Engineering Calcs Structural Calculations For 16’ X 44’ POLE BARN 508 E Bower Street Meridian, Idaho 83642 Prepared for: AJB Contractors, LLC PO Box 1014 Caldwell, Idaho 83606 Rogue Richardson, PE 1720 S Powerline – Nampa, Idaho 83686 (208) 577-7071 roguerichardson@yahoo.com Revision # Prepared by Project # 0 Rogue Richardson, PE 21022.003 DESIGN CRITERIA: CODE: 2018 INTERNATIONAL BUILDING CODE LOCATION: MERIDIAN, IDAHO Wind Load: 102 MPH Seismic: Ss=0.284, S1=0.104 Snow Load: 25psf (27 pages of Calculations) TABLE OF CONTENTS Calculations Seismic Coefficients 1 Wind Speed 2 Structural Loads 3 Purlin Loading 8 Purlin Bending Check 9 Hanger Load Table 11 Truss Support Blocks 12 Nail Loads 13 Wind Load on Columns - End Columns 14 Column Check - End Columns 15 Wind Load on Columns - Field Columns 18 Column Check - Field Columns 19 Wind Load on Columns - Front/Rear Columns 22 Column Check - Front/Rear Columns 23 Pole Footing Embedded in Soil 26 1 2 Rogue Richardson, PE JOB TITLE 16' X 44' Pole Structure 1720 S Powerline Road 508 E Bower Street Nampa, Idaho 83686 JOB NO.SHEET NO. 9208) 577-7071 CALCULATED BY DATE CHECKED BY DATE CS2018 Ver 2018.11.30 www.struware.com STRUCTURAL CALCULATIONS FOR 16' X 44' Pole Structure Meridian, Idaho 83642 3 Rogue Richardson, PE JOB TITLE 16' X 44' Pole Structure 1720 S Powerline Road 508 E Bower Street Nampa, Idaho 83686 JOB NO.SHEET NO. 9208) 577-7071 CALCULATED BY DATE CHECKED BY DATE www.struware.com Code Search Code: Occupancy: Occupancy Group = B Risk Category & Importance Factors: Risk Category = II Wind factor = 1.00 Snow factor = 1.00 Seismic factor = 1.00 Type of Construction: Fire Rating: Roof = 0.0 hr Floor = 0.0 hr Building Geometry: Roof angle (θ)3.00 / 12 14.0 deg Building length (L) 44.0 ft Least width (B) 16.0 ft Mean Roof Ht (h) 15.0 ft Parapet ht above grd 0.0 ft Minimum parapet ht 0.0 ft Live Loads: Roof 0 to 200 sf: 20 psf 200 to 600 sf: 24 - 0.02Area, but not less than 12 psf over 600 sf: 12 psf Floor: Typical Floor N/A Partitions N/A Partitions N/A Partitions N/A Partitions N/A International Building Code 2018 Business 4 Rogue Richardson, PE JOB TITLE 16' X 44' Pole Structure 1720 S Powerline Road 508 E Bower Street Nampa, Idaho 83686 JOB NO.SHEET NO. 9208) 577-7071 CALCULATED BY DATE CHECKED BY DATE Wind Loads :ASCE 7- 16 Ultimate Wind Speed 102 mph Nominal Wind Speed 79 mph Risk Category II Exposure Category C Enclosure Classif. Enclosed Building Internal pressure +/-0.18 Directionality (Kd)0.85 Kh case 1 0.849 Kh case 2 0.849 Type of roof Gable Topographic Factor (Kzt) Topography Flat Hill Height (H)0.0 ft H< 15ft;exp C Half Hill Length (Lh) 0.0 ft Kzt=1.0 Actual H/Lh = 0.00 Use H/Lh = 0.00 Modified Lh = 0.0 ft From top of crest: x = Bldg up/down wind? downwind H/Lh= 0.00 K1 =0.000 x/Lh = 0.00 K2 =0.000 z/Lh = 0.00 K3 =1.000 At Mean Roof Ht: Kzt = (1+K1K2K3)^2 =1.00 Gust Effect Factor Flexible structure if natural frequency < 1 Hz (T > 1 second). h = 15.0 ft If building h/B>4 then may be flexible and should be investigated. B = 16.0 ft h/B = 0.94 Rigid structure (low rise bldg) /z (0.6h) = 15.0 ft G = 0.85 Using rigid structure default Rigid Structure Flexible or Dynamically Sensitive Structure ē =0.20 34ncy (η1) =0.0 Hz ℓ = 500 ft Damping ratio (β) = 0zmin =15 ft /b = 0.65 c = 0.20 /α = 0.15 gQ, gv =3.4 Vz = 86.1 Lz =427.1 ft N1 =0.00 Q = 0.94 Rn =0.000 Iz =0.23 Rh =28.282 η = 0.000 h = 15.0 ft G = 0.90 use G = 0.85 RB =28.282 η = 0.000 RL =28.282 η = 0.000 gR =0.000 R = 0.000 Gf = 0.000 5 Rogue Richardson, PE JOB TITLE 16' X 44' Pole Structure 1720 S Powerline Road 508 E Bower Street Nampa, Idaho 83686 JOB NO.SHEET NO. 9208) 577-7071 CALCULATED BY DATE CHECKED BY DATE Wind Loads - MWFRS h≤60' (Low-rise Buildings) except for open buildings Kz = Kh (case 1) = 0.85 Edge Strip (a) = 3.0 ft Base pressure (qh) =19.2 psf End Zone (2a) = 6.0 ft GCpi = +/-0.18 Zone 2 length = 8.0 ft Wind Pressure Coefficients CASE A CASE B Surface GCpf w/-GCpi w/+GCpi GCpf w/-GCpi w/+GCpi 1 0.48 0.66 0.30 -0.45 -0.27 -0.63 2 -0.69 -0.51 -0.87 -0.69 -0.51 -0.87 3 -0.44 -0.26 -0.62 -0.37 -0.19 -0.55 4 -0.37 -0.19 -0.55 -0.45 -0.27 -0.63 5 0.40 0.58 0.22 6 -0.29 -0.11 -0.47 1E 0.72 0.90 0.54 -0.48 -0.30 -0.66 2E -1.07 -0.89 -1.25 -1.07 -0.89 -1.25 3E -0.63 -0.45 -0.81 -0.53 -0.35 -0.71 4E -0.56 -0.38 -0.74 -0.48 -0.30 -0.66 5E 0.61 0.79 0.43 6E -0.43 -0.25 -0.61 Ultimate Wind Surface Pressures (psf) 1 12.7 5.7 -5.2 -12.1 2 -9.8 -16.7 -9.8 -16.7 3 -4.9 -11.8 -3.7 -10.6 4 -3.7 -10.7 -5.2 -12.1 5 11.1 4.2 6 -2.1 -9.0 1E 17.4 10.5 -5.8 -12.7 2E -17.1 -24.0 -17.1 -24.0 3E -8.6 -15.5 -6.7 -13.6 4E -7.2 -14.2 -5.8 -12.7 5E 15.2 8.3 6E -4.8 -11.7 Parapet Windward parapet = 0.0 psf (GCpn = +1.5)Windward roof Leeward parapet = 0.0 psf (GCpn = -1.0)overhangs = 13.5 psf (upward) add to windward roof pressure Horizontal MWFRS Simple Diaphragm Pressures (psf) Transverse direction (normal to L) Interior Zone: Wall 16.4 psf Roof -4.9 psf ** End Zone: Wall 24.6 psf Roof -8.5 psf ** Longitudinal direction (parallel to L) Interior Zone: Wall 13.3 psf End Zone: Wall 20.0 psf ** NOTE: Total horiz force shall not be less than that determined by neglecting roof forces (except for MWFRS moment frames). The code requires the MWFRS be designed for a min ultimate force of 16 psf multiplied by the wall area plus an 8 psf force applied to the vertical projection of the roof. θ = 14 deg 6 Rogue Richardson, PE JOB TITLE 16' X 44' Pole Structure 1720 S Powerline Road 508 E Bower Street Nampa, Idaho 83686 JOB NO.SHEET NO. 9208) 577-7071 CALCULATED BY DATE CHECKED BY DATE Seismic Loads:IBC 2018 Strength Level Forces Risk Category : II Importance Factor (I) : 1.00 Site Class : D Ss (0.2 sec) = 28.40 %g S1 (1.0 sec) = 10.40 %g Fa = 1.573 Sms = 0.447 SDS =0.298 Design Category = B Fv = 2.392 Sm1 = 0.249 SD1 =0.166 Design Category = C Seismic Design Category =C Redundancy Coefficient ρ = 1.30 Number of Stories: 1 Structure Type:All other building systems Horizontal Struct Irregularities:No plan Irregularity Vertical Structural Irregularities:No vertical Irregularity Flexible Diaphragms: No Building System: Cantilevered Column Systems detailed to conform to the requirements for: Seismic resisting system: Timber frames System Structural Height Limit: 35 ft Actual Structural Height (hn) =16.0 ft DESIGN COEFFICIENTS AND FACTORS Response Modification Coefficient (R) = 1.5 Over-Strength Factor (Ωo) = 1.5 Deflection Amplification Factor (Cd) =1.5 SDS =0.298 SD1 =0.166 Seismic Load Effect (E) = Eh +/-Ev = ρ QE +/- 0.2SDS D = 1.3Qe +/-0.060D Special Seismic Load Effect (Em) =Emh +/- Ev = Ωo QE +/- 0.2SDS D = 1.5Qe +/-0.060D D = dead load PERMITTED ANALYTICAL PROCEDURES Simplified Analysis - Use Equivalent Lateral Force Analysis Equivalent Lateral-Force Analysis - Permitted Building period coef. (CT) =0.020 Cu = 1.57 Approx fundamental period (Ta) =CThn x = 0.160 sec x= 0.75 Tmax = CuTa = 0.251 User calculated fundamental period (T) =sec Use T = 0.160 Long Period Transition Period (TL) =ASCE7 map =6 Seismic response coef. (Cs) =SDSI/R =0.199 need not exceed Cs =Sd1 I /RT =0.691 but not less than Cs =0.044SdsI = 0.013 USE Cs = 0.199 Design Base Shear V =0.199W Model & Seismic Response Analysis - Permitted (see code for procedure) ALLOWABLE STORY DRIFT Structure Type: All other structures Allowable story drift Δa = 0.020hsx where hsx is the story height below level x QE = horizontal seismic force 7 Rogue Richardson, PE CLIENT:AJB Contractors 1720 S Powerline JOB: 16' x 44' Pole Structure Nampa, ID 83686 DESCRIPTION: Purlin Load (208) 463-7670 DESIGNER: Rogue Richardson DATE: Comments: DL = 10 psf LL = 25 psf Purlin Load = 2 * ( 10 + 25 ) = 70 plf Distance between Trusses =11 ft Load at each Hanger = 11 / 2 * 70 = 385 lbs See Enercalc bending check - next page Jul. 26, 2021 PURLIN LOAD 8 Wood Beam ROGUE RICHARDSONLic. # : KW-06008302 DESCRIPTION:2x6 Roof Purlin Title Block Line 1 You can change this area using the "Settings" menu item and then using the "Printing & Title Block" selection. Title Block Line 6 Software copyright ENERCALC, INC. 1983-2020, Build:12.20.8.17 File: circle d pole barn.ec6 Project Title: Engineer: Project ID: Printed: 26 JUL 2021, 5:11PM Project Descr: CODE REFERENCES Calculations per NDS 2018, IBC 2018, CBC 2019, ASCE 7-16 Load Combination Set : ASCE 7-16 Material Properties Beam Bracing :Beam is Fully Braced against lateral-torsional buckling Repetitive Member Stress Increase Allowable Stress Design Douglas Fir-Larch No.2 900 900 1350 625 1600 580 180 575 31.21 Analysis Method : Eminbend - xx ksi Wood Species : Wood Grade : Fb + psi psi Fv psi Fb - Ft psi Fc - Prll psi psiFc - Perp E : Modulus of Elasticity Ebend- xx ksi Density pcf Load Combination :ASCE 7-16 Applied Loads Service loads entered. Load Factors will be applied for calculations. Beam self weight calculated and added to loads Uniform Load : D = 0.0070, S = 0.0250 ksf, Tributary Width = 2.0 ft DESIGN SUMMARY Design OK Maximum Bending Stress Ratio 0.975: 1 Load Combination +D+S+H Span # where maximum occurs Span # 1 Location of maximum on span 5.357 ft 59.13 psi= = 1,547.33 psi 2x6Section used for this span Span # where maximum occurs Location of maximum on span Span # 1= Load Combination +D+S+H = = = 207.00 psi== Section used for this span 2x6 Maximum Shear Stress Ratio 0.286 : 1 10.319 ft= = 1,507.94 psi Maximum Deflection 0 <265 215 Ratio =0 <201 Max Downward Transient Deflection 0.454 in 284Ratio =>=265 Max Upward Transient Deflection 0.000 in Ratio = Max Downward Total Deflection 0.597 in Ratio =>=201 Max Upward Total Deflection 0.000 in fb: Actual Fb: Allowable fv: Actual Fv: Allowable Maximum Forces & Stresses for Load Combinations Span # Moment ValuesLoad Combination C i C LCCCCF/V mr td Shear ValuesMax Stress Ratios M CV fbM fvF'b V F'vSegment Length +D+H 0.00 0.00 0.000.00 1.00Length = 10.750 ft 1 0.299 0.088 0.90 1.300 1.15 1.00 1.00 0.23 361.88 1210.95 0.08 162.00 1.00 14.19 1.00+D+L+H 1.300 1.15 1.00 1.00 0.00 0.00 0.00 1.00 0.00 1.00Length = 10.750 ft 1 0.269 0.079 1.00 1.300 1.15 1.00 1.00 0.23 361.88 1345.50 0.08 180.00 1.00 14.19 1.00+D+Lr+H 1.300 1.15 1.00 1.00 0.00 0.00 0.00 1.00 0.00 1.00Length = 10.750 ft 1 0.215 0.063 1.25 1.300 1.15 1.00 1.00 0.23 361.88 1681.88 0.08 225.00 1.00 14.19 1.00+D+S+H 1.300 1.15 1.00 1.00 0.00 0.00 0.00 1.00 0.00 1.00Length = 10.750 ft 1 0.975 0.286 1.15 1.300 1.15 1.00 1.00 0.95 1,507.94 1547.33 0.33 207.00 1.00 59.13 1.00+D+0.750Lr+0.750L+H 1.300 1.15 1.00 1.00 0.00 0.00 0.00 1.00 0.00 1.00Length = 10.750 ft 1 0.215 0.063 1.25 1.300 1.15 1.00 1.00 0.23 361.88 1681.88 0.08 225.00 1.00 14.19 1.00+D+0.750L+0.750S+H 1.300 1.15 1.00 1.00 0.00 0.00 0.00 1.00 0.00 1.00Length = 10.750 ft 1 0.789 0.231 1.15 1.300 1.15 1.00 1.00 0.77 1,221.43 1547.33 0.26 207.00 1.00 47.90 1.00+D+0.60W+H 1.300 1.15 1.00 1.00 0.00 0.00 0.00 1.00 0.00 9 Wood Beam ROGUE RICHARDSONLic. # : KW-06008302 DESCRIPTION:2x6 Roof Purlin Title Block Line 1 You can change this area using the "Settings" menu item and then using the "Printing & Title Block" selection. Title Block Line 6 Software copyright ENERCALC, INC. 1983-2020, Build:12.20.8.17 File: circle d pole barn.ec6 Project Title: Engineer: Project ID: Printed: 26 JUL 2021, 5:11PM Project Descr: Span # Moment ValuesLoad Combination C i C LCCCCF/V mr td Shear ValuesMax Stress Ratios M CV fbM fvF'b V F'vSegment Length 1.00Length = 10.750 ft 1 0.168 0.049 1.60 1.300 1.15 1.00 1.00 0.23 361.88 2152.80 0.08 288.00 1.00 14.19 1.00+D+0.750Lr+0.750L+0.450W+H 1.300 1.15 1.00 1.00 0.00 0.00 0.00 1.00 0.00 1.00Length = 10.750 ft 1 0.168 0.049 1.60 1.300 1.15 1.00 1.00 0.23 361.88 2152.80 0.08 288.00 1.00 14.19 1.00+D+0.750L+0.750S+0.450W+H 1.300 1.15 1.00 1.00 0.00 0.00 0.00 1.00 0.00 1.00Length = 10.750 ft 1 0.567 0.166 1.60 1.300 1.15 1.00 1.00 0.77 1,221.43 2152.80 0.26 288.00 1.00 47.90 1.00+0.60D+0.60W+0.60H 1.300 1.15 1.00 1.00 0.00 0.00 0.00 1.00 0.00 1.00Length = 10.750 ft 1 0.101 0.030 1.60 1.300 1.15 1.00 1.00 0.14 217.13 2152.80 0.05 288.00 1.00 8.51 1.00+D+0.70E+0.60H 1.300 1.15 1.00 1.00 0.00 0.00 0.00 1.00 0.00 1.00Length = 10.750 ft 1 0.168 0.049 1.60 1.300 1.15 1.00 1.00 0.23 361.88 2152.80 0.08 288.00 1.00 14.19 1.00+D+0.750L+0.750S+0.5250E+H 1.300 1.15 1.00 1.00 0.00 0.00 0.00 1.00 0.00 1.00Length = 10.750 ft 1 0.567 0.166 1.60 1.300 1.15 1.00 1.00 0.77 1,221.43 2152.80 0.26 288.00 1.00 47.90 1.00+0.60D+0.70E+H 1.300 1.15 1.00 1.00 0.00 0.00 0.00 1.00 0.00 1.00Length = 10.750 ft 1 0.101 0.030 1.60 1.300 1.15 1.00 1.00 0.14 217.13 2152.80 0.05 288.00 1.00 8.51 Location in SpanLoad CombinationMax. "-" Defl Location in SpanLoad Combination Span Max. "+" Defl Overall Maximum Deflections +D+S+H 1 0.5973 5.393 0.0000 0.000 Load Combination Support 1 Support 2 Vertical Reactions Support notation : Far left is #1 Values in KIPS Overall MAXimum 0.354 0.354 Overall MINimum 0.269 0.269 +D+H 0.085 0.085 +D+L+H 0.085 0.085 +D+Lr+H 0.085 0.085 +D+S+H 0.354 0.354 +D+0.750Lr+0.750L+H 0.085 0.085 +D+0.750L+0.750S+H 0.286 0.286 +D+0.60W+H 0.085 0.085 +D+0.750Lr+0.750L+0.450W+H 0.085 0.085 +D+0.750L+0.750S+0.450W+H 0.286 0.286 +0.60D+0.60W+0.60H 0.051 0.051 +D+0.70E+0.60H 0.085 0.085 +D+0.750L+0.750S+0.5250E+H 0.286 0.286 +0.60D+0.70E+H 0.051 0.051 D Only 0.085 0.085 S Only 0.269 0.269 H Only 10 11 Rogue Richardson, PE CLIENT:AJB Contractors 1720 S Powerline JOB: 16' x 44' Pole Structure Nampa, ID 83686 DESCRIPTION: Truss Support Blocks (208) 463-7670 DESIGNER: Rogue Richardson DATE: Comments: Controlling Load at Block DL = 10 psf SL = 25 psf Truss Span =16 ft Distance between Posts =11 ft Truss Load = 8 * ( 10 + 25 ) * 5.5 = 1540 plf Number of Nails = 1540 / 141) = 12 16d Nails . Block Size = 21 Use 21in block with (12) 16d nails under each Truss End Post Dead Load =440 End Post Live Load =1100 Field Post Dead Load =880 Field Post Live Load =2200 Jul. 26, 2021 TRUSS SUPPORT BLOCK Main Support Truss 12 13 Rogue Richardson, PE CLIENT:AJB Contractors 1720 S Powerline JOB: 16' x 44' Pole Structure Nampa, ID 83686 DESCRIPTION: End Column on Side Wall (208) 463-7670 DESIGNER: Rogue Richardson DATE: Comments: 2ft 8.5psf 14 ft 24.6 psf Distance Between Columns = 11 ft 2 Columns Resisting Wind Loading Point Load at the Top of Column = (5.5 * 2 * 8.5) / 2 47 lbs Distributed Load along Column = (24.6 * 5.5) / 2 = 68 lbs Jul. 26, 2021 Wind Load on Column - End Column 14 Wood Column ROGUE RICHARDSONLic. # : KW-06008302 DESCRIPTION:End Column Title Block Line 1 You can change this area using the "Settings" menu item and then using the "Printing & Title Block" selection. Title Block Line 6 Software copyright ENERCALC, INC. 1983-2020, Build:12.20.8.17 File: circle d pole barn.ec6 Project Title: Engineer: Project ID: Printed: 26 JUL 2021, 5:57PM Project Descr: Code References Calculations per NDS 2018, IBC 2018, CBC 2019, ASCE 7-16 Load Combinations Used : ASCE 7-16 General Information Wood Section Name 6x6Analysis Method : 14Overall Column Height ft Load Resistance Factor Design ( Used for non-slender calculations )Allow Stress Modification Factors End Fixities Top Free, Bottom Fixed Wood Species Hem-Fir (North) Wood Grade No. 1/No. 2 Fb +1,000.0 1,000.0 psi 1,450.0 405.0 145.0 575.0 28.720 psi Fv psi Fb - Ft psi Fc - Prll psi psi Density pcf Fc - Perp E : Modulus of Elasticity . . . 1,600.0 580.0 1,600.0 580.0 Cfu : Flat Use Factor 1.0 Cf or Cv for Tension 1.0 Use Cr : Repetitive ? Kf : Built-up columns 1.0 NDS 15.3.2 Exact Width 6.0 in Exact Depth 6.0 in Area 36.0 in^2 Ix 108.0 in^4 Iy 108.0 in^4 Wood Grading/Manuf.Graded Lumber Wood Member Type Sawn Ct : Temperature Factor 1.0 Cf or Cv for Compression 1.0 1,600.0 Axial Cm : Wet Use Factor 1.0 Cf or Cv for Bending 1.0 x-x Bending y-y Bending ksi YesMinimum Basic Y-Y (depth) axis : X-X (width) axis : Fully braced against buckling ABOUT X-X Axis Fully braced against buckling ABOUT Y-Y Axis Brace condition for deflection (buckling) along columns : Service loads entered. Load Factors will be applied for calculations.Applied Loads Column self weight included : 100.520 lbs * Dead Load Factor AXIAL LOADS . . . Gravity: Axial Load at 14.0 ft, D = 0.440, L = 1.10 k BENDING LOADS . . . Lat. Point Load at 14.0 ft creating Mx-x, W = 0.0470 k Lat. Uniform Load creating Mx-x, W = 0.060 k/ft DESIGN SUMMARY PASS PASS Max. Axial+Bending Stress Ratio =0.8776 Location of max.above base 0.0 ft Applied Axial 1.749 k Applied Mx -6.538 k-ft Load Combination +1.20D+0.50Lr+L+W+1.60H Load Combination +0.90D+W+1.60H Bending & Shear Check Results Maximum Shear Stress Ratio = Applied Design Shear 36.958 psi 313.20Allowable Shear psi 0.07867 : 1 Bending Compression Tension LRFD - Format Conversion factor 2.541 2.400 2.700 LRFD - Resistance factor 0.850 0.900 0.800 Location of max.above base 0.0 ft : 1 At maximum location values are . . . Applied My 0.0 k-ft Maximum SERVICE Lateral Load Reactions . . Top along Y-Y 0.0 k Bottom along Y-Y 0.8870 k Top along X-X 0.0 k Bottom along X-X 0.0 kGoverning NDS Forumla11Comp + Mxx, NDS Eq. 3.9-3 Maximum SERVICE Load Lateral Deflections . . . Along Y-Y 3.296 in at 14.0 ft above base for load combination :W Only Along X-X 0.0 in at 0.0 ft above base Fc : Allowable 3,132.0 psi Other Factors used to calculate allowable stresses . . . for load combination :n/a Maximum Axial + Bending Stress Ratios Maximum Shear RatiosCLambdaLoad Combination Stress Ratio Location Stress Ratio Status LocationPStatus Load Combination Results +1.40D+1.60H 0.600 PASS PASS0.0 0.0 0.0 ft1.000 ft0.01119 +1.20D+0.50Lr+1.60L+1.60H 0.800 PASS PASS0.0 0.0 0.0 ft1.000 ft0.02670 +1.20D+1.60L+0.50S+1.60H 0.800 PASS PASS0.0 0.0 0.0 ft1.000 ft0.02670 +1.20D+1.60Lr+L+1.60H 0.800 PASS PASS0.0 0.0 0.0 ft1.000 ft0.01939 +1.20D+1.60Lr+0.50W+1.60H 0.800 PASS PASS0.0 0.04917 0.0 ft1.000 ft0.5484 +1.20D+L+1.60S+1.60H 0.800 PASS PASS0.0 0.0 0.0 ft1.000 ft0.01939 +1.20D+1.60S+0.50W+1.60H 0.800 PASS PASS0.0 0.04917 0.0 ft1.000 ft0.5484 +1.20D+0.50Lr+L+W+1.60H 1.000 PASS PASS0.0 0.07867 0.0 ft1.000 ft0.8776 15 Wood Column ROGUE RICHARDSONLic. # : KW-06008302 DESCRIPTION:End Column Title Block Line 1 You can change this area using the "Settings" menu item and then using the "Printing & Title Block" selection. Title Block Line 6 Software copyright ENERCALC, INC. 1983-2020, Build:12.20.8.17 File: circle d pole barn.ec6 Project Title: Engineer: Project ID: Printed: 26 JUL 2021, 5:57PM Project Descr: Maximum Axial + Bending Stress Ratios Maximum Shear RatiosCLambdaLoad Combination Stress Ratio Location Stress Ratio Status LocationPStatus Load Combination Results +1.20D+L+0.50S+W+1.60H 1.000 PASS PASS0.0 0.07867 0.0 ft1.000 ft0.8776 +0.90D+W+1.60H 1.000 PASS PASS0.0 0.07867 0.0 ft1.000 ft0.8774 +1.20D+L+0.20S+E+1.60H 1.000 PASS PASS0.0 0.0 0.0 ft1.000 ft0.01551 +0.90D+E+0.90H 1.000 PASS PASS0.0 0.0 0.0 ft1.000 ft0.004314 k k-ft Note: Only non-zero reactions are listed. Load Combination X-X Axis Reaction Y-Y Axis Reaction Axial Reaction @ Base @ Top @ Base@ Base @ Top Maximum Reactions @ Base @ Base@ Top @ Top My - End Moments Mx - End Moments +D+H 0.541 +D+L+H 1.641 +D+Lr+H 0.541 +D+S+H 0.541 +D+0.750Lr+0.750L+H 1.366 +D+0.750L+0.750S+H 1.366 +D+0.60W+H 0.5410.532 3.923 +D+0.750Lr+0.750L+0.450W+H 1.3660.399 2.942 +D+0.750L+0.750S+0.450W+H 1.3660.399 2.942 +0.60D+0.60W+0.60H 0.3240.532 3.923 +D+0.70E+0.60H 0.541 +D+0.750L+0.750S+0.5250E+H 1.366 +0.60D+0.70E+H 0.324 D Only 0.541 Lr Only L Only 1.100 S Only W Only 0.887 6.538 E Only H Only Maximum Deflections for Load Combinations Max. X-X Deflection Max. Y-Y Deflection DistanceLoad Combination Distance +D+H 0.0000 0.0000 0.000 ftft inin 0.000 +D+L+H 0.0000 0.0000 0.000 ftft inin 0.000 +D+Lr+H 0.0000 0.0000 0.000 ftft inin 0.000 +D+S+H 0.0000 0.0000 0.000 ftft inin 0.000 +D+0.750Lr+0.750L+H 0.0000 0.0000 0.000 ftft inin 0.000 +D+0.750L+0.750S+H 0.0000 0.0000 0.000 ftft inin 0.000 +D+0.60W+H 0.0000 1.9776 14.000 ftft inin 0.000 +D+0.750Lr+0.750L+0.450W+H 0.0000 1.4832 14.000 ftft inin 0.000 +D+0.750L+0.750S+0.450W+H 0.0000 1.4832 14.000 ftft inin 0.000 +0.60D+0.60W+0.60H 0.0000 1.9776 14.000 ftft inin 0.000 +D+0.70E+0.60H 0.0000 0.0000 0.000 ftft inin 0.000 +D+0.750L+0.750S+0.5250E+H 0.0000 0.0000 0.000 ftft inin 0.000 +0.60D+0.70E+H 0.0000 0.0000 0.000 ftft inin 0.000 D Only 0.0000 0.0000 0.000 ftft inin 0.000 Lr Only 0.0000 0.0000 0.000 ftft inin 0.000 L Only 0.0000 0.0000 0.000 ftft inin 0.000 S Only 0.0000 0.0000 0.000 ftft inin 0.000 W Only 0.0000 3.2960 14.000 ftft inin 0.000 E Only 0.0000 0.0000 0.000 ftft inin 0.000 H Only 0.0000 0.0000 0.000 ftft inin 0.000 16 Wood Column ROGUE RICHARDSONLic. # : KW-06008302 DESCRIPTION:End Column Title Block Line 1 You can change this area using the "Settings" menu item and then using the "Printing & Title Block" selection. Title Block Line 6 Software copyright ENERCALC, INC. 1983-2020, Build:12.20.8.17 File: circle d pole barn.ec6 Project Title: Engineer: Project ID: Printed: 26 JUL 2021, 5:57PM Project Descr: Sketches 17 Rogue Richardson, PE CLIENT:AJB Contractors 1720 S Powerline JOB: 16' x 44' Pole Structure Nampa, ID 83686 DESCRIPTION: Field Columns on Side Wall (208) 463-7670 DESIGNER: Rogue Richardson DATE: Comments: 2ft 4.9psf 14 ft 16.4 psf Distance Between Columns = 11 ft 2 Columns Resisting Wind Loading Point Load at the Top of Column = (11 * 2 * 4.9) / 2 =54 lbs Distributed Load along Column = (16.4 * 11) / 2 = 90 lbs Jul. 26, 2021 Wind Load on Column - Field Column 18 Wood Column ROGUE RICHARDSONLic. # : KW-06008302 DESCRIPTION:Field Column Title Block Line 1 You can change this area using the "Settings" menu item and then using the "Printing & Title Block" selection. Title Block Line 6 Software copyright ENERCALC, INC. 1983-2020, Build:12.20.8.17 File: circle d pole barn.ec6 Project Title: Engineer: Project ID: Printed: 26 JUL 2021, 5:57PM Project Descr: Code References Calculations per NDS 2018, IBC 2018, CBC 2019, ASCE 7-16 Load Combinations Used : ASCE 7-16 General Information Wood Section Name 6x8Analysis Method : 14Overall Column Height ft Load Resistance Factor Design ( Used for non-slender calculations )Allow Stress Modification Factors End Fixities Top Free, Bottom Fixed Wood Species Hem-Fir (North) Wood Grade No. 1/No. 2 Fb +1,000.0 1,000.0 psi 1,450.0 405.0 145.0 575.0 28.720 psi Fv psi Fb - Ft psi Fc - Prll psi psi Density pcf Fc - Perp E : Modulus of Elasticity . . . 1,600.0 580.0 1,600.0 580.0 Cfu : Flat Use Factor 1.0 Cf or Cv for Tension 1.0 Use Cr : Repetitive ? Kf : Built-up columns 1.0 NDS 15.3.2 Exact Width 6.0 in Exact Depth 8.0 in Area 48.0 in^2 Ix 256.0 in^4 Iy 144.0 in^4 Wood Grading/Manuf.Graded Lumber Wood Member Type Sawn Ct : Temperature Factor 1.0 Cf or Cv for Compression 1.0 1,600.0 Axial Cm : Wet Use Factor 1.0 Cf or Cv for Bending 1.0 x-x Bending y-y Bending ksi YesMinimum Basic Y-Y (depth) axis : X-X (width) axis : Fully braced against buckling ABOUT X-X Axis Fully braced against buckling ABOUT Y-Y Axis Brace condition for deflection (buckling) along columns : Service loads entered. Load Factors will be applied for calculations.Applied Loads Column self weight included : 134.027 lbs * Dead Load Factor AXIAL LOADS . . . Gravity: Axial Load at 14.0 ft, D = 0.880, L = 2.20 k BENDING LOADS . . . Lat. Point Load at 14.0 ft creating Mx-x, W = 0.0540 k Lat. Uniform Load creating Mx-x, W = 0.090 k/ft DESIGN SUMMARY PASS PASS Max. Axial+Bending Stress Ratio =0.7233 Location of max.above base 0.0 ft Applied Axial 3.417 k Applied Mx -9.576 k-ft Load Combination +1.20D+0.50Lr+L+W+1.60H Load Combination +0.90D+W+1.60H Bending & Shear Check Results Maximum Shear Stress Ratio = Applied Design Shear 41.063 psi 313.20Allowable Shear psi 0.08740 : 1 Bending Compression Tension LRFD - Format Conversion factor 2.541 2.400 2.700 LRFD - Resistance factor 0.850 0.900 0.800 Location of max.above base 0.0 ft : 1 At maximum location values are . . . Applied My 0.0 k-ft Maximum SERVICE Lateral Load Reactions . . Top along Y-Y 0.0 k Bottom along Y-Y 1.314 k Top along X-X 0.0 k Bottom along X-X 0.0 kGoverning NDS Forumla11Comp + Mxx, NDS Eq. 3.9-3 Maximum SERVICE Load Lateral Deflections . . . Along Y-Y 2.022 in at 14.0 ft above base for load combination :W Only Along X-X 0.0 in at 0.0 ft above base Fc : Allowable 3,132.0 psi Other Factors used to calculate allowable stresses . . . for load combination :n/a Maximum Axial + Bending Stress Ratios Maximum Shear RatiosCLambdaLoad Combination Stress Ratio Location Stress Ratio Status LocationPStatus Load Combination Results +1.40D+1.60H 0.600 PASS PASS0.0 0.0 0.0 ft1.000 ft0.01574 +1.20D+0.50Lr+1.60L+1.60H 0.800 PASS PASS0.0 0.0 0.0 ft1.000 ft0.03939 +1.20D+1.60L+0.50S+1.60H 0.800 PASS PASS0.0 0.0 0.0 ft1.000 ft0.03939 +1.20D+1.60Lr+L+1.60H 0.800 PASS PASS0.0 0.0 0.0 ft1.000 ft0.02841 +1.20D+1.60Lr+0.50W+1.60H 0.800 PASS PASS0.0 0.05463 0.0 ft1.000 ft0.4519 +1.20D+L+1.60S+1.60H 0.800 PASS PASS0.0 0.0 0.0 ft1.000 ft0.02841 +1.20D+1.60S+0.50W+1.60H 0.800 PASS PASS0.0 0.05463 0.0 ft1.000 ft0.4519 +1.20D+0.50Lr+L+W+1.60H 1.000 PASS PASS0.0 0.08740 0.0 ft1.000 ft0.7233 19 Wood Column ROGUE RICHARDSONLic. # : KW-06008302 DESCRIPTION:Field Column Title Block Line 1 You can change this area using the "Settings" menu item and then using the "Printing & Title Block" selection. Title Block Line 6 Software copyright ENERCALC, INC. 1983-2020, Build:12.20.8.17 File: circle d pole barn.ec6 Project Title: Engineer: Project ID: Printed: 26 JUL 2021, 5:57PM Project Descr: Maximum Axial + Bending Stress Ratios Maximum Shear RatiosCLambdaLoad Combination Stress Ratio Location Stress Ratio Status LocationPStatus Load Combination Results +1.20D+L+0.50S+W+1.60H 1.000 PASS PASS0.0 0.08740 0.0 ft1.000 ft0.7233 +0.90D+W+1.60H 1.000 PASS PASS0.0 0.08740 0.0 ft1.000 ft0.7229 +1.20D+L+0.20S+E+1.60H 1.000 PASS PASS0.0 0.0 0.0 ft1.000 ft0.02273 +0.90D+E+0.90H 1.000 PASS PASS0.0 0.0 0.0 ft1.000 ft0.006071 k k-ft Note: Only non-zero reactions are listed. Load Combination X-X Axis Reaction Y-Y Axis Reaction Axial Reaction @ Base @ Top @ Base@ Base @ Top Maximum Reactions @ Base @ Base@ Top @ Top My - End Moments Mx - End Moments +D+H 1.014 +D+L+H 3.214 +D+Lr+H 1.014 +D+S+H 1.014 +D+0.750Lr+0.750L+H 2.664 +D+0.750L+0.750S+H 2.664 +D+0.60W+H 1.0140.788 5.746 +D+0.750Lr+0.750L+0.450W+H 2.6640.591 4.309 +D+0.750L+0.750S+0.450W+H 2.6640.591 4.309 +0.60D+0.60W+0.60H 0.6080.788 5.746 +D+0.70E+0.60H 1.014 +D+0.750L+0.750S+0.5250E+H 2.664 +0.60D+0.70E+H 0.608 D Only 1.014 Lr Only L Only 2.200 S Only W Only 1.314 9.576 E Only H Only Maximum Deflections for Load Combinations Max. X-X Deflection Max. Y-Y Deflection DistanceLoad Combination Distance +D+H 0.0000 0.0000 0.000 ftft inin 0.000 +D+L+H 0.0000 0.0000 0.000 ftft inin 0.000 +D+Lr+H 0.0000 0.0000 0.000 ftft inin 0.000 +D+S+H 0.0000 0.0000 0.000 ftft inin 0.000 +D+0.750Lr+0.750L+H 0.0000 0.0000 0.000 ftft inin 0.000 +D+0.750L+0.750S+H 0.0000 0.0000 0.000 ftft inin 0.000 +D+0.60W+H 0.0000 1.2135 14.000 ftft inin 0.000 +D+0.750Lr+0.750L+0.450W+H 0.0000 0.9101 14.000 ftft inin 0.000 +D+0.750L+0.750S+0.450W+H 0.0000 0.9101 14.000 ftft inin 0.000 +0.60D+0.60W+0.60H 0.0000 1.2135 14.000 ftft inin 0.000 +D+0.70E+0.60H 0.0000 0.0000 0.000 ftft inin 0.000 +D+0.750L+0.750S+0.5250E+H 0.0000 0.0000 0.000 ftft inin 0.000 +0.60D+0.70E+H 0.0000 0.0000 0.000 ftft inin 0.000 D Only 0.0000 0.0000 0.000 ftft inin 0.000 Lr Only 0.0000 0.0000 0.000 ftft inin 0.000 L Only 0.0000 0.0000 0.000 ftft inin 0.000 S Only 0.0000 0.0000 0.000 ftft inin 0.000 W Only 0.0000 2.0224 14.000 ftft inin 0.000 E Only 0.0000 0.0000 0.000 ftft inin 0.000 H Only 0.0000 0.0000 0.000 ftft inin 0.000 20 Wood Column ROGUE RICHARDSONLic. # : KW-06008302 DESCRIPTION:Field Column Title Block Line 1 You can change this area using the "Settings" menu item and then using the "Printing & Title Block" selection. Title Block Line 6 Software copyright ENERCALC, INC. 1983-2020, Build:12.20.8.17 File: circle d pole barn.ec6 Project Title: Engineer: Project ID: Printed: 26 JUL 2021, 5:57PM Project Descr: Sketches 21 Rogue Richardson, PE CLIENT:AJB Contractors 1720 S Powerline JOB: 16' x 44' Pole Structure Nampa, ID 83686 DESCRIPTION: End Wall (208) 463-7670 DESIGNER: Rogue Richardson DATE: Comments: 14 ft 13.3 psf Controlling Tributary Width =8 ft Distributed Load along Column = 8 * 13.3 = 106.4 lbs Jul. 26, 2021 Controlling End Wall Column 22 Wood Column ROGUE RICHARDSONLic. # : KW-06008302 DESCRIPTION:Front/Back Wall Column Title Block Line 1 You can change this area using the "Settings" menu item and then using the "Printing & Title Block" selection. Title Block Line 6 Software copyright ENERCALC, INC. 1983-2020, Build:12.20.8.17 File: circle d pole barn.ec6 Project Title: Engineer: Project ID: Printed: 26 JUL 2021, 5:58PM Project Descr: Code References Calculations per NDS 2018, IBC 2018, CBC 2019, ASCE 7-16 Load Combinations Used : ASCE 7-16 General Information Wood Section Name 6x6Analysis Method : 14Overall Column Height ft Allowable Stress Design ( Used for non-slender calculations )Allow Stress Modification Factors End Fixities Top Pinned, Bottom Fixed Wood Species Hem-Fir (North) Wood Grade No. 1/No. 2 Fb +1,000.0 1,000.0 psi 1,450.0 405.0 145.0 575.0 28.720 psi Fv psi Fb - Ft psi Fc - Prll psi psi Density pcf Fc - Perp E : Modulus of Elasticity . . . 1,600.0 580.0 1,600.0 580.0 Cfu : Flat Use Factor 1.0 Cf or Cv for Tension 1.0 Use Cr : Repetitive ? Kf : Built-up columns 1.0 NDS 15.3.2 Exact Width 6.0 in Exact Depth 6.0 in Area 36.0 in^2 Ix 108.0 in^4 Iy 108.0 in^4 Wood Grading/Manuf.Graded Lumber Wood Member Type Sawn Ct : Temperature Factor 1.0 Cf or Cv for Compression 1.0 1,600.0 Axial Cm : Wet Use Factor 1.0 Cf or Cv for Bending 1.0 x-x Bending y-y Bending ksi YesMinimum Basic Y-Y (depth) axis : X-X (width) axis : Fully braced against buckling ABOUT X-X Axis Fully braced against buckling ABOUT Y-Y Axis Brace condition for deflection (buckling) along columns : Service loads entered. Load Factors will be applied for calculations.Applied Loads Column self weight included : 100.520 lbs * Dead Load Factor BENDING LOADS . . . Lat. Uniform Load creating My-y, W = 0.1070 k/ft DESIGN SUMMARY PASS PASS Max. Axial+Bending Stress Ratio =0.2849 Location of max.above base 0.0 ft Applied Axial 0.1005 k Applied Mx 0.0 k-ft Load Combination +D+0.60W+H Load Combination +D+0.60W+H Bending & Shear Check Results Maximum Shear Stress Ratio = Applied Design Shear 23.406 psi 232.0Allowable Shear psi 0.1009 : 1 Bending Compression Tension Location of max.above base 0.0 ft : 1 At maximum location values are . . . Applied My -1.573 k-ft Maximum SERVICE Lateral Load Reactions . . Top along Y-Y 0.0 k Bottom along Y-Y 0.0 k Top along X-X 0.5618 k Bottom along X-X 0.9363 kGoverning NDS Forumla Comp + Myy, NDS Eq. 3.9-3 Maximum SERVICE Load Lateral Deflections . . . Along Y-Y 0.0 in at 0.0 ft above base for load combination :n/a Along X-X 0.2226 in at 8.175 ft above base Fc : Allowable 2,320.0 psi Other Factors used to calculate allowable stresses . . . for load combination :W Only Maximum Axial + Bending Stress Ratios Maximum Shear RatiosCDCLoad Combination Stress Ratio Location Stress Ratio Status LocationPStatus Load Combination Results +D+H 0.900 PASS PASS0.0 0.0 14.0 ft1.000 ft0.002140 +D+L+H 1.000 PASS PASS0.0 0.0 14.0 ft1.000 ft0.001926 +D+Lr+H 1.250 PASS PASS0.0 0.0 14.0 ft1.000 ft0.001541 +D+S+H 1.150 PASS PASS0.0 0.0 14.0 ft1.000 ft0.001674 +D+0.750Lr+0.750L+H 1.250 PASS PASS0.0 0.0 14.0 ft1.000 ft0.001541 +D+0.750L+0.750S+H 1.150 PASS PASS0.0 0.0 14.0 ft1.000 ft0.001674 +D+0.60W+H 1.600 PASS PASS0.0 0.1009 0.0 ft1.000 ft0.2849 +D+0.750Lr+0.750L+0.450W+H 1.600 PASS PASS0.0 0.07567 0.0 ft1.000 ft0.2137 +D+0.750L+0.750S+0.450W+H 1.600 PASS PASS0.0 0.07567 0.0 ft1.000 ft0.2137 +0.60D+0.60W+0.60H 1.600 PASS PASS0.0 0.1009 0.0 ft1.000 ft0.2849 +D+0.70E+0.60H 1.600 PASS PASS0.0 0.0 14.0 ft1.000 ft0.001204 +D+0.750L+0.750S+0.5250E+H 1.600 PASS PASS0.0 0.0 14.0 ft1.000 ft0.001204 23 Wood Column ROGUE RICHARDSONLic. # : KW-06008302 DESCRIPTION:Front/Back Wall Column Title Block Line 1 You can change this area using the "Settings" menu item and then using the "Printing & Title Block" selection. Title Block Line 6 Software copyright ENERCALC, INC. 1983-2020, Build:12.20.8.17 File: circle d pole barn.ec6 Project Title: Engineer: Project ID: Printed: 26 JUL 2021, 5:58PM Project Descr: Maximum Axial + Bending Stress Ratios Maximum Shear RatiosCDCLoad Combination Stress Ratio Location Stress Ratio Status LocationPStatus Load Combination Results +0.60D+0.70E+H 1.600 PASS PASS0.0 0.0 14.0 ft1.000 ft0.000722 k k-ft Note: Only non-zero reactions are listed. Load Combination X-X Axis Reaction Y-Y Axis Reaction Axial Reaction @ Base @ Top @ Base@ Base @ Top Maximum Reactions @ Base @ Base@ Top @ Top My - End Moments Mx - End Moments +D+H 0.101 +D+L+H 0.101 +D+Lr+H 0.101 +D+S+H 0.101 +D+0.750Lr+0.750L+H 0.101 +D+0.750L+0.750S+H 0.101 +D+0.60W+H 0.1010.562 0.337 1.573 +D+0.750Lr+0.750L+0.450W+H 0.1010.421 0.253 1.180 +D+0.750L+0.750S+0.450W+H 0.1010.421 0.253 1.180 +0.60D+0.60W+0.60H 0.0600.562 0.337 1.573 +D+0.70E+0.60H 0.101 +D+0.750L+0.750S+0.5250E+H 0.101 +0.60D+0.70E+H 0.060 D Only 0.101 Lr Only L Only S Only W Only 0.936 0.562 2.621 E Only H Only Maximum Deflections for Load Combinations Max. X-X Deflection Max. Y-Y Deflection DistanceLoad Combination Distance +D+H 0.0000 0.0000 0.000 ftft inin 0.000 +D+L+H 0.0000 0.0000 0.000 ftft inin 0.000 +D+Lr+H 0.0000 0.0000 0.000 ftft inin 0.000 +D+S+H 0.0000 0.0000 0.000 ftft inin 0.000 +D+0.750Lr+0.750L+H 0.0000 0.0000 0.000 ftft inin 0.000 +D+0.750L+0.750S+H 0.0000 0.0000 0.000 ftft inin 0.000 +D+0.60W+H 0.1336 0.0000 0.000 ftft inin 8.174 +D+0.750Lr+0.750L+0.450W+H 0.1002 0.0000 0.000 ftft inin 8.174 +D+0.750L+0.750S+0.450W+H 0.1002 0.0000 0.000 ftft inin 8.174 +0.60D+0.60W+0.60H 0.1336 0.0000 0.000 ftft inin 8.174 +D+0.70E+0.60H 0.0000 0.0000 0.000 ftft inin 0.000 +D+0.750L+0.750S+0.5250E+H 0.0000 0.0000 0.000 ftft inin 0.000 +0.60D+0.70E+H 0.0000 0.0000 0.000 ftft inin 0.000 D Only 0.0000 0.0000 0.000 ftft inin 0.000 Lr Only 0.0000 0.0000 0.000 ftft inin 0.000 L Only 0.0000 0.0000 0.000 ftft inin 0.000 S Only 0.0000 0.0000 0.000 ftft inin 0.000 W Only 0.2226 0.0000 0.000 ftft inin 8.174 E Only 0.0000 0.0000 0.000 ftft inin 0.000 H Only 0.0000 0.0000 0.000 ftft inin 0.000 24 Wood Column ROGUE RICHARDSONLic. # : KW-06008302 DESCRIPTION:Front/Back Wall Column Title Block Line 1 You can change this area using the "Settings" menu item and then using the "Printing & Title Block" selection. Title Block Line 6 Software copyright ENERCALC, INC. 1983-2020, Build:12.20.8.17 File: circle d pole barn.ec6 Project Title: Engineer: Project ID: Printed: 26 JUL 2021, 5:58PM Project Descr: Sketches 25 Pole Footing Embedded in Soil ROGUE RICHARDSONLic. # : KW-06008302 DESCRIPTION:Controlling Column Footing Title Block Line 1 You can change this area using the "Settings" menu item and then using the "Printing & Title Block" selection. Title Block Line 6 Software copyright ENERCALC, INC. 1983-2020, Build:12.20.8.17 File: circle d pole barn.ec6 Project Title: Engineer: Project ID: Printed: 26 JUL 2021, 5:55PM Project Descr: Code References Calculations per IBC 2018 1807.3, CBC 2019, ASCE 7-16 Load Combinations Used : ASCE 7-16 General Information Circular 24.0 200.0 2,500.0 Lateral Restraint at Ground Surface Pole Footing Shape Pole Footing Diameter . . . . . . . . . . .in Allow Passive . . . . . . . . . . . . . . . . . . pcf Max Passive . . . . . . . . . . . . . . . . . . . psf Calculate Min. Depth for Allowable Pressures +D+0.60W+HGoverning Load Combination : Lateral Load 0.7884 Moment 5.746 k-ft Minimum Required Depth 4.0 ft k Restraint @ Ground Surface Pressure at Depth Actual 763.09 psf Allowable 800.0 psf Surface Retraint Force 3,840.75 lbs Controlling Values ft^2Footing Base Area 3.142 Maximum Soil Pressure 0.9804 ksf k k k 0.880 k 2.20 k Applied Loads k Lateral Concentrated Load (k) D : Dead Load L : Live Lr : Roof Live S : Snow W : Wind E : Earthquake H : Lateral Earth Load distance above 0.0540 14.0 k k k k k k k ft Lateral Distributed Loads (klf) TOP of Load above ground surface BOTTOM of Load above ground surface 0.090 14.0 k/ft k/ft k/ft k/ft k/ft k/ft k/ft ft Applied Moment (kft) k-ft k-ft k-ft k-ft k-ft k-ft k-ft ground surface ft Vertical Load (k) k Load Combination Results Factor Soil IncreaseForces @ Ground Surface Load Combination Required Loads - (k) Moments - (ft-k) Depth - (ft) Pressure at Depth Allow - (psf)Actual - (psf) 0.00.000 0.000+D+H 0.13 1.00025.0 0.00.000 0.000+D+L+H 0.13 1.00025.0 0.00.000 0.000+D+Lr+H 0.13 1.00025.0 0.00.000 0.000+D+S+H 0.13 1.00025.0 0.00.000 0.000+D+0.750Lr+0.750L+H 0.13 1.00025.0 0.00.000 0.000+D+0.750L+0.750S+H 0.13 1.00025.0 763.10.788 5.746+D+0.60W+H 4.00 1.000800.0 696.90.591 4.309+D+0.750Lr+0.750L+0.450W+H 3.63 1.000725.0 696.90.591 4.309+D+0.750L+0.750S+0.450W+H 3.63 1.000725.0 26 Pole Footing Embedded in Soil ROGUE RICHARDSONLic. # : KW-06008302 DESCRIPTION:Controlling Column Footing Title Block Line 1 You can change this area using the "Settings" menu item and then using the "Printing & Title Block" selection. Title Block Line 6 Software copyright ENERCALC, INC. 1983-2020, Build:12.20.8.17 File: circle d pole barn.ec6 Project Title: Engineer: Project ID: Printed: 26 JUL 2021, 5:55PM Project Descr: 763.10.788 5.746+0.60D+0.60W+0.60H 4.00 1.000800.0 0.00.000 0.000+D+0.70E+0.60H 0.13 1.00025.0 0.00.000 0.000+D+0.750L+0.750S+0.5250E+H 0.13 1.00025.0 0.00.000 0.000+0.60D+0.70E+H 0.13 1.00025.0 27