. PIPING INSTALLATION A. Install underground polyvinyl chloride (PVC) plastic pipe according to ASTM D 2774. B. Lay piping on solid subbase, uniformly sloped without humps or depressions. 1. Install polyvinyl chloride (PVC) plastic pipe in dry weather when temperature is above 40 deg F (4 deg C). Allow joints to cure at least 24 hours at temperature above 40 deg F (4 deg C) before testing, unless otherwise recommended by manufacturer 2. Hand water covered trenches to ensure proper trench settings. C. Minimum Cover: Provide following minimum cover over top of buried piping: 1. Mainline Pressure Piping: Minimum of 24 inches below finished grade. Mainline shall run under Badly Lateral pipe in sleeve provided. 2. Lateral Circuit Piping: 18 inches (300 mm). 4. Sleeves: 24 inches (600 mm). D. Install piping and wiring under sidewalks and paving in sleeves. E. Provide underground warning tapes full length of all pressure piping. 3.9. VALVE APPLICATIONS A. Valve types both manual & automatic to be used are as follows: IRRIGATION SYSTEMS 02810 - 11 ~ ~ 1. Below grade (underground) IVlanual Valves 3 Inches (80 mm) and Larger: A~VWA, gate valves, nonrising stem, with stem nut and valve box. 2. Below grade (underground) Automatic Valves >Rainbird= 200-PESB-NP-HAN. 3.10. VALVE INSTALLATION A. Valves: Install underground valves in 10" circular valve boxes or large rectangular valve boxes. B. Control Valves: Install in valve control valve boxes, per detail on drawings. Arrange for easy adjustment and removal. Install union on downstream side. 3.11. SPRINKLER INSTALLATION A. Sprinklers: Flush circuit piping with full head of water and install sprinklers after hydrostatic test is completed. 1. Install lawn sprinklers at manufacturer's recommended heights. 2. Install shrubbery sprinklers at heights indicated. 3. Locate part-circle sprinklers to maintain a minimum distance of4 inches (100 mm) from walls and 2 inches (50 mm) from other boundaries, unless otherwise indicated. 3. Adjust heads for proper spray and equal precipitation rates in entire system. 3.12. AUTOMATIC CONTROL SYSTEM INSTALLATION A. Install controllers according to manufacturer's written instructions and as indicated. B. Install control wiring in same trench with mainline piping. 3.13. CONNECTIONS A. Connect piping to sprinklers, devices, valves, control valves, specialties, and accessories. B. Connect water supplies to irrigation systems. Include backflow preventers on potable water supplies. C. Minimum requirements for electrical installations are specified in Division 16. IRRIGATION SYSTEMS 02810 - 12 • • D. Ground systems according to Division 16 Section "Grounding." 3.14. FIELD QUALITY CONTROL A. Testing: Perform hydrostatic test of piping and valves before backtilling trenches. Piping may be tested in sections to expedite work. 1. Cap and subject the piping system to a static water pressure of 50 psig (345 kPa) above the operating pressure without exceeding pressure rating of piping system materials. Isolate test source and allow to stand for 4 hours. Leaks and loss in test pressure constitute defects that must be repaired. 2. Repair leaks and defects with new materials and retest system or portion thereof until satisfactory results are obtained. 3.15. CLEANING AND ADJUSTING A. Flush dirt and debris from piping before installing sprinklers and other devices. B. Adjust automatic control valves to provide flow rate of rated operating pressure required for each sprinkler circuit. C. Carefully adjust lawn sprinklers so they will be flush with, or not more than 2 inch (13 mm) above, finish grade after completion of landscape work. D. Adjust settings of controllers and automatic control valves. 3.16. COMMISSIONING A. Starting Procedures: Follow manufacturer's written procedures. If manufacturers prescribe no procedures, proceed as follows: 1. Verify that specialty valves and their accessories have been installed correctly and operate correctly. 2. Verify that specified tests of piping are complete. 3. Check that sprinklers and devices are correct type. 4. Check that damaged sprinklers and devices have been replaced with new materials. 5. Check that potable water supplies have correct type backflow preventers. IRRIGATION SYSTEMS 02810 - 13 ~ ~ 6. Energize circuits to electrical equipment and devices. 7. Adjust operating controls. B. Operational Testing: Perform operational testing after hydrostatic testing is completed, backfill is in place, and sprinklers are adjusted to final position. 3.17. DEMONSTRATION A. Demonstrate to Architect that system meets coverage requirements and that automatic controls function properly. B. Train the Owner's personnel in the operation and maintenance of equipment, sprinklers, specialties, and accessories. C. Schedule demonstration and training meetings at least seven (7) days' in advance of such demonstration and training. 3.18. AS BUILT DRAWINGS A. The Contractor shall maintain complete and accurate as built drawings indicating exact piping runs, valve and head locations, zoning details, etc. for the irrigation system as installed. Such as built drawings shall be submitted as a condition of Substantial Completion of the Work. END OF SECTION 02810 IRRIGATION SYSTEMS 02810 - 14 ~,'e'"'a~'A. ~ Ada County Highway District Dave Bivens, 1st Vice President Garden City ID 83714-6499 Judy Peavey-Derr, 2nd Vice President Phone (208) 387-6100 Susan S. Eastlake, Commissioner FAX (208) 387-6391 E-mail: tellus Sherry R. Huber, Commissioner , , . ~ ,~ .... @ACHD.ada.id.us March 1, 2002 TO: Joint School District 911 Meridian Street Meridian, ID 83642 SUBJECT: MCZC-02-008 Classroom addition to Meridian Charter High 3800 Locust Grove Road The Ada County Highway District (ACRD) staff has received and reviewed the application and site plan for the item referenced above and is submitting this no review letter in response to the lead agency's request for comment. Based on the submitted information, it has been determined that the proposed development will generate less than 10 additional vehicle trips per day (VTD). ACRD policy states that no site related improvements will be required for developments generating less than 10 additional VTD; and therefore ACRD has no site requirements attributable to this application. If the site plan or use changes in such a manner that more than 10 additional vehicle trips per day are generated, then ACRD will review the site plan and may issue requirements based on the ACRD Policy Manual. ACRD policy requires that before any improvements of any kind are constructed or installed within the public right-of- way, apermit or license agreement permitting the improvements must be obtained. All future design plans and construction shall be in accordance with the Ada County Highway District Policy Manual, ISPWC Standards and approved supplements, Construction Services procedures and all applicable ACRD Ordinances unless specifically waived in writing by the District. Meet District drainage requirements per section 8000 of the ACRD Development Policy Manual. Contact District staff at 387-6170 for details. Contact the office for payment of possible road impact fees prior to building construction in accordance with Ordinance #195, also known as the Ada County Highway District Road Impact Fee Ordinance. If you have any questions, please feel free to contact me at (208) 387-6170. Si erely, M evelopment Anal~rst Planning & Development Cc: Planning & Development/Chron/Project File Planning & Development Services Meridian Construction Services LKV Architects, 1735 Federal Way, Boise, ID 83705 Meridian Charter High School, 3800 N. Locust Grove Rd, Meridian, ID 83642 CITY OF MERIDIAN FINE C;ZL- DZ~oo $ Planning & Zoning Department 660 E. Watertower Ln., Ste. 202, Meridian, ID 83642 (208)884-5533 Phone / (208)888-6854 Fax CERTIFICATE OF ZONING COMPLIANCE (CZC) APPLICATION (Section 11-19-1, Zoning and Development Ordinance) PROJECT NAME: M G~ iz I I~ I A tJ G N A IZT~ tz' N I to N S G N v 0 V Ap t7 IT I D N APPLICANT: M G IZ I r71 Anl GNA 12TH- N I (~ N S G N oo I.. ~, I N G ADDRESS: ~19J00 N• LDGL~Sx (,1(ZaYG~ R.oAI~ MG~~.IDIAI`I PHONE: 7i ~J PJ ~ 2 ~ 2 P> FAX: 2 S FJ ~ ~7 (~ S ~ E-MAII,: s' ools•or~ OWNER(S) OF RECORD: .~OIIJ'( ~GNDOV 1715TP 1 GT IJ D• 2 ADDRESS: ~ 1 l M fG tZ I O I A N S '~ IZ ~ L~ T M CG FZ- 117 I A N PHONE: '~ ~ ~ ~ ~ 70 ( FAX: S ~ ~ ~ (0 7 0 D E-MAIL: ~n h r12. < < C 1'YleXil~,i((~1SGhoO~S• ~('G ARCHITECT (IF DIFFERENT THAN APPLICANT): L K Y A 12 G N I T G G'f 5 ADDRESS: I7 3 5 F G I~G IZA 1. WAY _~1~0 1 5 a 3 7 c~ S PHONE: ?73 (~ ~ 3 q-4 3 FAX: 3 3l~ - 3 ~/ S O E-MAIL L K A R G N G~ r'1 I N t7 5 ~(L.1 N C~ . GOh'I ADDRESS, GENERAL LOCATION OF SITE: 3 ~ n0 N . LOG U 5'~ la IZO Y G~ ~I~ DESCRIPTION OF USE: G V A 5 5 O D A 1~ b I T 10 I~l PRESENT ZONE CLASSIFICATION: IZ ' I, ~Q . N ~ c h o I S , do hereby affirm that I will agree to pay any additional sewer, water or trash fees or charges, if any, associated with the use that Uwe have applied for, whether the use be residential, commercial or industrial in nature. Furthermore, I have read the information contained herein and certify that the information is true and correct. ~/~/ / ate. (Applicant's Signature) (Date) Re>>. 2/1/0? MAYOR Robert D. Come CTIY COUNCdL MEMBERS Ron Anderson Keith Bird Taumy deWeerd CUerie McCandless HUB OF 7REA.SURE l/AI,IEY • A Good Place to Live CITY OF MERIDI~~N 33 EAST IDAHO MERIDIAN, IDAHO 83642 (208) 888-4433 • FAX (208) 887-4813 Ciry Qedc O(iice Fag (208) 888-4218 CERTIFICATE OF ZONING COMPLIANCE* ~'~.,~ ~`~E . LEGAL DEPARI"MFNI" (208) 288-2499 • Faz 288-2501 PUBLIC WORKS BUILDING DEPARTMENT (208) 887-2211 Fag 887-1297 PLANNING AND ZONING DEPARTMENT" (208) 884-5533 • FAX 888-6854 Date: February, 25.2002 Owner: The Meridian Charter High School Inc (Joint School District No. 2) Address: 3800 N. Locust Grove Road Proposed Use: A 2,040 squaze foot classroom addition Zoning: R-4 COMMENTS: Signa~e: No new signs have been applied for with this permit and no signs are approved for this location. A sign perirut shall be required for any signage to be installed at this location. Scope of Development: This Certificate of Zoning Compliance shall be valid for the construction of 2,040 square foot classroom addition and the other site improvements as depicted on the site/landscaping plans. Landscaping: .The landscaping shall be installed per the plans stamped approved on 02-25-02. Written approval of any changes is required; no field changes will be accepted without written approval. Number of Students: The issuance of this permit does not allow the School District to increase the maximum enrollment number beyond 200 students. Irrigation: An underground, pressurized irrigation/sprinkler system must be installed to all landscaped areas. Li tin :All new lighting, whether attached to the building or placed within the parking lot, shall not cause glare or impact the traveling public or neighboring developments, as determined by the City. Parking_ Parking shall be installed as depicted on the approved site plan. ADA: All construction and site improvements shall be in compliance with the ADA. Certificate of Occupancy: All required improvements must be completed or installed prior to obtaining a Certificate of Occupancy. A Temporary Certificate of Occupancy may be obtained by providing surety to the City in the form of a Letter of Credit or cash in the amount of 110% of the cost of the remaining improvements (including paving, striping, landscaping, and/or irrigation). A bid must accompany any request for Temporary Occupancy. ACRD Acceptance: Applicant shall be responsible for meeting the requirements of ACRD as they pertain to this type of development. All impact fees, if any, shall be paid prior to the issuance of a building permit. If any changes must be made to the site plan to accommodate the ACRD 4 K • requirements, a new site plan shall be submitted to the City of Meridian Planning and Zoning Staff for approval prior to the issuance of a building permit. Plan Modifications: The Site Plan and the Landscape Plan are not to be altered without prior written approval of the Planning & Zoning Department. No field changes to the site or landscape plans are permitted; prior written approval of all changes is required. CitX's failure to specifically identify requirements in this Certificate of Zoning; Compliance does not relieve owner of responsibility for compliance. The landscape/site plans stamped 02/25/02 are approved with the comments noted above. ~~ VV ~G David McKinnon (For Shari Stiles) Planning & Zoning Administrator *Receipt of a Certificate of Zoning Compliance does not indicate compliance with requirements of other departments/agencies, including, but not limited to, Ada County Highway District, Central District Health Department, affected irrigation district(s), Meridian Sewer, Water, Building or Fire Departments, etc. This certificate shall expire one (1) year from the date of issuance if work has not begun. ~ ~ • A R C H I T E C T S LEATHAM KROHN VAN OCKER February 22, 2002 Shari Stiles City of Meridian Planning and Zoning 660 E. Watertower Meridian, Idaho 83642 RE: Meridian Charter High School Classroom Addition Application for Certificate of Zoning Compliance Shari: Meridian Charter High School requests Certificate of Zoning Compliance approval fora 2,040 square foot, two-classroom addition on the north side of the school's present facility located at 3800 N. Locust Grove Road. All addition exterior colors and materials will match the existing building and all rooftop equipment will be entirely screened from view by the addition's parapet walls. The addition. is being constructed not to accommodate more students, but to reduce class size and eliminate use of the building's multi-purpose room as instructional space. Meridian Charter High School's enrollment cannot exceed its original design capacity of 200 students by State statute. See attached letter from Principal Jana Nichols. It is the school's opinion, therefore, that parking is fully adequate and that additional parking is not warranted. With regard to landscaping, all street frontage and parking lot landscaping as approved under the original building's Certificate of Zoning Compliance will remain unchanged. The only landscaping that will be affected by the proposed addition is one tree and some grass on the north side of the building. The small tree will be moved or replaced as shown on the site plan and new grass will be planted around the addition. The existing automatic sprinkler system piping and spray heads in the vicinity of the addition will be repositioned to provide complete coverage around the perimeter of the new construction. Please don't hesitate to call if you need additional information. Respectfu , ~~ Wayne Thowless, Architect LKV Architects DARRELL LEATHAM -KENT KROHN -AMBER VAN OCKER - WAYNE THOWLESS - STILLMAN ANDERSON 1735 FEDERAL WAY, BOISE, IDAHO 83705 PHONE 208-336-3443 FAX 208-336-3680 EMAIL LKARCH~MICRON.NET • ! Meridian Charter High School 3800 N. Locust Grove Meridian, Idaho 83642 (208) 288-2928 Fax (208)288-5685 February 4, 2002 Dear Mr. Thowless: Meridian Charter High School would like to add 2 more classrooms. We are not adding more students. Our Charter allows for a maximum of 200 students. This number is capped by both our charter and funding formula. The additional classrooms will allow us to have smaller class sizes in the junior and senior tech classes. Sincerely, 4 Jana Nichols Principal