2021-10-13 MFD MERIDIAN FIRE DEPARTMENT STAFF REPORT DATE: 10/13/2021 TO: Joseph Dodson REVIEWER: Joseph Bongiorno, Deputy Chief of Prevention 208-888-1234 SUBJECT: H-2021-0071 PROJECT NAME: Lennon Pointe Community Fire Department Summary of Report: Overview: This project can be serviced by the Meridian Fire Department. 1. Fire Response Time Travel time from nearest fire station (level of service expectation goal = 5 minutes) This development currently falls inside the 5 minute response time area as shown on the priority growth map. It is currently nearest to Fire Station 2. This fire station is approximately 1.5 miles from the project. 2. Resource reliability Current reliability of closest fire station (Reliability Goal is 80% or greater) This development is closest to Fire Station #2. Current reliability is 63% from this station and does not meet the targeted goal of 80% or greater. 3. Risk Identification Risk Factor (1=residential, 2=residential with hazards, 3=commercial, 4=commercial with hazards, 5=industrial) This proposed commercial development has a risk factor of 4, in which current resources would not be adequate to supply service to this propose project. Risk factors include an open waterway on the project site. Water rescue teams would have to be mutal aided from another department. Other hazards may be found once the development is completed. 4. Accessibility Roadway Access, traffic, Radio Coverage This project meets all required access, road widths and turnarounds as presented in the preliminary plat. Any changes shall require fire department approval if any roadways or accesses are changed. The private roads shall be signed “No Parking Fire Lane” per appendix D of the 2018 IFC. At the entrance of each end of the private road. the complex shall have a lighted map at the entrance showing the layout of the complex. All building numbers shall be backlit or frontlit for Police, Fire or EMS to easily see them from dusk to dawn. Page 2 of 8 5. Specialty/Resource needs a. Aerial device needed for development (more than 30’ in height)? i. If yes, is one available within a 12 minute travel time goal This proposed project will not require an aerial device. The closest truck company is 8 minutes travel time (under ideal conditions) to the proposed development, and therefore the Fire Department can meet this need in the required timeframe if a truck company is required. This fire station is approximately 3.5 miles from the project b. Other specialty needs (water rescue, hazmat, and technical rescue)? i. If yes, is one available within a 5 minute travel time? In the event of a hazmat event, there will need to be mutual aid required for the development. In the event of a structure fire an additional truck company will be required. This will require additional time delays as a second truck company is not available in the city. Water rescue teams would have to be mutal aided from another department in the event of a water rescue. 6. Water Supply (list expectations) Page 3 of 8 Water supply for this proposed development varies as there is residential and commercial requirements. (See appendix B of the 2018 International Fire Code) The fire flow requirements may be less if the buildings are fully sprinklered. 7. Other Comments Project specific comments are listed below. ***All IFC code sections per 2018 IFC or as noted*** RESOURCE AVAILABILITY - Fire Flow and Water Supply: 1. Fire Flow: One and two family dwellings not exceeding 3,600 square feet require a fire- flow of 1,000 gallons per minute for a duration of 1 hours to service the entire project. One and two family dwellings in excess of 3,600 square feet require a minimum fire flow as specified in Appendix B of the International Fire Code. Fire Hydrant spacing shall be provided as required by Appendix C of the International Fire Code. 2. Fire Flow: Commercial and office occupancies will require a fire-flow consistent with International Fire Code Appendix B to service the proposed project. Fire hydrants shall be placed per Appendix C. 3. Water Supply: Acceptance of the water supply for fire protection will be by the Meridian Fire Department and water quality by the Meridian Water Department for bacteria testing. 4. Water Supply: Final Approval of the fire hydrant locations shall be by the Meridian Fire Department or their designee in accordance with International Fire Code Section (IFC) 507.5.4 as follows: a. Fire hydrants shall have a Storz LDH connection in place of the 4 ½” outlet. The Storz connection may be integrated into the hydrant or an approved adapter may be used on the 4 1/2" outlet. b. Fire hydrants shall have the Storz outlet face the main street or parking lot drive aisle. c. Fire hydrants shall be placed on corners when spacing permits. d. Fire hydrants shall not have any vertical obstructions to outlets within 10’. Fire hydrants shall be placed 18” above finished grade to the center of the Storz e. outlet. f. Fire hydrants shall be provided to meet the requirements of the Meridian Water Dept. Standards. g. Show all proposed or existing hydrants for all new construction or additions to existing buildings within 1,000 feet of the project. 5. Water Supply: Where a portion of the facility or building hereafter constructed or moved into or within the jurisdiction is more than 400 feet (122 m) from a hydrant on a fire apparatus access road, as measured by an approved route around the exterior of the facility or building, on-site fire hydrants and mains shall be provided where required by the code official as set forth in International Fire Code Section 507.5.1. For buildings equipped throughout with an approved automatic sprinkler system installed in accordance with Section 903.3.1.1 or 903.3.1.2 the distance requirement shall be 600 feet (183). a. For Group R-3 and Group U occupancies, the distance requirement shall be 600 feet Page 4 of 8 (183 m). b. For buildings equipped throughout with an approved automatic sprinkler system installed in accordance with Section 903.3.1.1 or 903.3.1.2, the distance requirement shall be 600 feet (183 m). 6. Water Supply: There shall be a fire hydrant within 100’ of all fire department connections as set forth in local amendment to the International Fire Code 10-4-1. Over 100 apartment units without an approved sprinkler system or over 200 apartment units with an approved sprinkler system will require a secondary access per International Fire Code Section D104.3. The access roads shall be placed a distance apart equal to not less than one half of the length of the overall diagonal dimension of the property or area to be served, measured in a straight line as set forth in International Fire Code Appendix D104.1. 7. Water Supply: All R-2 occupancies with 3 or more units shall be required to be fire sprinkled as set forth in International Fire Code Section 903.2.8. ACCESSIBILITY - Fire Department Roadways, Access and Addressing: 8. Roadways: When required by the Fire Marshall, “No Parking Fire Lane” signs shall be used per appendix D of the 2018 IFC. No other signs shall be approved: 9. Roadways: All entrances, internal roads, drive aisles, and alleys shall have a turning radius of 28’ inside and 48’ outside, per International Fire Code Section 503.2.4. 10. Roadways: All common driveways and alleys shall be maintained at all times for access by fire, police and EMS at all times of the year. 11. Roadways: To increase emergency access to the site a minimum of two points of access will be required for any portion of the project which serves more than 30 homes, as set forth in International Fire Code Section D107.1. The two entrances should be separated by no less than ½ the diagonal measurement of the full development as set forth in International Fire Code Section D104.3. The applicant shall provide an additional stub street to the property. . Page 5 of 8 12. Roadways: The roadways shall be built to Ada County Highway District cross section standards and have a clear driving surface. Streets less than 26’ in width shall have no on- street parking. Both sides of the street shall be signed “No Parking Fire Lane” per appendix D of the IFC; streets less than 32’ in width shall have parking only on one side. One side of the street shall be signed “No Parking Fire Lane” per appendix D of the IFC. These measurements shall be based on the drivable surface dimension exclusive of shoulders. The roadway shall be able to accommodate an imposed load of 80,000 GVW as set forth in International Fire Code Section 503.2.1 and D103.6.1 and D103.6.2. 13. Roadways: Traffic calming devices. Traffic calming devices shall be prohibited unless approved by the fire code official. National Fire Protection IFC 503.4.1. 14. Access: Fire lanes, streets, and structures (including the canopy height of mature trees) shall have a vertical clearance of 13’6 as set forth in International Fire Code Section 503.2.1. 15. Access: Where fire apparatus access roads or a water supply for fire protection are required to be installed, such protection shall be installed and made serviceable prior to and during the time of construction except where approved alternative methods of protection are provided. Temporary street signs shall be installed at each street intersection where construction of new roadways allows passage by vehicles in accordance with Section 505.2., as set forth in International Fire Code Section (IFC) 501.4. 16. Access: Provide a Fire Department Key box entry system for the complex prior to occupancy as set forth in International Fire Code Section 506. Knox Boxes can be ordered from www.knoxbox.com. Page 6 of 8 17. Access: Based on the size of new construction and the location of the sprinkler room in relation to the address side of the structure, the AHJ may require separate Fire Department key box locations. One being at the main, address side entrance and the other at the entrance to the sprinkler riser room. Knox Boxes can be ordered from www.knoxbox.com. 18. Access: The Fire Department will require Fire Department locking Connection caps on all FDC inlets. IFC 102.9. Caps can be ordered at www.knoxbox.com. 19. Access: All portions of the buildings located on this project must be within 150’ of a paved surface as measured around the perimeter of the building as set forth in International Fire Code Section 503.1.1. Page 7 of 8 20. Access: As set forth in International Fire Code Section 504.1, multi-family and commercial projects shall be required to provide an additional sixty inches (60”) wide access point to the building from the fire lane to allow for the movement of manual fire suppression equipment and gurney operations. The unobstructed breaks in the parking stalls shall be provided so that building access is provided in such a manner that the most remote part of a building can be reached with a length of 150' fire hose as measured around the perimeter of the building from the fire lane. Code compliant handicap parking stalls may be included to assist meeting this requirement. Contact the Meridian Fire Department for details. 21. Addressing: The first digit of the Apartment/Office Suite shall correspond to the floor level as set forth in International Fire Code Section 505.1 and Meridian Amendment 10-4-1. 22. Addressing: The applicant shall work with Public Works and Planning Department staff to provide an address identification plan and a sign which meets the requirements of the City of Meridian sign ordinance and is placed in a position that is plainly legible and visible from the street or road fronting the property, as set forth in International Fire Code Section 505.1 and Meridian Amendment 104-4-1. 23. Addressing: If required by the Fire Code Official, the complex shall have a lighted map at the entrance showing the layout of the complex. All building numbers shall be backlit or frontlit for Police, Fire or EMS to easily see them from dusk to dawn. 24. Addressing: This project will require private streets. The applicant will work with the addressing agent for this project. All private streets shall shall be signed on both sides of the roadway “No Parking Fire Lane” per International Fire Code 503.3 & D103.6 unless approved by the Fire Marshal. Page 8 of 8