M5.1_HVAC SchedulesREMARKS: 1. APPROVED ALTERNATE MANUFACTURERS: BRYANT, TRANE, AAON AND LENNOX. 2. CONTROLLED BY DDC. PROVIDE UNIT WITH SAFETIES ONLY. ALL CONTROLS WILL BE FIELD INSTALLED BY DDC CONTRACTOR. 3. PROVIDE UNIT WITH MANUFACTURER'S ROOF CURB, (SEE DETAIL FOR SEISMIC RESTRAINTS), FLUE EXTENDER, HAIL GUARDS, HIGH ALTITUDE KIT, THRU-THE-BOTTOM OF CURB ELECTRICAL CONNECTION KIT, HINGED ACCESS PANELS, MICROMETL GEAR DRIVEN INTEGRATED DRY BULB ECONOMIZER WITH BELIMO LOGIC ACTUATORS AND AUX END SWITCH, MODULATING POWER EXHAUST WITH VARIABLE SPEED MOTOR CONTROLLER (100% RELIEF) AND WIRING HARNESS, PRESSURE SENSOR SET TO .02 POSITIVE PRESSURE. 4. PROVIDE UNIT WITH MICROMETL WELDED ISOLATION CURB (SEE DETAIL FOR SEISMIC RESTRAINTS), FLUE EXTENDER, HAIL GUARDS, HIGH ALTITUDE KIT, THRU-THE-BOTTOM OF CURB ELECTRICAL CONNECTION KIT, HINGED ACCESS PANELS, MICROMETL GEAR DRIVEN INTEGRATED DRY BULB ECONOMIZER WITH BELIMO LOGIC ACTUATORS AND AUX END SWITCH, MODULATING POWER EXHAUST WITH VARIABLE SPEED MOTOR CONTROLLER (100% RELIEF) AND WIRING HARNESS, PRESSURE SENSOR SET TO .02 POSITIVE PRESSURE. 5. PROVIDE UNIT WITH DDC WALL MOUNTED C02 SENSOR. OUTSIDE AIR SHALL HAVE A MINIMUM SETPOINT OF ZERO AND THE DAMPER SHALL MODULATE OPEN AS REQUIRED TO SATISFY THE C02 SENSOR. THE OSA CFM LISTED IN THIS SCHEDULE SHALL BE THE MAXIMUM OSA DAMPER SETPOINT (IF NOT IN ECONOMIZER MODE). THE OUTSIDE AIR DAMPER SHALL CLOSE DURING THE UNOCCUPIED MODE. 6. PROVIDE 2" PLEATED MERV 8 FILTER AND FILTER RACK WITH 4 EXTRA SETS PER UNIT. 7. MAXIMUM "A-WEIGHTED" SUPPLY AIR SOUND RATINGS FOR UNITS 2-18 TONS = 95 DB @ 125 HZ, 90 DB @ 250 HZ, PER ARI STANDARDS 270 & 370. 8. MAXIMUM "A-WEIGHTED" SUPPLY AIR SOUND RATINGS FOR UNITS 20 TONS OR LARGER = 99 DB @ 125 HZ, 93 DB @ 250 HZ, PER ARI STANDARDS 270 & 370. PACKAGED AIR CONDITIONING SCHEDULE SYMBOL AREA SERVED NOM. TONS SUPPLY FAN COOLING REQUIRED 95° OSA, 80° EDB, 62° EWB GAS HEATING RTU ELECTRICAL ELECTRICAL POWER EXHAUST OSA CFM MIN. SEER / EER OPER. WEIGHT (LBS) MANUFACTURER AND MODEL REMARKS CFM ESP BRAKE HP DRIVE TOTAL MBH SENSIBLE MBH INPUT MBH OUTPUT MBH MCA MOCP V/Ø STATIC MCA MOCP V/Ø RTU-101A STAGE 5 2,000 .60 .86 ECM 59.9 51.2 110.0 81.8 12 15 460/3 .5 1.4 2.5 460/3 500 16.0 SEER 1,100 CARRIER 48GC06 HIGH EFFICIENCY 1 , 2 , 3 , 6 , 7 82.0 57.2 RTU-102A GYMNASIUM 20 8,000 .60 6.18 BELT 229.4 223.7 320.0 228.8 57.6 70 460/3 .5 10.8 20 460/3 2,200 12.0 EER 3,100 CARRIER 48HC24 HIGH EFFICIENCY 1 , 2 , 4 , 6 , 7 , 8 400.0 285.1 RTU-103A KITCHEN 5 2,000 .60 .86 ECM 59.9 51.2 110.0 81.8 12 15 460/3 .5 1.4 2.5 460/3 500 16.0 SEER 1,100 CARRIER 48GC06 HIGH EFFICIENCY 1 , 2 , 3 , 6 , 7 82.0 57.2 RTU-104A CAFETERIA 12.5 5,000 .60 1.98 BELT 140.2 139.0 194.0 137.3 30 35 460/3 .5 5.4 19.4 460/3 1,500 12.2 EER 2,000 CARRIER 48HC14 HIGH EFFICIENCY 1 , 2 , 4 , 5 , 6 , 7 240 171.6 RTU-105A MUSIC 4 1,600 .60 .68 ECM 45.4 44.3 110.0 81.8 11 15 460/3 .5 1.4 2.5 460/3 400 16.0 SEER 1,000 CARRIER 48GC05 HIGH EFFICIENCY 1 , 2 , 3 , 6 , 7 82.0 57.2 RTU-106A RECEPTION / OFFICE 3 1,200 .60 .35 ECM 31.4 30.5 110.0 81.8 10 15 460/3 .5 1.4 2.5 460/3 300 16.0 SEER 1,000 CARRIER 48GC04 HIGH EFFICIENCY 1 , 2 , 3 , 6 , 7 82.0 57.2 RTU-107A CORRIDOR 3 1,200 .60 .35 ECM 31.4 30.5 110.0 81.8 10 15 460/3 .5 1.4 2.5 460/3 300 16.0 SEER 1,000 CARRIER 48GC04 HIGH EFFICIENCY 1 , 2 , 3 , 6 , 7 82.0 57.2 RTU-101B CLASSROOM - EXTRA 5 2,000 .60 .86 ECM 59.9 51.2 110.0 81.8 12 15 460/3 .5 1.4 2.5 460/3 500 16.0 SEER 1,100 CARRIER 48GC06 HIGH EFFICIENCY 1 , 2 , 3 , 6 , 7 82.0 57.2 RTU-102B CLASSROOM - EXTRA 4 1,600 .60 .68 ECM 45.4 44.3 110.0 81.8 11 15 460/3 .5 1.4 2.5 460/3 400 16.0 SEER 1,000 CARRIER 48GC05 HIGH EFFICIENCY 1 , 2 , 3 , 6 , 7 82.0 57.2 RTU-103B CLASSROOM - 5TH 4 1,600 .60 .68 ECM 45.4 44.3 110.0 81.8 11 15 460/3 .5 1.4 2.5 460/3 400 16.0 SEER 1,000 CARRIER 48GC05 HIGH EFFICIENCY 1 , 2 , 3 , 6 , 7 82.0 57.2 RTU-104B CLASSROOM - 5TH 4 1,600 .60 .68 ECM 45.4 44.3 110.0 81.8 11 15 460/3 .5 1.4 2.5 460/3 400 16.0 SEER 1,000 CARRIER 48GC05 HIGH EFFICIENCY 1 , 2 , 3 , 6 , 7 82.0 57.2 RTU-105B CLASSROOM - 5TH 4 1,600 .60 .68 ECM 45.4 44.3 110.0 81.8 11 15 460/3 .5 1.4 2.5 460/3 400 16.0 SEER 1,000 CARRIER 48GC05 HIGH EFFICIENCY 1 , 2 , 3 , 6 , 7 82.0 57.2 RTU-106B CLASSROOM - 5TH 4 1,600 .60 .68 ECM 45.4 44.3 110.0 81.8 11 15 460/3 .5 1.4 2.5 460/3 400 16.0 SEER 1,000 CARRIER 48GC05 HIGH EFFICIENCY 1 , 2 , 3 , 6 , 7 82.0 57.2 RTU-107B CLASSROOM - 4TH 4 1,600 .60 .68 ECM 45.4 44.3 110.0 81.8 11 15 460/3 .5 1.4 2.5 460/3 400 16.0 SEER 1,000 CARRIER 48GC05 HIGH EFFICIENCY 1 , 2 , 3 , 6 , 7 82.0 57.2 RTU-108B CLASSROOM - 4TH 4 1,600 .60 .68 ECM 45.4 44.3 110.0 81.8 11 15 460/3 .5 1.4 2.5 460/3 400 16.0 SEER 1,000 CARRIER 48GC05 HIGH EFFICIENCY 1 , 2 , 3 , 6 , 7 82.0 57.2 RTU-109B CLASSROOM - 4TH 4 1,600 .60 .68 ECM 45.4 44.3 110.0 81.8 11 15 460/3 .5 1.4 2.5 460/3 400 16.0 SEER 1,000 CARRIER 48GC05 HIGH EFFICIENCY 1 , 2 , 3 , 6 , 7 82.0 57.2 RTU-110B CLASSROOM - 4TH 4 1,600 .60 .68 ECM 45.4 44.3 110.0 81.8 11 15 460/3 .5 1.4 2.5 460/3 400 16.0 SEER 1,000 CARRIER 48GC05 HIGH EFFICIENCY 1 , 2 , 3 , 6 , 7 82.0 57.2 RTU-111B CLASSROOM - 3RD 4 1,600 .60 .68 ECM 45.4 44.3 110.0 81.8 11 15 460/3 .5 1.4 2.5 460/3 400 16.0 SEER 1,000 CARRIER 48GC05 HIGH EFFICIENCY 1 , 2 , 3 , 6 , 7 82.0 57.2 RTU-112B CLASSROOM - 3RD 4 1,600 .60 .68 ECM 45.4 44.3 110.0 81.8 11 15 460/3 .5 1.4 2.5 460/3 400 16.0 SEER 1,000 CARRIER 48GC05 HIGH EFFICIENCY 1 , 2 , 3 , 6 , 7 82.0 57.2 RTU-101C CLASSROOM - 3RD 4 1,600 .60 .68 ECM 45.4 44.3 110.0 81.8 11 15 460/3 .5 1.4 2.5 460/3 400 16.0 SEER 1,000 CARRIER 48GC05 HIGH EFFICIENCY 1 , 2 , 3 , 6 , 7 82.0 57.2 RTU-102C COMPUTER LAB 5 2,000 .60 .86 ECM 59.9 51.2 110.0 81.8 12 15 460/3 .5 1.4 2.5 460/3 500 16.0 SEER 1,100 CARRIER 48GC06 HIGH EFFICIENCY 1 , 2 , 3 , 6 , 7 82.0 57.2 RTU-103C CONF. / WORK ROOM 3 1,200 .60 .35 ECM 31.4 30.5 110.0 81.8 10 15 460/3 .5 1.4 2.5 460/3 300 16.0 SEER 1,000 CARRIER 48GC04 HIGH EFFICIENCY 1 , 2 , 3 , 6 , 7 82.0 57.2 RTU-104C FACULTY 4 1,600 .60 .68 ECM 45.4 44.3 110.0 81.8 11 15 460/3 .5 1.4 2.5 460/3 400 16.0 SEER 1,000 CARRIER 48GC05 HIGH EFFICIENCY 1 , 2 , 3 , 6 , 7 82.0 57.2 PACKAGED AIR CONDITIONING SCHEDULE SYMBOL AREA SERVED NOM. TONS SUPPLY FAN COOLING REQUIRED 95° OSA, 80° EDB, 62° EWB GAS HEATING ELECTRICAL ELECTRICAL POWER EXHAUST OSA CFM MIN. SEER / EER OPER. WEIGHT (LBS) MANUFACTURER AND MODEL REMARKS CFM ESP BRAKE HP DRIVE TOTAL MBH SENSIBLE MBH INPUT MBH OUTPUT MBH MCA MOCP V/Ø STATIC MCA MOCP V/Ø RTU-101D PRE-SCHOOL 4 1,600 .60 .68 ECM 45.4 44.3 110.0 81.8 11 15 460/3 .5 1.4 2.5 460/3 400 16.0 SEER 1,000 CARRIER 48GC05 HIGH EFFICIENCY 1 , 2 , 3 , 4 , 5 , 6 82.0 57.2 RTU-102D KINDERGARTEN 4 1,600 .60 .68 ECM 45.4 44.3 110.0 81.8 11 15 460/3 .5 1.4 2.5 460/3 400 16.0 SEER 1,000 CARRIER 48GC05 HIGH EFFICIENCY 1 , 2 , 3 , 4 , 5 , 6 82.0 57.2 RTU-103D KINDERGARTEN 4 1,600 .60 .68 ECM 45.4 44.3 110.0 81.8 11 15 460/3 .5 1.4 2.5 460/3 400 16.0 SEER 1,000 CARRIER 48GC05 HIGH EFFICIENCY 1 , 2 , 3 , 4 , 5 , 6 82.0 57.2 RTU-104D PRE-SCHOOL 4 1,600 .60 .68 ECM 45.4 44.3 110.0 81.8 11 15 460/3 .5 1.4 2.5 460/3 400 16.0 SEER 1,000 CARRIER 48GC05 HIGH EFFICIENCY 1 , 2 , 3 , 4 , 5 , 6 82.0 57.2 RTU-105D SPECIAL EDUCATION 4 1,600 .60 .68 ECM 45.4 44.3 110.0 81.8 11 15 460/3 .5 1.4 2.5 460/3 400 16.0 SEER 1,000 CARRIER 48GC05 HIGH EFFICIENCY 1 , 2 , 3 , 4 , 5 , 6 82.0 57.2 RTU-106D CLASSROOM - 1ST 4 1,600 .60 .68 ECM 45.4 44.3 110.0 81.8 11 15 460/3 .5 1.4 2.5 460/3 400 16.0 SEER 1,000 CARRIER 48GC05 HIGH EFFICIENCY 1 , 2 , 3 , 4 , 5 , 6 82.0 57.2 RTU-107D SENSORY 3 1,200 .60 .35 ECM 31.4 30.5 110.0 81.8 10 15 460/3 .5 1.4 2.5 460/3 300 16.0 SEER 1,000 CARRIER 48GC04 HIGH EFFICIENCY 1 , 2 , 3 , 4 , 5 , 6 82.0 57.2 RTU-108D MEDIA CENTER 5 2,000 .60 .86 ECM 59.9 51.2 110.0 81.8 12 15 460/3 .5 1.4 2.5 460/3 500 16.0 SEER 1,100 CARRIER 48GC06 HIGH EFFICIENCY 1 , 2 , 3 , 4 , 5 , 6 82.0 57.2 RTU-109D SPECIAL EDUCATION 5 2,000 .60 .86 ECM 59.9 51.2 110.0 81.8 12 15 460/3 .5 1.4 2.5 460/3 500 16.0 SEER 1,100 CARRIER 48GC06 HIGH EFFICIENCY 1 , 2 , 3 , 4 , 5 , 6 82.0 57.2 RTU-101E CLASSROOM - EXTRA 5 2,000 .60 .86 ECM 59.9 51.2 110.0 81.8 12 15 460/3 .5 1.4 2.5 460/3 500 16.0 SEER 1,100 CARRIER 48GC06 HIGH EFFICIENCY 1 , 2 , 3 , 4 , 5 , 6 82.0 57.2 RTU-102E CLASSROOM - EXTRA 5 2,000 .60 .86 ECM 59.9 51.2 110.0 81.8 12 15 460/3 .5 1.4 2.5 460/3 500 16.0 SEER 1,100 CARRIER 48GC06 HIGH EFFICIENCY 1 , 2 , 3 , 4 , 5 , 6 82.0 57.2 RTU-103E CLASSROOM - 3RD 4 1,600 .60 .68 ECM 45.4 44.3 110.0 81.8 11 15 460/3 .5 1.4 2.5 460/3 400 16.0 SEER 1,000 CARRIER 48GC05 HIGH EFFICIENCY 1 , 2 , 3 , 4 , 5 , 6 82.0 57.2 RTU-104E CLASSROOM - 3RD 4 1,600 .60 .68 ECM 45.4 44.3 110.0 81.8 11 15 460/3 .5 1.4 2.5 460/3 400 16.0 SEER 1,000 CARRIER 48GC05 HIGH EFFICIENCY 1 , 2 , 3 , 4 , 5 , 6 82.0 57.2 RTU-105E CLASSROOM - 2ND 4 1,600 .60 .68 ECM 45.4 44.3 110.0 81.8 11 15 460/3 .5 1.4 2.5 460/3 400 16.0 SEER 1,000 CARRIER 48GC05 HIGH EFFICIENCY 1 , 2 , 3 , 4 , 5 , 6 82.0 57.2 RTU-106E CLASSROOM - 2ND 4 1,600 .60 .68 ECM 45.4 44.3 110.0 81.8 11 15 460/3 .5 1.4 2.5 460/3 400 16.0 SEER 1,000 CARRIER 48GC05 HIGH EFFICIENCY 1 , 2 , 3 , 4 , 5 , 6 82.0 57.2 RTU-107E CLASSROOM - 2ND 4 1,600 .60 .68 ECM 45.4 44.3 110.0 81.8 11 15 460/3 .5 1.4 2.5 460/3 400 16.0 SEER 1,000 CARRIER 48GC05 HIGH EFFICIENCY 1 , 2 , 3 , 4 , 5 , 6 82.0 57.2 RTU-108E CLASSROOM - 2ND 4 1,600 .60 .68 ECM 45.4 44.3 110.0 81.8 11 15 460/3 .5 1.4 2.5 460/3 400 16.0 SEER 1,000 CARRIER 48GC05 HIGH EFFICIENCY 1 , 2 , 3 , 4 , 5 , 6 82.0 57.2 RTU-109E CLASSROOM - 2ND 4 1,600 .60 .68 ECM 45.4 44.3 110.0 81.8 11 15 460/3 .5 1.4 2.5 460/3 400 16.0 SEER 1,000 CARRIER 48GC05 HIGH EFFICIENCY 1 , 2 , 3 , 4 , 5 , 6 82.0 57.2 RTU-110E CLASSROOM - 1ST 4 1,600 .60 .68 ECM 45.4 44.3 110.0 81.8 11 15 460/3 .5 1.4 2.5 460/3 400 16.0 SEER 1,000 CARRIER 48GC05 HIGH EFFICIENCY 1 , 2 , 3 , 4 , 5 , 6 82.0 57.2 RTU-111E CLASSROOM - 1ST 4 1,600 .60 .68 ECM 45.4 44.3 110.0 81.8 11 15 460/3 .5 1.4 2.5 460/3 400 16.0 SEER 1,000 CARRIER 48GC05 HIGH EFFICIENCY 1 , 2 , 3 , 4 , 5 , 6 82.0 57.2 RTU-112E CLASSROOM - 1ST 4 1,600 .60 .68 ECM 45.4 44.3 110.0 81.8 11 15 460/3 .5 1.4 2.5 460/3 400 16.0 SEER 1,000 CARRIER 48GC05 HIGH EFFICIENCY 1 , 2 , 3 , 4 , 5 , 6 82.0 57.2 REMARKS: 1. APPROVED ALTERNATE MANUFACTURERS: BRYANT, TRANE, AAON AND LENNOX. 2. CONTROLLED BY DDC. PROVIDE UNIT WITH SAFETIES ONLY. ALL CONTROLS WILL BE FIELD INSTALLED BY DDC CONTRACTOR. 3. PROVIDE UNIT WITH MANUFACTURER'S ROOF CURB, (SEE DETAIL FOR SEISMIC RESTRAINTS), FLUE EXTENDER, HAIL GUARDS, HIGH ALTITUDE KIT, THRU-THE-BOTTOM OF CURB ELECTRICAL CONNECTION KIT, HINGED ACCESS PANELS, MICROMETL GEAR DRIVEN INTEGRATED DRY BULB ECONOMIZER WITH BELIMO LOGIC ACTUATORS AND AUX END SWITCH, MODULATING POWER EXHAUST WITH VARIABLE SPEED MOTOR CONTROLLER (100% RELIEF) AND WIRING HARNESS, PRESSURE SENSOR SET TO .02 POSITIVE PRESSURE. 4. PROVIDE UNIT WITH DDC WALL MOUNTED C02 SENSOR. OUTSIDE AIR SHALL HAVE A MINIMUM SETPOINT OF ZERO AND THE DAMPER SHALL MODULATE OPEN AS REQUIRED TO SATISFY THE C02 SENSOR. THE OSA CFM LISTED IN THIS SCHEDULE SHALL BE THE MAXIMUM OSA DAMPER SETPOINT (IF NOT IN ECONOMIZER MODE). THE OUTSIDE AIR DAMPER SHALL CLOSE DURING THE UNOCCUPIED MODE. 5. PROVIDE 2" PLEATED MERV 8 FILTER AND FILTER RACK WITH 4 EXTRA SETS PER UNIT. 6. MAXIMUM "A-WEIGHTED" SUPPLY AIR SOUND RATINGS FOR UNITS 2-18 TONS = 95 DB @ 125 HZ, 90 DB @ 250 HZ, PER ARI STANDARDS 270 & 370. DIFFUSER SCHEDULE SYMBOL NOMINAL SIZE NECK / RUNOUT SIZE CFM RANGE REMARKS 6X6 6"Ø 0 - 90 1 , 2 , 3 , 4 , 5 , 6 , 7 9X9 8"Ø 90 - 200 1 , 2 , 3 , 4 , 5 , 6 , 7 12X12 10"Ø 200 - 350 1 , 2 , 3 , 4 , 5 , 6 , 7 15X15 12"Ø 300 - 500 1 , 2 , 3 , 4 , 5 , 6 , 7 18"X6" 18"X6" 275 - 475 2 , 4 , 5 , 6 , 7 , 8 6"Ø CFM D-1 8"Ø CFM D-2 10"Ø CFM D-3 12"Ø CFM D-4 18X6 CFM D-5 REMARKS: 1. SIZES BASED ON TITUS MODEL TDCA SERIES. APPROVED ALTERNATE MANUFACTURERS INCLUDE ANEMOSTAT, J&J REGISTER, NAILOR, METAL-AIRE, TUTTLE & BAILEY, KRUEGER, PRICE, AND UNITED ENERTECH. 2. SIZES BASED ON A MAXIMUM NC LEVEL OF 25. 3. ALL DIFFUSERS LOCATED IN LAY-IN CEILING AREAS SHALL BE BORDER TYPE 3 AND BE MOUNTED IN MANUFACTURER PROVIDED 24"x24" PANELS. ALL DIFFUSERS LOCATED IN HARD CEILING AREAS SHALL BE BORDER TYPE 6 (BEVELED) SURFACE MOUNTED. SEE ARCHITECTURAL PLANS FOR LOCATIONS OF VARIOUS CEILING TYPES. 4. SEE HVAC FLOOR PLANS FOR DIRECTIONAL THROW REQUIREMENTS FOR EACH DIFFUSER. 5. ALL OF THE DIFFUSERS SHOWN IN THIS SCHEDULE MAY NOT BE USED. REFERENCE THE HVAC PLAN FOR DIFFUSER CALL-OUTS AND THE QUANTITY OF EACH SIZE REQUIRED. 6. WHENEVER THERE IS A DISCREPANCY BETWEEN THE RUNOUT DUCT SIZE SHOWN ON THE PLANS AND THAT SHOWN IN THE SCHEDULE, ALWAYS USE THE LARGER OF THE TWO DUCT SIZES. 7. WHITE FINISH. 8. DRUM LOUVER, SIZES BASED ON TITUS MODEL S-DL. CURVED FRAME FOR ROUND OR SPIRAL DUCT, ADJUSTABLE VERTICAL AND HORIZONTAL THROW - HIGH DISCHARGE FOR LONG THROWS, OPPOSED BLADE DAMPER, WHITE FINISH. APPROVED ALTERNATE MANUFACTURERS INCLUDE ANEMOSTAT, CARNES, J&J REGISTER, TUTTLE & BAILEY, NAILOR, METAL-AIRE, KRUEGER, PRICE, AND UNITED ENERTECH. 6"Ø R-1 8"Ø R-2 10"Ø R-3 8"Ø R-5 10"Ø R-6 12"Ø R-7 14"Ø R-8 22X10 R-9 22X22 R-10 24X16 R-11 RETURN & EXHAUST GRILLE SCHEDULE SYMBOL NOMINAL SIZE NECK / RUNOUT SIZE CFM RANGE REMARKS 8X8 6"Ø 0-80 1 , 2 , 3 , 4 , 5 , 6 10X10 8"Ø 80-180 1 , 2 , 3 , 4 , 5 12X12 10"Ø 180-300 1 , 2 , 3 , 4 , 5 22X10 8"Ø 80-180 1 , 2 , 3 , 4 , 5 22X10 10"Ø 180-300 1 , 2 , 3 , 4 , 5 22X22 12"Ø 300-500 1 , 2 , 3 , 4 , 5 22X22 14"Ø 500-750 1 , 2 , 3 , 4 , 5 22X10 22X10 500-1100 1 , 2 , 3 , 4 , 5 22X22 22X22 1100-2000 1 , 2 , 3 , 4 , 5 24"X16" 24"X16" 1,050 - 1,300 2 , 6 REMARKS: 1. SIZES BASED ON TITUS MODEL 50F, ALUMINUM EGGCRATE RETURN GRILLE, 1/2" x 1/2" x 1" SPACING (SINGLE CORE). PROVIDE SQUARE TO ROUND TRANSITION (WHERE ROUND RUN-OUT INDICATED), WHITE FINISH. APPROVED ALTERNATE MANUFACTURERS INCLUDE , ANEMOSTAT, CARNES, PRICE, NAILOR, METAL-AIRE, TUTTLE & BAILEY, KRUEGER, J&J REGISTER, AND UNITED ENERTECH. 2. SIZES BASED ON A MAXIMUM NC LEVEL OF 25. 3. ALL GRILLES LOCATED IN LAY-IN CEILING AREAS SHALL HAVE BORDER #3, UNLESS OTHERWISE INDICATED. ALL GRILLES LOCATED IN HARD CEILING AREAS SHALL HAVE BORDER #1, UNLESS OTHERWISE INDICATED. REFER TO ARCHITECTURAL PLANS FOR LOCATIONS OF VARIOUS CEILING TYPES. SHEET METAL DUCTWORK VISIBLE BEHIND GRILLE SHALL BE PAINTED FLAT BLACK. 4. ALL OF THE GRILLES SHOWN IN THIS SCHEDULE MAY NOT BE USED. REFERENCE THE HVAC PLAN FOR GRILLE CALL-OUTS AND THE QUANTITY OF EACH SIZE REQUIRED. 5. WHENEVER THERE IS A DISCREPANCY BETWEEN THE RUNOUT DUCT SIZE SHOWN ON THE PLANS AND THAT SHOWN IN THE SCHEDULE, ALWAYS USE THE LARGER OF THE TWO DUCT SIZES. 6. WALL GRILLE SIZES BASED ON TITUS MODEL 33R, HEAVY DUTY STEEL, 14 GAUGE BLADES, 1/2" SPACING, 38° DEFLECTION, ALL-WELDED CONSTRUCTION., WHITE FINISH APPROVED ALTERNATE MANUFACTURERS INCLUDE ANEMOSTAT, CARNES, J&J REGISTER, NAILOR, TUTTLE & BAILEY, KRUEGER, PRICE, AND UNITED ENERTECH. DESTRATIFICATION FAN SCHEDULE SYMBOL AREA SERVED UNIT TYPE BLOWER ELECTRICAL MAXIMUM SONES OPERATING WEIGHT (LBS) MANUFACTURER AND MODEL REMARKS CFM MAXIMUM RPM DRIVE WATTS AMPS V/Ø DF-101 GYMNASIUM FREE HANGING 600 1,700 DIRECT 30 0.4 120/1∅ N/A 15 AIRIUS AIR PEAR MODEL 25 EC-SH 1 , 2 , 3 , 4 DF-102 GYMNASIUM FREE HANGING 600 1,700 DIRECT 30 0.4 120/1∅ N/A 15 AIRIUS AIR PEAR MODEL 25 EC-SH 1 , 2 , 3 , 4 DF-103 GYMNASIUM FREE HANGING 600 1,700 DIRECT 30 0.4 120/1∅ N/A 15 AIRIUS AIR PEAR MODEL 25 EC-SH 1 , 2 , 3 , 4 DF-104 GYMNASIUM FREE HANGING 600 1,700 DIRECT 30 0.4 120/1∅ N/A 15 AIRIUS AIR PEAR MODEL 25 EC-SH 1 , 2 , 3 , 4 DF-105 CAFETERIA FREE HANGING 600 1,700 DIRECT 30 0.4 120/1∅ N/A 15 AIRIUS AIR PEAR MODEL 25 EC-SH 1 , 2 , 3 , 4 DF-106 CAFETERIA FREE HANGING 600 1,700 DIRECT 30 0.4 120/1∅ N/A 15 AIRIUS AIR PEAR MODEL 25 EC-SH 1 , 2 , 3 , 4 REMARKS: 1. APPROVED ALTERNATE MANUFACTURERS: SUBMIT FOR APPROVAL. 2. CONTROL FAN THROUGH DDC SYSTEM WITH WALL MOUNTED OVERRIDE SWITCH. FAN SHALL BE CAPABLE OF SHUTDOWN WITH FIRE ALARM SYSTEM. 3. PROVIDE W/ EYE BOLT, BEAM CLAMP BRIDAL RING, CHAINLINK/CARABINEER, 6' STEEL LEASH AND ANCHOR POINT, SAFETY CABLE , 6' POWER CHORD, THERMAL PROTECTION FOR MOTOR, ELECTRICAL CONNECTION AND JUNCTION BOX, 3-YEAR WARRANTY PARTS AND WORKMANSHIP. 4. COORDINATE COLOR WITH ARCHITECT. DRAWING NO.: 2400 E. Riverwalk Drive Boise, Idaho 83706 www.lkvarchitects.com 208.336.3443 DATE: LKV PROJECT #: DRAWN BY: CHECKED BY: 18-186 M5.1 HVAC SCHEDULESHVAC SCHEDULESHVAC SCHEDULESHVAC SCHEDULES 03/13/202003/13/202003/13/202003/13/2020 GPBGPBGPBGPB WACWACWACWACBLUE VALLEY ELEMENTARY SCHOOLWEST ADA SCHOOL DISTRICTW. AMERICAN FORK DR.BID SETRevisions# DescriptionDate3/12/2020