HomeMy WebLinkAboutFire Department CommentsMAYOR
ROBERT D. CORRIE
CxrEF
KEN W. BOWERS
COUNCE. MEMBERS ~ DEPUPY CrFi>EF -FIRE PREVENTION
WEav.M L.M. NARY JOSEPH Sllva
KErrxBBan
DEPITl'Y CFllEF - TRARJING
TaMMY DE WEERD
CrrER~McCaNnI.ESS cm' oP
\
~I~l~n `~~y BnzJors~soN
RvRacFmECoam,ESSIONBRS ~` M Ll/ `~ 540 EastFraoklinRoad
R[cxaRn OREENE ionrio
~. Meridian, ID 83642
TERRY LEIOHTON ~C~ (208) 888-1234
STEVEEcuoTT T ~ ev ~ ~~ Fax (208)895-0390
MERIDIAN CITY/RURAL FIRE DEPARTMENT
R~J 1 ~ !_I d. V 1.'~ ~~
December 31, 2003
DEC 3 1 2003
i;ity Of Meridian
City Clerk Office
TO: Mayor, City Council & Meridian Planning & Zoning Commission
FROM: Joseph Silva, Deputy Chief; Fire Prevention
SUBJECT: Wendy's Subdivision FP 03-068
The following will be the requirements and/or concerns to provide minimum levels of fire
protection for the proposed project:
1. That afire-flow as required by the lntwnational Fire Code is provided to service the
entire project. Fire hydrants shalt be placed an average of 3 50' apart.
2. Acceptance of the water supply for fire protection will be by the Meridian
water Department.
3. Final Approval of the fire hydrant locations shall be by the Meridian Fire
Department. Additionally, ir-temal fire hydrants may ba required for the project.
4. All entrances and internal roads shall have a turning radius of 28' inside and 48'
outside.
5. Operational fire hydrants and access roads are required before combustible
construction begins.
6. No vertical obstructions or mature landscaping which obstructions the outlets of the
fire hydram within 10'.
Vertical clearance fnr driveways shall be 13'6", this may affect tree placement in
landscaping areas.
8. All fire lanes shall have a clear driving surface which is20' wide available at all
times.