Life Safety PlanLIFE SAFETY LEGEND
XX"36"#
EXIT LOAD
EXIT WIDTH PROVIDED
EXIT WIDTH REQUIRED
# SF
#
#
ROOM NAME
ROOM #
A-1
SQUARE FOOTAGE OF ROOM
USE GROUP / LOAD FACTOR
OCCUPANT LOAD OF ROOM
EGRESS PATH
XX'INDICATES DISTANCE OF TRAVEL
INDICATES MOST REMOTE
LOCATION FROM EXIT
EXIT SIGN, REFER TO ELECTRICAL
FIRE EXTINGUISHER BRACKET (FEB)
OCCUPANT EGRESS AT
DOOR/STAIR TAG
OCCUPANT LOAD
ROOM TAG
1
B
A
2
71'
91.8 36"102"76"28'
10 2"36"
88'
36 SF
1
300
STORAGE
CLOSET
102
H-4
1698 SF
17
100
PUMP ROOM
101
H-4
405 SF
2
300
CHLORINE
ROOM
103
H-4
299 SF
ELECTRICAL
ROOM
104
54 SF
1
300
FIRE ROOM
106
H-498 SF
1
300
BLOWER ROOM
105
H-4
M
AX. O
VERALL DIA
G
O
NAL
78' - 5"SEPARATION DISTANCE > 1/3
33' - 9"
FIRE RATED WALLS LEGEND
2 HOUR RATED WALL
THIS DRAWING WAS PREPARED BY POWER
ARCHITECTURAL CONSULTANTS, INC. FOR A
SPECIFIC PROJECT. TAKING INTO CONSIDERATION
THE SPECIFIC AND UNIQUE REQUIRMENTS OF THE
PROJECT. REUSE OF THIS DRAWING OR ANY
INFORMATION CONTAINED IN THIS DRAWING FOR
ANY PURPOSE IS PROHIBITED UNLESS WRITTEN
PERMISSION FROM BOTH POWER AND POWER'S
CLIENT IS GRANTED.
DRAWING NO.
BAR IS ONE INCH ON
FULL SIZE DRAWING
0 1"
IDAHO OFFICES
BOISE · LEWISTON · MCCALL
ENGINEERING AND ENVIRONMENTAL SOLUTIONS
1161 W RIVER ST, STE 130
BOISE, IDAHO 83702
208.780.3990 DATE
PROJECT
VERIFY SCALENO.REVISION BY DATE DESIGN
DRAWN
CHECKED
APPROVED
10/22/20
TOW1/27/2021 11:20:28 AMA1.0
CITY OF MERIDIAN
LIFE SAFETY PLAN
167064
YM
BJT
SJB
WELL 17 TREATMENT FACILITY
0'2' 4' 8'
1/4" = 1'-0"1/4" = 1'-0"
LIFE SAFETY PLAN1
LIFE SAFETY PLAN NOTES
1. ALL EXITS SHALL HAVE EXIT SIGNS AND ALL BLIND CORRIDOR
TURNS SHALL HAVE DIRECTIONAL EXIT SIGNS.
2. CHANGE OF LEVEL AT ALL EXITS AND ENTRANCES SHALL NOT
EXCEED 1/2". NOTIFY ARCHITECT OF ANY DISCREPANCIES.
FIRE EXTINGUISHER NOTES
1. LOCATIONS AND CLASSIFICATIONS OF FIRE
EXTINGUISHERS SHALL BE IN ACCORDANCE WITH STATE &
LOCAL FIRE CODE AND IS SUBJECT TO THE APPROVAL OF
THE AHJ.
2. EXACT LOCATION AND QUANTITY OF FIRE EXTINGUISHER
CABINETS/BRACKETS TO BE CONFIRMED PRIOR TO
INSTALLATION.
3. ALL PORTABLE FIRE EXTINGUISHERS SHALL BE PROVIDED
AND INSTALLED BY CONTRACTOR BASED ON THE
FOLLOWING CRITERIA:
A. FIRE EXTINGUISHER TYPE (FE-1):
4-A:80-B:C
APPLICABLE PROJECT AREA:
INDUSTRIAL AREAS
CLASSIFICATION OF HAZARDS:
EXTRA (HIGH) HAZARD OCCUPANCY
MAXIMUM AREA TO BE PROTECTED PER EXTINGUISHER:
11,250 SQ. FT.
MAXIMUM DISTANCE TRAVELED:
75 FEET
4. FIRE EXTINGUISHERS MOUNTED IN UNHEATED AREAS
SHALL BE RATED FOR ANTICIPATED TEMPERATURES
TRUE
NORTH
PLANT
NORTHNORTH
PRELIMINARY
NOT FOR
CONSTRUCTION
A ISSUED FOR 60% REVIEW BJT 11/10/20
B ISSUED FOR 90% REVIEW BJT 01/27/21