Loading...
HomeMy WebLinkAboutIndependent Contractor Agreement with Clima-Tech for Supply and Installation of Auto Temp Control SystemAGREEMENT FOR INDEPENDENT CONTRACTOR SERVICES AUTOMATIC TEMPERATURE CONTROL SYSTEM PROJECT #1322B THIS AGREEMENT FOR INDEPENDENT CONTRACTOR RACTOR SERVICES is made this 9 day of August, 2011, and entered into by and between the City of Meridian, a municipal corporationorganized under the laws of the State of Idaho, hereinafter referred to as "CITY", 33 East Broadway Avenue ' . y ,Meridian, Idaho 83642, and Clima- Tech Corporation, hereinafter referred to as "CONTRACTOR", whose business address is 875 W. McGregor Ct. Ste 180 Boise and whose Public ID 83705 c Works Contractor License # is C-10307. INTRODUCTION Whereas, the City has a need for services involving =pply and Installation of Automatic Tem erature Control S stem • and WHEREAS, the Contractor is special) trained competent y experienced and com p t to perform and has agreed to provide such services; NOW, THEREFORE, in consideration of the mutual promises, covenants, terms and conditions hereinafter contained thearti • p es agree as follows. TERMS AND CONDITIONS 1. Scope of Work: 1.1 CONTRACTOR shall perform and furnish to the City ty upon execution of this Agreement and receipt of the City's written notice Y to proceed, all services and work, and comply in all respects, as specified in p the document titled "Scope of Work a copy of which is attached her ' hereto as Exhibit A and incorporated herein by this reference, together with any amendments that may be agreed to in writing by the parties. 1.2 All documents, drawings and written workr p oduct prepared or produced by the Contractor under this Agreement, including ng and without limitation electronic data files, are thero ert of the p p y Contractor; provided, however, the City shall have the right to reproduce, publish 9 p , p sh and use all such work, or any part thereof, in any manner and for an purposes y p p s whatsoever and to authorize others to do so. If an such work is copyrightable, y py ghtable, the Contractor may copyright the same, except that as to p any work which is copyrighted by the Contractor, the City reserves a royalty -free, non- exclusive, irrevocable rrevocable license to reproduce, publish and use such work, or any part thereof, and to authorize others to do so. 1.3 The Contractor shall provide services and work under this Agreement consistent with the requirements and standards established b applicable y pp ble federal, state and city laws, ordinances, regulations and resolutions. ons. The Contractor represents and warrants that it willerform its work in accordance cordance with generally accepted industry standards and practices for the profession . p p ss�on or professions that are used in performance of this Agreement and that tare in effect at the time of performance of this Agreement. Except for g p o that representation and any representations made or contained in any proposal submitted by the Contractor and any reports oro inions prepared or p p p issued as part of the work performed by the Contractor under this Agreement, g ' Contractor makes no other warranties, ether express or implied, as art of s Agreement. p p . 1.4 Services and work provided by the Contractor at the City's request equest under this Agreement will be performed in a time) manner in accordance ance with a Schedule of Work, which the parties hereto shall agree to. The he Schedule of Work may be revised from time to time upon mutual p written consent of the parties. 2. Consideration 2.1 The Contractor shall be compensated on a LumpSum basis s as provided in Exhibit B "Payment Schedule" attached hereto and b reference mad Y e a part hereof for the Not -To -Exceed amount of $479,441.00. 2.2 The Contractor shall provide the City with a month) statement as the e work warrants, of fees earned and costs incurred for servicesrovided during g the billing period, which the City will pay within 30 days of receipt of a correct p invoice and approval by the City. The City will not withhold any Federal or State income taxes or Social Security Taxfrom an payment made b Ci to Contractor under the terms and condition. Y p Y y City s of . this A Agreement. Payment of all g Y taxes and other assessments on such sums is the sole responsibility of Contractor. p Y 2.3 Except as expressly provided in this Agreement, Contractor shall not be entitled to receive from the City any additional consideration compensation, salary, wages, or other type of remuneration for services rendered under this Agreement including, but not limited to, meals, lodging, g g, transportation, drawings, renderings or mockups. Specifically, Contractor Y shall not be entitled by virtue of this Agreement to consideration in the form of overtime, health insurance benefits, retirement benefits, aid holidays or . p Y other paid leaves of absence of any type or kind whatsoever. 3. Term: 3.1 This agreement shall become effective upon execution by both parties, and shall expire upon (a) completion of the agreed upon work, (b) May 31, 2012 or (c) unless sooner terminated as provided below or unless some other method or time of termination is listed in Exhibit A. 3.2 Should Contractor default in the performance of this Agreement or materially breach any of its provisions, City, at City's option, may terminate this Agreement by giving written notification to Contractor. 3.3 Should City fail to pay Contractor all or any part of the compensation set forth in Exhibit B of this Agreement on the date due, Contractor, at the Contractor's option, may terminate this Agreement if the failure is not remedied by the City within thirty (30) days from the date payment is due. 3.4 TIME FOR EXECUTING CONTRACT AND LIQUIDATED DAMAGES Upon receipt of a Notice to Proceed, the Contractor shall have until May 31, 2012 to complete the work as described herein. Contractor shall be liable to the City for any delay beyond this time period in the amount of five hundred dollars ($500.00) per calendar day. Such payment shall be construed to be liquidated damages by the Contractor in lieu of any claim or damage because of such delay and not be construed as a penalty. 3.4.A EXCEPTIONS: Delays caused by negligence of Owner or acts of God will not be assessed on the Contractor. Termination: If, through any cause, CONTRACTOR, its officers, employees, or agents Y fails to fulfill in a timely and proper manner its obligations under this Agreement, violates any of the covenants, agreements, or stipulations of this Agreement, falsifies any record or document required to be prepared under this agreement, engages in fraud, dishonesty, or any other act of misconduct in the performance of this contract, or if the City Council determines that termination of this Agreement is in the best interest of CITY, the CITY shall thereupon have the right to terminate this Agreement by giving written notice to CONTRACTOR of such termination and specifying the effective date thereof at least fifteen (15) days before the effective date of such termination. CONTRACTOR may terminate this agreement at an time b Y Y giving at least sixty (60) days notice to CITY. In the event of any termination of this Agreement, all finished or unfinished documents, data, and reports prepared by CONTRACTOR under this Agreement shall, at the option of the CITY, become its property, and CONTRACTOR shall be entitled to receive just and equitable compensation for any work satisfactorily complete hereunder. Notwithstanding the above, CONTRACTOR shall not be relieved of liability to the CITY for damages sustained by the CITY by virtue of any breach of this Agreement by CONTRACTOR, and the CITY may withhold any payments to CONTRACTOR for the purposes of set-off until such time as the exact amount of damages due the CITY from CONTRACTOR is determined. This provision shall survive the termination of this agreement and shall not relieve CONTRACTOR of its liability to the CITY for damages. 4. Independent Contractor: 4.1 In all matters pertaining to this agreement, CONTRACTOR shall be acting as an independent contractor, and neither CONTRACTOR nor any officer, employee or agent of CONTRACTOR will be deemed an employee of CITY. Except as expressly provided in Exhibit A, Contractor has no authority or responsibility to exercise any rights or power vested in the City and therefore has no authority to bind or incur any obligation on behalf of the City. The selection and designation of the personnel of the CITY in the performance of this agreement shall be made by the CITY. 4.2 Contractor, its agents, officers, and employees are and at all times during the term of this Agreement shall represent and conduct themselves as independent contractors and not as employees of the City. 4.3 Contractor shall determine the method, details and means of performing the work and services to be provided by Contractor under this Agreement. Contractor shall be responsible to City only for the requirements and results specified in this Agreement and, except as expressly provided in this Agreement, shall not be subjected to City's control with respect to the physical action or activities of Contractor in fulfillment of this Agreement. If in the performance of this Agreement any third persons are employed by Contractor, such persons shall be entirely and exclusively under the direction and supervision and control of the Contractor. 5. Indemnification and Insurance: CONTRACTOR shall indemnify and save and hold harmless CITY from and for any and all losses, claims, actions, judgments for damages, or injury to persons or property and losses and expenses and other costs including litigation costs and attorney's fees, arising out of, resulting from, or in connection with the performance of this Agreement by the CONTRACTOR, its servants, agents, officers, employees, guests, and business invitees, and not caused by or arising out of the tortious conduct of CITY or its employees. CONTRACTOR shall maintain, and specifically agrees that it will maintain, throughout the term of this Agreement, liability insurance, in which the CITY shall be named an additional insured in the minimum amounts as follow: General Liability One Million Dollars ($1,000,000) per incident or occurrence, Automobile Liability Insurance One Million Dollars ($1,000,000) per incident or occurrence and Workers' Compensation Insurance, in the statutory limits as required by law.. The limits of insurance shall not be deemed a limitation of the covenants to indemnify and save and hold harmless CITY; and if CITY becomes liable for an amount in excess of the insurance limits, herein provided, CONTRACTOR covenants and agrees to indemnify and save and hold harmless CITY from and for all such losses, claims, actions, or judgments for damages or injury to persons or property and other costs, including litigation ation costs and attorneys, fees, arising out of, resulting from, or in connection with the performance of this Agreement by the Contractor or Contractor's officers, employs, agents, representatives or subcontractors and resulting in or attributable to personal injury, death, or damage or destruction to or tangible intangible property, including use of. CONTRACTOR shall g g provide CITY with a Certificate of Insurance, or other proof of insurance evidencing CONTRACTOR'S compliance with the requirements of this paragraph and file such proof of insurance with the CITY at least ten (10) gra p p days prior to the date Contractor begins performance of it's obligations under this Agreement. In the event the insurance minimums are changed, g CONTRACTOR shall immediately submit proof of compliance with the changed limits. Evidence of all insurance shall be submitted to the City Purchasing Agent ent with a copy to Meridian City Accounting, 33 East Broadway Avenue, Meridian, Idaho 83642. 5.2 Any deductibles, self-insured retention, or named insureds must be declared in writing and approved by the City. At the option of the City, either: the insurer shall reduce or eliminate such deductibles, self-insured retentions or named insureds; or the Contractor shall provide a bond, cash or letter of credit guaranteeing payment of losses and related investigations, claim administration and defense expenses. 5.3 To the extent of the indemnity in this contract, Contractor's Insurance coverage shall be primary insurance regarding the City's elected officers, officials, employees and volunteers. Any insurance or self- insurance maintained by the City or the City's elected officers, officials, employees and volunteers shall be excess of the Contractor's insurance and shall not contribute with Contractor's insurance except as to the extent of City's negligence. 5.4 The Contractor's insurance shall apply separately to each insured against whom claim is made or suit is brought, except with respect to the limits of the insurer's liability. 5.5 All insurance coverages for subcontractors shall be subject to all of the insurance and indemnity requirements stated herein. 5.6 The limits of insurance described herein shall not limit the liability of the Contractor and Contractor's agents, representatives, employees or subcontractors. 6. Bonds: Payment and Performance Bonds are required on all Public Works Improvement Projects. 7. Warranty: Contractor must warrant parts and labor for one year. Notices: An and all notices required to be given by either of the parties 8 Y . . hereto unless otherwise stated in this agreement, shall be in writing and be deemed communicated when mailed in the United States mail, certified, return receipt requested, addressed as follows: City of Meridian Purchasing Manager 33 E. Broadway Avenue Meridian, Idaho 83642 Clima-Tech Corporation Attn: Jen Johnson 875 W. McGreggor Ct., Ste. 180 Boise, ID 83705 Ph. (208) 377-9755 Jeni(aclima-tech.com Idaho Public Works License #: C-10307 Eitherart change their address for the purpose of this paragraph p Y may bYg g ivin written notice of such change to the other in the manner herein provided. 9. AttorneyFees: Should any litigation be commenced between the parties hereto concerning ithis Agreement, the prevailing party shall be entitled, n addition to an other relief as may be granted, to court costs and reasonable Y attorneys' fees as determined by a Court of competent jurisdiction. This Y . provision shall be deemed to be a separate contract between the partes and shall survive any default, termination or forfeiture of this Agreement. 10. Time is of the Essence: The parties hereto acknowledge and agree that time is strictly of the essence with respect to each and every term, condition andp rovision hereof, and that the failure to timely perform any of the obligations hereunder shall constitute a breach of, and a default under, this Agreement by the party so failing to perform. 11. Assignment: It is expressly agreed and understood by the parties hereto, that CONTRACTOR shall not have the right to assign, transfer, hypothecate or sell any of its rights under this Agreement except upon the prior express written consent of CITY. 12. Discrimination Prohibited: In performing the Work required herein, CONTRACTOR shall not unlawfully discriminate in violation of any federal, state or local law, rule or regulation against any person on the basis of race, color, religion, sex, national origin or ancestry, age or disability. 13. Reports and Information: 13.1 At such times and in such forms as the CITY may require, there shall be furnished to the CITY such statements, records, reports, data and information as the CITY may request pertaining to matters covered by this Agreement. 13.2 Contractor shall maintain all writings, documents and records prepared or compiled in connection with the performance of this Agreement for a minimum of four (4) years from the termination or completion of this or Agreement. This includes any handwriting, typewriting, printing, photo static, photographic and every other means of recording upon any tangible thing, any form of communication or representation including letters, words, pictures, sounds or symbols or any combination thereof. 14. Audits and Inspections: At any time during normal business hours and as often as the CITY may deem necessary, there shall be made available to the CITY for examination all of CONTRACTOR'S records with respect to all matters covered by this Agreement. CONTRACTOR shall permit the CITY to audit, examine, and make excerpts or transcripts from such records, and to make audits of all contracts, invoices, materials, payrolls, records of personnel, conditions of employment and other data relating to all matters covered by this Agreement. 15. Publication, Reproduction and Use of Material: No material produced in whole or in part under this Agreement shall be subject to copyright in the United States or in any other country. The CITY shall have unrestricted authority to publish, disclose and otherwise use, in whole or in part, any reports, data or other materials prepared under this Agreement. 16. Compliance with Laws: In performing the scope of work required hereunder, CONTRACTOR shall comply with all applicable laws, ordinances, and codes of Federal, State, and local governments. 17. Changes: The CITY may, from time to time, request changes in the Scope of Work to be performed hereunder. Such changes, including any increase or decrease in the amount of CONTRACTOR'S compensation, which are mutually agreed upon by and between the CITY and CONTRACTOR, shall be incorporated in written amendments (Change Orders) which shall be executed with the same formalities as this Agreement. 18. Construction and Severability: If any part of this Agreement is held to be invalid or unenforceable, such holding will not affect the validity or enforceability of any other part of this Agreement so long as the remainder of the Agreement is reasonably capable of completion. 19. Waiver of Default: Waiver of default by either party to this Agreement shall not be deemed to be waiver of any subsequent default. Waiver or breach of any provision of this Agreement shall not be deemed to be a waiver of any other or subsequent breach, and shall not be construed to be a modification of the terms of this Agreement unless this Agreement is modified as provided above. 20. Advice of Attorney: Each party warrants and represents that in executing this Agreement, it has received independent legal advice from its attorney's or the opportunity to seek such advice. contains the entire agreement 21. Entire Agreement: This Agreement of the. • I other agreements or understandings, oral parties and supersedes any and al g p of written, whether previous to the execution hereof or contemporaneous herewith. • order or precedence shall be the contract 22. Order of Precedence. The p . agreement, the Invitation for Bid document, then the winning bidders submitted bid document. 23. Applicable Law. This Agreement shall be governed by and construed and .enforced in .accordance with the laws of the State of Idaho, and the ordinances of the City of Meridian. Agreement shall not become effective or binding 24. Approval Required: This Ag. until approved by the City of Meridian. CITY OF MERIDIAN 1 BY: TAM e WEERD, MAYOR Dated: Attest: JAYC L H r�7 r CLIMA-TECH CORPORATION pe0000jo—en J nson Dated: 7//]/// Approved as to Content Sys KEITbI`WATTS, PYJRCSING MANAGER Dated: B-11-1 Approved as to Form CITY ATTORNEY Department Approval NAME: JOHN MCCORMICK TITLE: PW BUSINESS OPERATIONS KAAKinr,PQ Dated: 6-11-11 Exhibit A SCOPE OF WORK DDC SYSTEM SPECIFICATIONS Meridian City Hall Meridian, Idaho May 17, 2011 Tj g e e B "a n k Contents 14 OVERVIEW................................................................................................................................................ . 14 A. Statement of Intent............................................................................................................................ . 14 B. Specification Compliance.................................................................................................................. 14 C. Approved DDC Contractor and System............................................................................................ . 14 D. Warranty............................................................................................................................................ 14 E. Alternate 2 —Extended Warranty....................................................................................................... 14 SCOPEOF WORK...................................................................................................................... ............... 14 A. Control Hardware and Software......................................................................................................... Control 16 B. Control Wiring and Interface to Line Voltage ........................................................................ 16 C. Commissioning ."'.".."'."'.."'...'." D. Training and Technical Support............................................................................. 17 SUBMITTALS AND O&M MANUALS......................................................................................................... .. 17 A. Submittals........................................................................................................................................ 17 B. O&M Manuals.................................................................................................................................... 17 CONTRACTORCAPABILITY.................................................................................................................... PRODUCTCAPABILITY -HARDWARE....................................................................................................18 18 A. System Server................................................................................................................................... 18 B. Field Hardware................................................................................................................................... 18 C. Distributed Control............................................................................................................................. D. Ethernet Gateway Routers................................................................................................................19 19 E. Control Modules................................................................................................................................. 19 F. Temperature Sensors........................................................................................................................ 20 G. Valve and Damper Actuators............................................................................................................ 20 H. Dampers............................................................................................................................................ 20 I. Wire..................................................................................................................................................... PRODUCTCAPABILITY -SOFTWARE.................................................................................................... 20 20 A. BACnet Compatibility......................................................................................................................... 21 B. Multiple Operating Platforms.............................................................................................................. 21 C. Graphical Programming .."".."."".. D. Graphical Interface Software............................................................................................. 23 E. Software Graphic Programming Live User Interface......................................................................... 23 F. Facility Management And Energy Management Functions................................................................ 23 G. Demand Control................................................................................................................................ H. Demand Control -Alternate 1............................................................................................................23 I. Interactive Operations.........................................................................................................................23 J. Enterprise Integration.........................................................................................................................24 K. Alarms, Trends And Reports.............................................................................................................24 25 EXECUTION............................................................................................................................................... 25 A. General.............................................................................................................................................. 25 B. Wiring and Raceways........................................................................................................................ System C. Demolition of Existing Control ...............................................................................................25 D. Relocation of Underfloor VAV Boxes.................................................................................................26 26 SEQUENCESOF OPERATION................................................................................................................. 26 A. General (Common to All Equipment Sequences).............................................................................. B. Zone Sequences................................................................................................................................ 28 31 C. Variable Air Volume Air Handling Units............................................................................................. 36 D. Underfloor Pressurization Control (Air Highway Terminals).............................................................. E. Heating Water System.......................................................................................................................36 F. Chilled Water System........................................................................................................................38 G. Fan Coils FCU 2 — 5..........................................................................................................................40 H. Exhaust Fan Contol...........................................................................................................................40 I. Miscelleanous Monitoring Points.........................................................................................................41 41 J. Alternate 1 -Energy Metering....:........................................................................................................ a r) OVERVIEW A. Statement of Intent The system shall be an extension of the existing Automated Logic control system currently providing rovidin control of the server room systems. Interface for the new controls shall be integratedTM into City of Meridian existing WebCTRL frontend software. Thera hical user interface shall display real time values of all system g p operating conditions. Additionally, it shall include graphic displays of system p g programming, operating logic and logic flow. It shall be capable of displaying that logic flow with real time values of logical inputs and outputs. Graphical displays shall be consistent with those currently available for the server room equipment. The features of the system must be fully installed, configured and demonstrated in a manner that provides maximum benefit to the end user. Remote Access shall completed per the attached Remote Access Procedure on page 60 of this document. B. Specification Compliance These specifications are intended to provide a minimum capability for the DDC system. Manufacturers data sheets included in the submittals will be reviewed to verify significant nificant hardware and software system features. Key system features must be documented by manufacturer's data sheets in the submittals or by demonstration of an existing installation. C. Approved DDC Contractor and System DDC Control System shall be: Automated Logic WebCTRL by Clima-Tech Corporation or approved equal. Contractors wishing to provide pricing for this project shall submit request to Keith Watts City of Meridian Purchasing Manager not later than 14 working days prior to bid opening date. This is to allow for demonstration of their ability to interface p g with existing software. D. Warranty Warrant shall cover all new parts and labor furnished in the scope of this Y specification for a period of one year following completion of Functional Testing. E. Alternate 2 — Extended Warranty Warranty shall cover all new parts and labor furnished in the scope of this specification for a period of five years following completion of Functional Testing. SCOPE OF WORK A. Control Hardware and Software Automatic Temperature Control (ATC) Contractor shall be responsible to furnish Page 14 and install all control hardware and software necessary for complete DDC control system as specified. ATC contractor shall furnish all modules, temperature sensors, flow sensors humiditysensors, IAQ sensors, control valves, control valve actuators, dam damper actuators and any other items necessary fora dampers, p complete system q p sequence and se of operation, except where existing components can be re y newsystem. used b the stem. The ATC contractor is allowed to reuse existing compo, nents however verification of operation shall be included in a Log. Point Checkout Lo . Contractor will prepare a list of non-operational replacement ricin for City review prior to installation of components with p pricing replacement components. The Cit retains the option of obtaining alternate p Y pricing for these replacement components. 1. Specifically the ATC Contractor shall furnish the following: a. Individual unitary control modules for each unitary system: 1) Underfloor Fan CoilNAV Boxes w/Reheat 2) Underfloor VAV Boxes w/out Reheat 3) Overhead Fan Powered VAV Boxes w/Reheat b. Individual control modules for all non unitary air handlers or package units: 1) VAV Air Handling Units 2 Underfloor Pressurization Control Boxes w/Reheat (Control For Air Highways) c. Generalp urpose modules for control of central fan, pump, chiller, boiler or tower operation: 1) Hot Water Central Plant Operations 2) Chilled Water Central Plant Operations 3) General Make Up and Relief Control Dampers 4) Misc Exhaust Fan Controllers 5) Monitoring of Sewage Pumps 6) Monitoring of Emergency Generator Status 7) Monitoring of Run Status for Fresh Water Pumps 8) Monitoring of Glycol Make Up Alarm d. Required peripheral mechanical components to be furnished by ATC contractor: 1) Existing dampers and actuators for underfloor boxes are to be replaced under the scope of this project. Actuators shall be fully modulating. 2) Damper and valve actuators on primary air and water systems shall be assessed during installation and deficiencies shall be reported to the City of Meridian 3) Low pressure air highway extensions shall be added at five designated locations e. Required software integration to other digital control systems: f. Interface to variable frequency drives Page 15 g. Alternate 1 Energy Metering Installation of g digital as meter, electrical current transformers and control g connection wiring shall be priced under a separate proposal. All software programming required for energy metering and Dashboard are to be g g included within the scope of this Alternate. 1) Gas Metering 2) Electric Metering 3) EnergyVu Dashboard B. Control Wiring and Interface to Line Voltage Control ATC Contractor shall be responsible for control wiring to all control modules, sensors relays and actuators required to meet sequences of operation. ATC contractor shall provide mechanical control interface to boilers, chillers, pumps and fans for a complete and operational system. ATC Contractor shall provide all control conduit as required. C. Commissioning ATC Contractor shall be responsible for self -commissioning of all hardware and software furnished with the project. Completed field Point Checkout sheets shall be included with the final "as -built" O&M manuals. These sheets shall include validation check fields for all physical and LAN inputs and outputs. Each system and point shall be listed, using logical names for future reference by the owner. Commissioning shall include calibration and verification of operation of each 1/0 and graphic field. Contractor shallerform Functional Testing of software programming to verify p that the programs meet sequences of operation as submitted and approved. Functional Tests shall be documented for each unique program and for each individual sequence within that program. Functional Test verification sheets shall be included in final "As Built" documentation. D. Training and Technical Support Contractor shall provide access to a three-day training class in a classroom setting p for u to four employees of the City of Meridian. Training shall be oriented to making the owner self-sufficient in the day to day use and operation of the DDC system. Additionally the training shall include information specifically focused on showing the owners representative methods of p Y troubleshooting the mechanical systems using the DDC system. For this purpose, the trainer must be well grounded in both DDC system operation and in mechanical systems service. The contractor shall provide unlimited phone technical support to the owner's representative during the first year of warranty. If the technical support location p of the contractor is outside of the toll free calling area for the customer, the contractor shall have a toll free number or accept collect calls for the purpose of providing technical support. Page 16 ' ' required technical support and training Contractor shall make I n addition to q pp access to facto approved training classes. Classes shall be available acc factory pp .. , d multiple times during the first year to allow flexibility for Owner's schedule p g representative to attend. Tuition to these classes shall be included within the scope oft project. ect. If course locations are more than 200 miles from the '� project site, i cost of transportation, lodging and meals shall be included within p the scope of this project. SUBMITTALS AND O&M MANUALS A. Submittals 1. Submittals shall include the following sections: a. Shop Drawings with: b. Title Page c. Table of Contents d. Typical Device Wiring Drawings e. Summary Bill of Materials f. Sequences of Operation g. Local Area Network Drawings h. Drawings for all operating systems showing both equipment and module connections. i. Bill of Materials for each equipment drawing j. Manufacturers specification data sheets for all control modules, sensors, dampers, valves, actuators, flow switches, current sensors and transducers required in the project. If the contractor wishes to substitute any item after approval of submittal the shall submit appropriate data sheets for approval to the City of Y p Meridian before including substituted product on the project. B. O&M Manuals 1. O&M Manuals shall be furnished upon project completion and include technical instructions for all items originally included in the submittal with "as built" modifications and completed Commissioning Worksheets. 2. O&M Manuals shall be in a separate three ring binder. 3. Contractor's toll free technical support number or the words "Call Collect" with the contractor's regular phone number shall be on the front of the manual. CONTRACTOR CAPABILITY 1. Contractor service and installation technicians shall be technically proficient in both control systems and mechanical service without subcontracting to any other entity. Page 17 2. Contractor shall maintain toll-free technical support phone line or accept collect phone calls during warranty period. 3. Contractor shall provide service within 4 hours. PRODUCT CAPABILITY - HARDWARE A. System Server Software shall be installed on owner furnished server. Specifications for this server will be provided to the owner prior to installation. B. Field Hardware 1. BACnet Compatibility The system shall be fully native BACnet at the time of installation. The system shall use BACnet as the native communication protocol between distributed controllers communicating on the controller network (i.e. Field Bus) and must, as a minimum, support the following Objects and Application Services (Conformance Class 3): a. Objects 1) Binary Input 2) Binary Output 3) Binary Value 4) Analog Input 5) Analog Output 6) Analog Value 7) Calendar 8) Schedules b. Services 1) Readproperty 2) Writeproperty 3) I -Am 4) I -Have 5) ReadMultiple Property 6) WriteMultiple Property 7) Who -Has 8) Who -Is C. Distributed Control System shall observe the concept of distributed control. All modules shall have Page 18 "stand alone" capability and shall maintain operator setpoints without connection to primary controllers or central station equipment. Modules shall be located at each operating equipment location such that individual systems or zones shall remain functional without communication to other systems on the network. Equipment operating logic, schedules and current trends shall reside in control modules serving each system. Use of global modules required to maintain programming, schedules or current trend data are not acceptable. D. Ethernet Gateway/Router System shall include an Ethernet Gateway/Router between the control module network and owner's Ethernet. This gateway shall route BACnet communications between the control module network and the owner's IP network. If the system is not to be connected to customer Ethernet the gateway shall be capable of connection via a web browser on the local host server. E. Control Modules 1. Control modules shall include required inputs and outputs to meet sequence of operation and points list. 2. Digital outputs shall be dry contact relays and analog outputs shall be industry standard 0-5 vdc, 0-10 vdc, 2-10 vdc or 4-20 milli -amp. Triac digital outputs are not acceptable. 3. Modules shall be fully programmable for maximum system flexibility. Application specific controllers are not acceptable. 4. All schedules and current trends shall be maintained in the individual control modules. 5. The modules shall be capable of maintaining sufficient trend samples to report 24 hours of trend history in 5 minute increments for each input or output. 6. All modules shall have battery backup capable of maintaining all programs, setpoints, schedules and trend information for a minimum of 7 days. F. Temperature Sensors 1. Temperature sensors shall be 10 k ohm thermistor. 2. Zone sensors in primary occupied areas other than restrooms, hallways or storage rooms shall have setpoint adjustment to allow the occupants to raise or lower setpoint within operator defined parameters. 3. Additionally sensors in these primary areas shall have a push button to return the system to normal occupancy setpoints for an operator defined period. 4. Exception will be common areas. a. Zone sensors for auditoriums or other places of assembly, restrooms, hallways and storage areas, shall have a similar appearance to other sensors in the building however they will not have setpoint adjustment or override capabilities. 5. Immersion sensors shall be mounted in a blind well for future serviceability. 6. Averaging sensors shall be used in mixed air plenums. Page 19 G. Valve and Damper Actuators 1. Actuators shall be manufactured by Belimo. 2. Actuator torque shall be rated for required load. 3. Modulated actuator input shall be industry standard 0-10 vdc, 2-10 vdc, 4-20 milli -amp, floating motor (tri-state), or pulse width modulation. 4. Two or three position operation is not acceptable for economizers, VAV dampers, underfloor supply air dampers, multizone dampers, valves or any other application specifying modulated operation. H. Dampers 1. Air control zone dampers shall be Ruskin CD45 or equal and have leakage rates of 1 % or less when tested with AMCA Standard 500. I. Wire 1. All wiring not in raceways or control cabinets shall be rated for plenum installation. 2. All wires and cables shall meet the requirements of the National Electrical Code. PRODUCT CAPABILITY - SOFTWARE A. BACnet Compatibility 1. The system shall be fully native BACnet at the time of installation. This means that the system must use BACnet as the native communication protocol between distributed controllers communicating on the controller network (i.e. Field Bus) and must, as a minimum, support the following Objects and Application Services (Conformance Class 3): a. Objects 1) Binary Input 2) Binary Output 3) Binary Value 4) Analog Input 5) Analog Output 6) Analog Value 7) Calendar 8) Schedules b. Services 1) Readproperty 2) Writeproperty 3) I -Am Page 20 4) I -Have 5) ReadMultiple Property 6) WriteMultiple Property 7) Who -Has 8) Who -Is 2. Programming for the system shall use BACnet objects and services. a. All BACnet objects and services shall be opened for read and/or read/write access during programming for future exposure to other BACnet systems. b. The front end software for the system shall be able to query other third party BACnet points for read/write access. B. Multiple Operating Platforms The front end server software furnished as a part of the DDC system shall be capable of operating on multiple operating systems such as Microsoft Windows, Linux or Sun Solaris. C. Graphical Programming 1. The system shall be programmed using a graphical programming language for ease of operator understanding. 2. Operating sequences and logic flow shall be assembled in a schematic format using MicroBlocks representing inputs, outputs and logical functions such as setpoints, switches, limits, relays, PIDs etc. 3. Full simulation capability shall also be provided with the graphic programming. a. User shall be able to fully simulate the constructed sequence on screen before the sequences are downloaded into the controllers. b. The system shall also include the ability to simulate multiple graphic programs communicating with each other on a simulated network. 4. The programming software shall be furnished within this scope of work. D. Graphical Interface Software 1. Graphical Operator Interface a. The operator's interface software shall be graphical based and display in 256 colors at a minimum 1024x768 pixel resolution. b. Graphics display screens shall include a system level graphic of either a map of facilities or an elevation of the building, a graphic of each building floor plan and graphics for each operating system or unit within each building. C. Entry to the zone and equipment level interface graphics shall be through area maps and/or floor plans to facilitate user orientation. Page 21 d. Additionally the system hierarchy shall be displayed in a fashion similar to Windows Explorer to enable the user to navigate to any graphical screen in the system by expanding building levels or floor levels and selecting a particular zone or system. e. Graphics shall be accessed by using a mouse or other pointer device. f. The system shall provide a visual indication of which building, floor and zone the user is accessing at any time. g. System shall be capable of changing all parameters and schedules, as well as downloading operating software from the same Graphical User Interface software program as that used for viewing system operation. h. Software for creating or modifying graphics shall be furnished within this scope of work. 2. Thermal Graphics a. Thermal graphic floor plans shall display each temperature zone in a color appropriate to current space temperature conditions. b. The system shall display zone temperature conditions in 8 separate colors the following conditions: 1) High or low temperature alarm 2) Temperature at setpoint 3) Cooling call 4) Heating call 5) Temperature more than 20 above setpoint 6) Temperature more than 2° below setpoint 7) Unoccupied mode between setpoints 8) No communication. c. Floor plans shall also include color graphic indicators for non -zone specific mechanical equipment operation showing On/Off and Alarm Conditions. d. Status indication colors shall be updated dynamically as conditions change. 3. Mechanical Equipment Graphics a. Mechanical equipment pictorial graphics shall be displayed by the use of point -and -shoot selection using a mouse or other pointer device. b. Graphics shall be provided for all mechanical equipment and devices controlled by the DDC system. c. These graphics shall provide a current status of all 1/0 points being controlled and applicable to each piece of equipment including analog readouts in appropriate engineering units, i.e. damper position in percent or duct pressure in inches water column, at appropriate locations on the graphic representation. Page 22 E. Software Graphic Programming Live User Interface 1. The system shall be able to display the graphic displays of system programming, operating logic and logic- flow with real time conditions displayed at each input, output and logical function. 2. This display will allow the operator to observe each step of a control logic process and facilitate system troubleshooting. 3. Operator shall have the ability to select any MircoBlock in the graphical program to change parameters, including the ability to lock values. F. Facility Management And Energy Management Functions 1. Scheduling a. The DDC system shall have the ability to schedule each individual zone, each building or floor or the entire network of buildings for any user with a single entry. b. Additionally the operator shall have the capability of assembling groups of zones, buildings or floors for single entry programming, e.g. several offices may be grouped for scheduling of Saturday operations. c. Available schedule types shall include normal operation, unoccupied operation, setback override and holidays. d. For maximum flexibility, schedules shall reside in the local control modules. e. Dated schedules shall be self managing and automatically delete after execution. 2. Demand Control a. All operating zones shall include the capability_ of receiving up to 3 Demand Control Levels and initiating progressively greater setpoints offsets to reduce zone equipment demand and equipment demand from Source equipment systems. b. The system will be capable of rotating greater or lower demand levels every 10 minutes to alternate zones throughout the facility to minimize long term setpoint offset. 3. Demand Control - Alternate 1 a. Demand control shall be initiated if Alternate 1, Energy Metering, is accepted. G. Interactive Operations 1. The system shall have the ability to send run requests, heating requests and cooling requests from one module to another for the purpose of optimizing run operations of central plant equipment. 2. The system shall be capable of limiting operation of various equipment based on status of another point elsewhere in the system, e.g. a boiler loop circulating pump shall run only when requested by a zone requiring heating operation and will shut down during hours that zone demand is satisfied. 3. The system shall be capable of changing conditions within a program based on the status of other systems, e.g. VAV supply air setpoints shall be able of being adjusted based on demands of connected zones. Page 23 H. Enterprise Integration 1. The system shall include Enterprise Integration capability and be able to: a. Obtain web services information from other Enterprise servers for the purpose of optimizing system operation, e.g. obtaining NOAA Weather Service for optimizing Night Flush operation b. Provide web services information for the purpose of optimizing other building information systems, e.g. providing maintenance notifications to an Enterprise based facilities maintenance software. 2. The software to enable this interface shall be provided and fully operational within the scope of this project. I. Alarms, Trends And Reports 1. System and Temperature Alarms a. The system shall have the capability of monitoring conditions throughout the system and sending alarms or messages to an e-mail address, to a local PC or printer, to remote PC's and printers, or to dial-up pagers. b. Alarms and messages shall be able to be prioritized for various levels of reporting and action. c. Alarms shall have the ability of being enabled, or disabled to minimize nuisance alarming. d. The operator shall have the ability to customize alarm text and messages. 2. Trends a. The system shall be capable of trending any input or output, or any logical point within the graphic program. b. There shall be no limitation to the number of points that can be trended at any particular time. c. The interval between trend samples shall be adjustable from 1 second to 24 hours. d. Trends from one or more modules shall be able to be simultaneously displayed on a single trend graph. e. Operator shall be able to "window" any segment of a trend to enlarge the view by dragging a mouse to form the "window". f. The system shall also have the ability of automatically downloading trend information from any module to the server or other computer connected to the network for historical trend storage. 1) This historical trend information shall be able to be displayed on the trend graph along with live current trends in seamless fashion. g. Modules shall store in live memory trend samples points for each trended item. 1) Trend data collection reguiriDg the use of a locally connected PC for data storage is unacceptable. Page 24 3. Reports a. The system shall be capable of generating reports of equipment run times, all trended points, temperature conditions, electric demand and usage and alarms or messages. b. Specifically temperature and humidity trends for the Server Room shall be configured for easy retrieval by IT and facilities staff. 1) Alarms for the Server Room shall be coordinated with the City of Meridian Information Technology staff. c. The system shall also have the ability of automatically downloading report information from any module to the server or other computer connected to the network. d. The operator shall have the ability to create custom report and logging formats. EXECUTION A. General All work shall be performed in a workmanlike manner. Occupied areas are to be continually keep clean of debris. Unoccupied areas are to be cleaned following each work shift. B. Wiring and Raceways 1. Installation of wiring and cables shall be in accordance with requirements of the National Electrical Code. 2. All wiring in open areas at heights below 12 feet must be run in conduit. 3. Control wiring above accessible ceilings or floors areas may be run open using plenum. 4. Control wiring in non -accessible ceilings, walls or floors shall be in raceways. 5. All wiring not in raceways or control cabinets shall be rated for plenum installation. 6. Raceways and cables shall be supported as required by the National Electrical Code. 7. All raceways and cable runs shall follow the contours of the building structure. 8. Communication wiring shall be run in data cable tray whenever possible. 9. Wire in data cable trays shall be clearly identified as Temperature Control wire. C. Demolition of Existing Control System 1. The ATC contractor shall remove all unused control hardware and wiring. 2. The ATC contractor shall inform the City of Meridian of any places where removal or relocation of control hardware requires patching or painting of wall surfaces, e.g. relocation of zone sensors. 3. Patching and painting shall be the responsibility of the City of Meridian. Page 25 D. Relocation of Underfloor VAV Boxes The City of Meridian shall be responsible for relocation of underfloor VAV boxes from areas that have been identified as having excess air flow capabilities to areas that have been identified as having too little air flow capability. SEQUENCES OF OPERATION A. General (Common to All Equipment Sequences) 1. All numeric values in the Sequence of Operation shall be adjustable parameters that can be modified without program changes or re -downloading that would interrupt system operation. 2. All Input/Output (1/0) control modules shall have sufficient memory to maintain their own operating programs, schedules and trends without connection to the Local Area Network (LAN). 3. All 1/0 control modules shall be equipped with battery backup and shall retain programming, including time of day, upon loss of power. On return of power control functions shall return to normal operation based on scheduling and time of day with no operator interface. System shall include the capability to set delay on start parameters to start system at random intervals to prevent demand surges on restart. 4. On loss of power to the server only, the Energy Management Control System (EMCS) shall continue to run as normal. 5. The EMCS human interface software shall be a network service and shall automatically restart and connect to the system when power is restored. 6. Trends a. Trending shall be available for all BACnet input/output (1/0) points. b. System shall be capable of adding trending for any digital or analog value as well as any logical value in the graphical program, e.g. PID output trending. c. Trending shall be setup for all significant 1/0 points. 1) Analog values shall be set to log every 5 minutes and store 288 data points for live retrieval. 2) Binary points shall be set to trend on Change of Value (COV) and to store 100 COV trend samples for live retrieval. 3) Sample frequency and quantity of stored data shall be adjustable within the memory limits of each module. d. Trends shall be stored in module memory. e. Extended trending shall be available by archiving trends in server storage. 7. Schedules a. Occupancy schedules shall be initiated from the zone level. 1) Air handling units, chillers, boilers, pumps etc. whose operation is intended to provide air or water flow to zones shall function based on Run Requests, Cooling Requests or Page 26 Heating Requests from the zones they serve. This equipment shall not have separate scheduling capability. b. System shall be capable of setting individual schedules for all zones in a customer database, or for a campus, a single building or floor. c. Additionally system shall be capable of assembling multiple zones for single entry scheduling for specific functions, e.g. a Council Meetings Group could be used for single entry scheduling of all zone equipment required for the City Council Meetings etc., or a group of rooms used by a department that regularly requires scheduling during times when the building would be otherwise scheduled for unoccupied setback. d. The system shall be capable of setting specific equipment to ignore schedules for the rest of the building, e.g. Server Room equipment. e. System shall be capable of setting schedules for weekly reoccurring occupancy, dated weekly, date, date range, wildcard or continuous. f. The system shall be capable of scheduling for multiple years in advance. g. Timed Local Override (TLO) at the local zone sensor, where required, shall override unoccupied schedule, placing equipment in occupied operation for the programmed time period. 8. Unoccupied Operation a. Whenever system operation is required during unoccupied hours of operation, PID control of heating or cooling functions shall be bypassed and systems shall go to 100% operation until setpoint is satisfied. b. Capability shall be in the software to set an On/Off differential greater than occupied differential to reduce the frequency of unoccupied cycling, e.g. heating might be set to cycle on at 550 and remain on until 580 is reached. 9. Optimal Start a. The system shall have optimal start capability so that zone start time will be adjusted based on indoor and outdoor temperatures so as to achieve occupied temperatures at the scheduled occupancy time. b. Optimal start shall be based on zone heat capacitance. The capacitance value shall be adjustable for each zone in the program. c. System shall be capable of a learning adaptive feature allowing the zone control to automatically adjust the capacitance to optimize start times. d. Both optimal start and learning shall be able to be disabled. 10. Load to Source Control a. Central air handling equipment serving multiple zones shall operate based on Run Requests from connected zones. b. Central systems such as boilers, chillers and pumps shall operate based on Heating, Cooling or Run Requests from connected air handlers or zones as required. Page 27 c. Central systems shall have the capability of resetting Heating Water and Chilled Water temperature setpoints, resetting Supply Air temperature or pressure setpoints or Ventilation Air damper position based on the PID output of associated zones. 11. Night Purge (Flush) Operation a. 1/0 control modules programming shall include logic for Night Purge operation designed to pre -cool the facility during warm weather periods. Night Purge programming shall consist of a Global Broadcast to initiate three levels of purge at the zone level. Each zone shall be programmed to receive Night Purge level broadcasts and initiate logic as described below. 1) Each night the EMCS shall query the nearest National Weather Service webserver to obtain temperature forecast for the following day to provide Purge logic for initiation of Night Purge operation. 2) When forecast high is greater than 80°F, Purge Level III shall be broadcast to each zone. If the forecast is between 75°F and 80°F a Level II broadcast shall be sent and when forecast is between 70017and 75°F a Level I broadcast shall be sent. b. Zones shall have the capability to determine action taken for each level of night purge. This is described at the zone level. c. Central systems programmed logic shall include the capability of receiving Night Purge broadcast to initiate the appropriate response, e.g.central mechanical cooling equipment such as Chillers will be disabled during Night Purge operation. d. System shall include capability of deactivating Night Purge through the EMCS by time of year (month and day) or manually through DDC. 12. Alarming a. Programs shall include alarms for conditions as specified. Additionally programs shall include alarms for all 1/0 points. Only those alarms specified are to be initially enabled. b. The system shall have the ability for the operator to enable or disable all alarms without program change or memory download. c. All alarms shall be set with default messages. The system shall have the ability for the operator to create custom messages without program change or memory download. d. All alarms generated shall have the capability of setup for the following actions: 1) Alarm Popup 2) Print 3) Propagate To Server 4) Run External Program 5) Send Alphanumeric Page 6) Send E -Mail 7) Write to File B. Zone Sequences 1. General Zone Sequences (Common to All Zone Sequences) Page 28 a. Run Conditions 1) Zone shall have independent schedule capability. System shall have the ability to write scheduling from a global schedule input, from local schedule or from a group schedule. 2) Outside air temperature shall be available from a global broadcast for local control options. 3) Zone control programs shall include the ability to receive a global broadcast of three escalating demand levels. The program shall be capable of initiating zone setpoint offset in response to each demand level. Each zone shall have the ability of enabling demand response and to be directed to alternate demand broadcast sources. b. Zone Setpoint Control 1) Standard zone sensors, except those noted below, shall include setpoint adjustment and timed local override. Setpoint adjustment shall be by means of an adjustable slide lever and setback override shall be from a button located on the sensor. Program shall have the capability of canceling setback override by holding the momentary contact button down for 3 seconds. Default set point adjustment shall be plus or minus VF and timed override shall be 30 minutes per pulse with a maximum override of 180 minutes. Adjustment values and override times shall be individually programmable for each sensor. i. Zone sensors located in hallways and other common areas shall not include setpoint adjustment or local override options. ii. Sensors in restrooms shall have the appearance of a blank single gang electrical box cover with the thermistor mounted on the back side, inside the junction box. 2) Zones programs shall include the ability to program independent cooling and heating setpoints. Heating and cooling setpoint offsets from a common setpoint is not acceptable. 3) Zone set point control shall use a modified Zone PID algorithm to provide a smooth modulated variable for cooling and heating. 4) Zone control shall alarm on high or low zone temperature. Zone temperature alarms shall be disabled during Optimal Start, during first 30 minutes of scheduled occupancy or during setback override. 5) Supply air temperature (SAT) shall be monitored for all zones where local equipment has heating or cooling capability. Terminal Unit zones without heat and that use primary SAT for cooling or warmup do not require SA sensors. 6) Program shall have the capability of initiating an alarm or message when SAT differential from space or return air temperature exceeds preset values. c. Night Purge Mode 1) Night Purge setpoints shall be set by purge level from Global Night Purge Broadcast. Level 1 Night Purge cooling setpoint shall be 69°F. iv. Level 2 Night Purge cooling setpoint shall be 67°F. V. Level 3 Night Purge cooling setpoint shall be 65°F. Page 29 2) Night Purge heating setpoint shall be offset down by 5°F until scheduled occupancy. On initiation of occupancy, heating setpoint shall be reset up 1 OF every 20 minutes until occupied heating setpoint is reached. This is to prevent reheating a zone that has just night purged. 3) Night purge shall begin 5 hours before scheduled occupancy when: vi. A Night Purge Mode broadcast is received. vii. Zone temperature is 1 ° or more above night purge setpoint. viii. Outside air (OA) temperature is above 450 and more than 5° below zone temperature. 4) Night Purge Mode shall end one hour prior to scheduled occupancy. 2. General VAV Terminal Unit Sequence (Common to All VAV Zones) a. Programming for 1/0 control modules on central Air Handling Units (AHU) and associated Terminal Units (TU) shall include network 1/0 points for communication of AHU and Zone conditions. 1) The following network points shall be broadcast by each TU to the associated AHU for load to source optimization. ix. Occupied Run time X. Unoccupied Run time A. Zone Heating and Cooling PID Percent xii. Zone Damper Position xiii. Night Flush request xiv. CO2 level 2) The following network points shall be broadcast by each AHU to associated TUs for load to source optimization routines. xv. AHU Supply Air Temperature xvi. AHU Supply Static Pressure 3. Underfloor VAV Terminal Units (York Boxes w/Out Fans and HW Coil) a. Cooling Control 1) The supply air damper shall modulate, using Analog or Floating Motor (TriState) control, to maintain cooling setpoint except when the AHU supply air temperature exceeds zone temperature. 4. Underfloor Fan Powered Terminal Units (York Boxes w/Fans and HW Coil) a. Cooling Control 1) The supply air damper shall modulate, using Analog or Floating Motor (TriState) control, to maintain cooling setpoint except when the AHU supply air temperature exceeds zone temperature. b. Heating Control w/Heating Water Page 30 1) When zone heating PID reaches 10% the underfloor inlet dampers shall close completely and the supply fan shall start. 2) Heating water valve shall modulate from 0 to 100% as zone heating PID increases from 10 to 100% to maintain heating set point. 3) Heating shall be locked out when outside air temperature is above 65°F. 5. VAV Fan Powered Terminal Units (Basement VAV Boxes) a. Cooling Control 1) The supply air damper shall modulate, using Analog or Floating Motor (TriState) control, to maintain cooling set point except when the AHU supply air temperature exceeds zone temperature. b. Heating Control w/Heating Water (Not Included in Underfloor VAV Sequence) 1) When zone heating PID reaches 10% the underfloor inlet dampers shall close completely and the supply fan shall start. 2) Heating water valve shall modulate from 0 to 100% as zone heating PID increases from 10 to 100% to maintain heating set point. 3) Heating shall be locked out when outside air temperature is above 65°F. C. Variable Air Volume Air Handling Units 1. Run Conditions a. System shall operate based on requests from zones served by each AHU. b. Outside air temperature from a LAN broadcast is available for control options. c. Optimal start shall be based on optimal start requests from associated zones. Optimal stop shall end AHU operation 5 minutes before the last VAV box goes into setback. 2. Supply Fan Enable a. The supply fan shall be continuously enabled whenever any zone is operating in an occupied mode and shall cycle on zone demand for cooling to maintain unoccupied zone setpoints. b. If supply air flow from the AHU is required for unoccupied heating at the zones, the fan shall cycle on demand for zone heating to maintain unoccupied zone heating setpoints. c. During Night Purge operation fan shall run when requested for Night Purge cooling. d. Fan motor status shall be monitored. If supply fan has been commanded to run by the DDC system and the fan status is not indicated, the DDC system shall send an alarm to the operator workstation. 3. Return Fan Enable a. Return fan shall start whenever supply fan is enabled. If supply fans fails to prove status the return fan shall shut down. Page 31 b. Return fan motor status shall be monitored. If return fan has been commanded to run by the DDC system and the fan status is not indicated, the DDC system shall send an alarm to the operator workstation. 4. Supply Air Temperature Setpoint Reset a. Occupied Mode 1) Reset of SA temperature shall be based on cooling demand from VAV zones. a) The cooling PID value from each box shall be broadcast to this AHU controller. b) The PID value from the boxes with the highest cooling PIDs shall be used for reset. 2) Initial setpoint for supply air temperature shall be 75°F. 3) When any box has a cooling PID more than 10%, SA temperature shall be reset to 65°F. 4) When cooling PID for two or more zones reach 90%, SAT setpoint shall be reset down 1 OF every five minutes. Minimum supply setpoint shall be 55°F. 5) When the highest cooling PID drops to 50%, cooling demand shall be reset up 1 OF every five minutes until maximum PID stops decreasing at which point the setpoint shall remain at the last command until max cooling PID rises again to 90% or falls below 50%. 6) When OA ventilation causes SA to fall below cooling setpoint the heating setpoint shall be cooling setpoint minus 5°. 7) During morning warmup SA heating setpoint shall be 1200 . 8) The cooling PID value from the zones shall only be requested every 3 minutes to minimize narrow range hunting. b. Unoccupied Mode 1) Cooling and heating operation shall be disabled except when two or more zones are requesting operation to meet unoccupied conditioning setpoints. 2) When the AHU operation is required by two or more zones to maintain zone cooling unoccupied setpoint, cooling SA cooling setpoint shall be 550 . 3) When the AHU operation is required by two or more zones to maintain zone night purge, cooling SA setpoint shall be 500 . 4) When the AHU operation is required by two or more zones to maintain zone heating unoccupied setpoint, heating SA setpoint shall be 1200 . c. Morning Warm Up 1) Morning warm up mode shall start when two or more TUs request heating for optimized start. 2) Morning warm up setpoint shall be 1200 . 3) Morning warm up shall be disabled if any TU requests cooling from the AHU. 4) Morning warm up mode shall end when all zones PIDs drop to zero or occupancy time is reached by any zone. Page 32 5. Supply Air Static Pressure Setpoint Reset a. Initial supply air static pressure setpoint shall be 0.5" wc. b. Maximum pressure setpoint, P -max, shall be determined as follows: 1) Set all VAV boxes to maximum occupied cfm. 2) Starting at 0.5" we static pressure, adjust setpoint up until all boxes can maintain maximum occupied cfm. c. When P -max is initially determined the Supply Air flow CFM measured at the SA air flow station shall be noted and used on the system graphic to calculate % air flow during system operation. d. Static pressure setpoint shall be reset between 0.5"wc and P -max using trim and respond logic: 1) If any 2 VAV boxes are 100% open, increase the static pressure setpoint by 0.05" we every 5 minutes until only one VAV box is 100% open or until P -Max is met. 2) If there are no VAV boxes reporting 100% open, decrease the pressure setpoint by 0.05" we every 5 minutes until SA static pressure reaches .5"wc. If any box opens to 100% hold the current pressure until a second box opens to 100% or all boxes again are below 100% open. 6. Supply Air Static Pressure Control a. Supply air pressure shall be monitored in the SA duct at a location approximately 2/3 of the length of the longest run. b. Supply fan VFD (s) shall modulate fan speed to maintain supply static setpoint. c. Minimum fan speed shall be 20% (12 hz). 7. Building Static Control w/Return Fan and Relief Damper Control a. The building static pressure differential to OA pressure shall be monitored The OA reference input opening shall be shielded from the wind. b. Return Fan VFD shall modulate fan speed to maintain .05" we in the return/relief plenum. The location of the pressure sensor inlet shall be between the return fan outlet and the return air dampers. c. The relief dampers shall modulate to maintain building space static of.03" wc. d. If both return air and relief dampers are closed the return fan shall be shutdown 8. Cooling Control a. Economizer and chiller water valve control shall operate in a coordinated fashion from a single cooling PID to maintain supply air temperature setpoint (see setpoint reset above). b. When economizer cooling is available the system shall utilize OA cooling to the maximum extent possible. 9. Cooling Control w/Chilled Water Page 33 a. Mechanical Cooling shall be enabled when the following conditions exist: 1) Outside air temperature is less than 4°F below supply air cooling setpoint 2) Supply fan is commanded on and fan status is proven. 3) Night Flush is not enabled b. The Chilled Water Valve shall modulate based on cooling PID control as follows: 1) When economizer is enabled the Chilled water valve shall modulate from 0% to 100% as cooling PI D rises from 50% to 100%. 2) When economizer is disabled the Chilled water valve shall modulate from 0% to 100% as cooling PI D rises from 0% to 100%. c. A cooing request shall be sent to the chilled water system when cooling valve is greater than 10% open. 10. Economizer Control a. Economizer operation shall be enabled when OA temperature is more than 4° below return air temperature. b. When enabled OA dampers shall modulate from 0% to 100% and RA dampers shall modulate from 100% to 0% open on rise of cooling PI D from 0 to 50%. c. When OA temperature is below 550, a temperature sensor in the mixed air plenum shall limit OA/RA modulation to maintain MA temperature low limit of 550 . d. Economizer shall be disabled when outside air temperature is within 2°F of return air temperature. e. Supply air low limit shall close outside air dampers if SA falls below 42°F. f. OA dampers shall go to a fully closed and RA shall open to 100%.when: 1) Supply Fan Proof is off 2) Freeze stat trips 3) Supply air temperature falls below 420 for more than 5 minutes. 4) Mixed air temperature falls below 36°F for more than 5 minutes. g. Outside air dampers shall be closed and RA damper fully open during unoccupied periods of operation except when the supply fan is enabled to maintain night setback cooling at the zones, including night purge operation. 11. Minimum Outside Air Damper a. When the building is occupied a minimum outside air damper shall modulate to maintain minimum ventilation air, measured by an air flow station in the OA intake. b. The minimum OA damper shall be fully closed whenever the building is in an unoccupied mode, except when enabled to maintain unoccupied cooling setpoint or night flush cooling setpoint. During these unoccupied operations the minimum OA damper will modulate with the other OA dampers for SA setpoint control. Page 34 c. Min OA damper shall close if any other low limit or fan failure occurs as described in the Economizer section above. 12. Heating Control a. A heating water coil is provided to reheat OA ventilation air during low ambient operation, and to provide morning warmup assistance for internal VAV boxes without reheat. b. The Heating water valve shall modulate from 0 to 100% as the heating PID rises from 0 to 100% to maintain discharge air temperature set point. c. If SA safety low limit is reached or the freeze stat trips the HW valve shall open to a preset position sufficient to maintain heating water flow in the HW coil. The degree of opening is to be determined during Functional Testing d. A heating request shall be sent to the heating water system when heating valve is greater than 10% open. 13. Safeties a. Following safety control devices shall be wired into the fan starter coil circuit for shutdown of Supply and Return Fan/Relief Fan when an alarm condition occurs. b. These control devices shall include an auxiliary contact to be wired for building automation input. c. 1/0 controller shall also open binary relays for redundant termination of fan operation and shall send an alarm to the webserver. 1) Freeze Stat — Requires manual reset 2) High static pressure at supply fan discharge — Requires manual reset 3) Smoke and/or Fire Alarm — Reset from Fire System Safety d. The following software safeties shall be available to receive broadcasts from other control modules on the network. 1) Building Fire Alarm broadcast. 2) High duct static pressure at location of duct static pressure control input. e. The following safety control routines shall be included in software programs. 1) Supply air low limit alarm shall initiate if SA temperature remains below 420 for more than 5 minutes. xvii. SA and RA fans shall shutdown xviii. Outside air and relief air dampers shall close completely and return air dampers will full open. xix. HW valve shall open to a preset position sufficient to maintain Heating water flow in the HW coil. The degree of opening is to be determined during Functional Testing. xx. Requires software reset 2) High duct static alarm shall initiate whenever SA static at static control location exceeds 25% of setpoint pressure. Page 35 xxi. SA and RA fans shall shutdown xxii. Requires software reset f. A low duct static message shall be sent to the server whenever SA static at static control location drops below 75% of setpoint pressure. 14. Mail Room Emergency Evacuation Control a. Mail Room Exhaust Fan 1) A switch shall be located on the wall of the mailroom to initiate emergency mail room exhaust fan operation. 2) The switch shall be monitored by a dedicated 1/0 controller. a) When enabled a global point shall be broadcast to the south VAV Air Handling Unit. b) On activation the south VAV AHU shall close OA and Exhaust Air Dampers, open RA dampers and both SA and RA fans will be turned off. D. Underfloor Pressurization Control (Air Highway Terminals) 1. Variable Air Volume Control a. VAV terminals shall control air flow from the primary air plenums (air highways) into the underfloor pressurized plenum to maintain local pressure control. b. Underfloor pressure control terminal units shall be associated with local zone VAV boxes for underfloor pressure reset. c. Initial underfloor pressure setpoint shall be .03" wc. d. If the maximum cooling PID for associated zones falls below 50% the underfloor pressure setpoint shall be reset down by .005" we every 5 minutes until setpoint is reset to .01" wc. e. If any associated zone PID rises above 50% setpoint shall be reset up by .005" we until setpoint rises to .03" wc. 2. Underfloor Temperature Control a. When there are no associated zones calling for cooling and any associated zone heating PID rises to 10% a heating PID will be enabled to temper the underfloor plenum temperature. b. Initial setpoint shall be 620 and shall rise from 620 to 700 as maximum heating PID from associated zones rises from 10% to 90%. c. A heating water valve shall modulate to maintain underfloor heating setpoint. E. Heating Water System 1. Heating Water System Operation a. Heating Water System Enable/Disable Page 36 1) The heating PID from associated zones and/or Air Handling Units shall be monitored and the heating water sequence initiated when any associated equipment heatingPID reaches 10%. 2) Heating water system shall be disabled when OA is above 650 . b. Heating Water Temperature Reset 1) Heating water setpoint temperature shall be automatically reset based on heating requests from equipment that direct) use the heating Y g water from the associated boder (s). When enabled the initial setpoint shall be 100° 2) When the heating PID loop output from any associated zone reaches 90% the heating setpoint will increase 50 every 5 minutes until heating setpoint reaches maximum setpoint temperature of 1500, or until the highest heating PID falls to 50%. 3) When the maximum heating PID from associated equipment falls to 50% the heating water setpoint shall be reset down 50 every 5 minutes until maximum heating PID stops decreasing at which point the setpoint shall remain at the last command until the max heating PID either rises again to 90% or falls below 50%. 4) The heating demand shall be requested no less than every 3 minutes c. Unoccupied Mode 1) Heating water system shall be enabled if any associated heating PID rises above 90%. 2) If heating is requested during unoccupied hours the heating water setpoint shall be 150°. 3) If Heating Water Pumps run for freeze protection with no zone requesting heat, the HWT setpoint shall be 100°F. d. Heating water sequence shall end when all associated equipment PIDs fall to 0% 2. Heating Water Pumps (HWP) a. The lead heating water pump shall start when the Heating Water Sequence is initiated. b. Heating Water Pump Lead/Standby Operation: 1) The two Heating water pumps shall be redundant and shall operate in a lead/standby fashion. 2) On failure of the lead pump, the standby pump shall run and the lead pump shall turn off and alarm shall be sent to the webserver. 3) If on a subsequent call for lead pump operation the lead pump fails again it shall be locked out and a software reset required before it is allowed to operate again. 4) The designated lead pump shall rotate upon one of the following conditions (user selectable): a) Manually through a software switch b) If pump runtime has exceeded an initial value of 300 hrs c) Daily d) Weekly e) Monthly Page 37 3. Heating Water Pump Speed a. Heating water loop pressure differential shall be maintained at 30 psi by varying pump speed using a variable frequency drive. b. Loop pressure control will use PID logic. c. On an initial call for pump operation the pump will start at 50% (30 hz) and modulate to maintain setpoint. d. Pump speed shall not vary up or down more than 1 % every 4 seconds. e. When pumps are commanded to switch Lead Pump while pumps are running, the incoming lead pump shall ramp up while the outgoing pump ramps down to minimize disturbance on the loop. 4. Boiler Control a. The Boiler Management System shall be enabled when the Heating Water Sequence is initiated and status is proven on either HWP. b. An analog output from the ATC system shall reset the BMS setpoint based on setpoint per reset schedule (see above). 5. Night Purge a. Boilers and heating water pumps shall be disabled whenever a Night Purge level 2 or level 3 global broadcast is active. 6. Emergency Shut Down Switches a. Emergency shutdown switches (if provided) located at each exit of the mechanical room shall be wired to each boiler's primary control circuit to shut down the boilers when depressed. b. DDC system shall pick up a status point from the Emergency shutdown switches and provide redundant boiler shut down when depressed. 7. Alarms a. Alarms shall be provided as follows: 1) Boiler alarms as provided though Modbus by the boiler manufacturer: 2) High Heating water supply temperature. 3) Low Heating water supply temperature after system has been running for 30 minutes. 4) Lead Heating Water Pump: a) Failure: Commanded on, but the status is off. b) Running in Hand: Commanded off, but the status is on. c) Runtime Exceeded: Status runtime exceeds a user definable limit. F. Chilled Water System 1. Chilled water system operation Page 38 a. Chilled Water System Enable/Disable 1) The cooling PID from associated zones and/or Air Handling Units shall be monitored and the chilled water sequence initiated when any associated equipment cooling PID reaches 10%. 2) Chilled water system shall be disabled when OA is below 500 . b. Chilled Water Temperature Reset 1) Chiller Water temperature setpoint shall be automatically reset based on cooling requests from equipment that directly use the chilled water from the chilled water system. a) Initial setpoint shall be 650 b) When the cooling PID loop output from any associated zone reaches 90% the chilled water setpoint will decrease 2° every 5 minutes until the chilled water setpoint reaches minimum setpoint temperature of 500, or until the highest cooling PID falls to 50%. c) When the maximum cooling PID from associated equipment falls to 50% the chilled water setpoint shall be reset up 20 ever 5 minutes until maximum cooling PID stops decreasing at which point the setpoint shall remain at the last command until the max cooling PID either rises again to 90% or falls below 50%. 2) The requesting units cooling demand shall be requested not less than every 3 minutes c. During unoccupied mode: 1) Chilled water system shall be enabled when any associated equipment cooling PID exceeds 90%. 2) When enabled in unoccupied mode the chilled water setpoint shall be 50°F. d. Chilled water sequence shall end when all associated equipment PIDs fall to 0% 2. Chilled Water Pumps (CHWP) a. The lead chilled water pump shall start when the Chilled Water Sequence is initiated. b. Chilled Water Pump Lead/Standby Operation: 1) The two chilled water pumps shall be redundant and shall operate in a lead/standby fashion. 2) On failure of the lead pump, the standby pump shall run and the lead pump shall turn off and alarm shall be sent to the webserver. 3) If on a subsequent call for lead pump operation the lead pump fails again it shall be locked out and a software reset required before it is allowed to operate again. 4) The designated lead pump shall rotate upon one of the following conditions (user selectable): a) Manually through a software switch b) If pump runtime has exceeded an initial value of 300 hrs c) Daily Page 39 d) Weekly e) Monthly 3. Chilled Water Pump Speed a. Chilled water loop pressure differential shall be maintained at 30 psi by varying pump speed using a variable frequency drive. b. Loop pressure control will use PID logic. c. On an initial call for pump operation the pump will start at 50% (30 hz) and modulate to maintain setpoint. d. Pump speed shall not vary up or down more than 1 % every 4 seconds. e. When pumps are commanded to switch Lead Pump while pumps are running, the incoming lead pump shall ramp up while the outgoing pump ramps down to minimize disturbance on the loop. 4. Chiller Control a. The Chiller Management System (CMS) shall be enabled when the Chilled Water Sequence is initiated and status is proven on either CHWP. 5. Night Purge 6. Chillers and chilled water pumps shall be disabled during Night Purge operation. 7. Alarms a. Alarms shall be provided as follows: 1) Low chilled water supply temperature. 2) Low chilled water supply temperature after system has been running for 30 minutes. 3) Lead chilled Water Pump a) Failure: Commanded on, but the status is off. b) Running in Hand: Commanded off, but the status is on. c) Runtime Exceeded: Status runtime exceeds a user definable limit. G. Fan Coils FCU 2 — 5 1. Zone Temperature Monitors a. Zone sensors shall monitor temperature on zones served by FCU 2 through 5 and display those temperatures on a graphic screen. H. Exhaust Fan Contol 1. EF -2 - a. A binary output on the mechanical room 1/0 controller shall open the intake damper on EF - 2. Page 40 b. When the damper is 75% open EF 2 shall start. 2. EF -3 a. A binary output on a local zone 1/0 controller shall enable EF -3 during occupied hours. I. Miscelleanous Monitoring Points 1. Sewage Ejection Pumps a. High Level Alarm b. The high sump level alarm on the sewage sumps shall be monitored and an alarm broadcast to the EMCS server when high sump level is sensed. 2. Emergency Generator a. Emergency Generator shall be monitored and a notification sent to the EMCS server whenever the generator is started. b. Start time and run time duration shall be trended and this trend shall be maintained in the server database for future reference. 3. Fresh Water Pumps a. Fresh water pump status shall be monitored and displayed on the system front graphic. 4. Glycol Make Up Tank a. The level of the glycol make up tank shall be monitored and displayed on the system front graphic. J. Alternate 1 - Energy Metering 1. Electrical Metering a. Current transformers shall be installed at the primary electrical entrance to the facility. 2. The EMCS shall meter and display the following: a. Instantaneous electrical demand (kW) b. A rolling average of the previous 15 minute demand level (kW) c. Energy consumption (kWh) for: 1) The previous 24 hours 2) The previous 30 days 3) The previous 12 months 3. Natural Gas Metering a. The EMCS shall meter and display the following: 1) Instantaneous gas usage (cu. ft.) Page 41 2) Energy consumption (cu. ft.) for: a) The previous 24 hours b) The previous 30 days c) The previous 12 months 4. EnergyVu Dashboard a. An EnergyVu Dashboard shall display the energy meter information noted above on a graphical Dashboard with separate screens for electrical and natural gas. b. In addition to current and recent energy information the dashboard shall show comparable year energy information for a base year. Baseline information p y at on shall be at the discretion of the City of Meridian. c. In addition to energy information the dashboard shall also display weather conditions from the nearest NOAA Weather Station. Information to be displayed is: 1) Current temperature 2) Weather forecast for the next 5 days, including the current day. d. The EnergyVu Dashboard screen shall only be accessible using a discreet WebCTRL login. System access from this login shall be limited to display of the dashboard only. Y e. The EnergyVu Dashboard shall have the capabilities of display from the following" 1) Internet/Intranet Login 2) A scrolling display monitor 3) A touchscreen monitor f. Monitors are not required to be furnished within the scope of this project. Page 42 Meridian City Hall Direct Digital Controls sequence of operations General (Common to All Equipment Sequences)...................................................................................... 44 A. Adjustable Parameters............................................................... . CB. Power Loss to Control Modules......................................................................................................... 44 . Power Loss to Server........................................................................................................................ 44 D. Trends................................................................................................................................................ 44 E. Schedules.................................................................... F. Unoccupied Operation....................................................................................................................... 45 G. Optimal Start ............................................................................................................................... 45 H. Load to Source Control ....... ...................................................................................................................... 45 I. Night Purge (Flush) Operation............................................................................................................ 46 J. Alarming............................................................................................................................................. 46 ZoneSequences........................................................................................................................................ 46 A. General Zone Sequences (Common to All Zone Sequences)........................................................... 46 B. General VAV Terminal Unit Sequence (Common to All VAV Zones) ................................................ 48 C. Underfloor VAV Terminal Units (York Boxes w/Out Fans and HW Coil) ........................................... 48 D. Underfloor Fan Powered Terminal Units (York Boxes w/Fans and HW Coil) .................................. 49 E. VAV Fan Powered Terminal Units (Basement VAV Boxes).............................................................. 49 Variable Air Volume Air Handling Units...................................................................................................... 49 A. Run Conditions.................................................................................................................................. 49 B. Supply Fan Enable............................................................................................................................. 49 C. Return Fan Enable............................................................................................................................. 50 D. Supply Air Temperature Setpoint Reset............................................................................................ 50 E. Supply Air Static Pressure Setpoint Reset......................................................................................... 51 F. Supply Air Static Pressure Control..................................................................................................... 51 G. Building Static Control w/Return Fan and Relief Damper Control ..................................................... 51 H. Cooling Control.................................................................................................................................. 52 I. Cooling Control w/Chilled Water......................................................................................................... 52 J. Economizer Control............................................................................................................................ 52 K. Minimum Outside Air Damper............................................................................................................ 53 L. Heating Control.................................................................................................................................. 53 M. Safeties..................................................................................................................................... 53 A. Variable Air Volume Control Underfloor Pressurization Control (Air Highway Terminals)............................................................................... 54 ............................................................................54 ................................... B. Underfloor Temperature Control........................................................................................................ 55 HeatingWater System................................................................................................................................ 55 A. Heating Water System Operation...................................................................................................... 55 B. Heating Water Pumps (HWP)........................................................................................................... 55 C. Heating Water Pump Speed.............................................................................................................. 56 D. Boiler Control..................................................................................................................................... 56 E. Night Purge........................................................................................................................................ 56 F. Emergency Shut Down Switches....................................................................................................... 56 G. Alarms............................................................................................................................................... 57 ChilledWater System................................................................................................................................. 57 A. Chilled Water System ................................................. ... .................................................................... 57 B. Chilled Water Pumps (CHWP).......................................................................................................... 58 C. Chilled Water Pump Speed............................................................................................................... 58 D. Chiller Control.................................................................................................................................... 59 E. Night Purge........................................................................................................................................ 59 F. Alarms................................................................................................................................................ 59 Page 43 General (Common to All Equipment Sequences) A. Adjustable Parameters 1. All numeric values in the Sequence of Operation shall be adjustablearameters that can b ram changes or re -down p e modified without pro 9 g loading that would interrupt system operation. B. Stand Alone Controllers 1. All Input/Output (1/0) control modules shall have sufficient memory to maintain their own operating programs, schedules and trends without connection to the Local Area Network (LAN). C. Power Loss to Control Modules 1. All 1/0 control modules shall be equipped with battery backup and shall retain programming, including time of day, upon loss of power. On return of power control functions shall return to normal operation based on scheduling and time of day with no operator interface. System shall include the capability to set delay on start parameters to start system at random intervals to prevent demand surges on restart. D. Power Loss to Server 1. On loss of power to the server only, the Energy Management Control System (EMCS) shall continue to run as normal. 2. The EMCS human interface software shall be a network service and shall automatically restart and connect to the system when power is restored. E. Trends 1. Trending shall be available for all BACnet input/output (1/0) points. System shall be capable of adding trending for any digital or analog value as well as any logical value in the graphical program, e.g. PID output trending. 2. Trending shall be setup for all significant 1/0 points. Analog values shall be set to log every 5 minutes and store 288 data points for live retrieval. Binary points shall be set to trend on Change of Value (COV) and to store 100 COV trend samples live. Sample frequency and quantity of stored data shall be adjustable within the memory limits of each module. 3. Trends shall be stored in module memory. Extended trending shall be available by archiving trends in server storage. F. Schedules 1. Occupancy schedules shall be initiated from the zone level. Air handling units, chillers, boilers, pumps etc. whose operation is intended to provide air or water flow to zones shall function based on Run Requests, Cooling Requests or Heating Requests from the zones they serve. This equipment shall not have separate scheduling capability. 2. System shall be capable of setting individual schedules for all zones in a customer database, or for a campus, a single building or floor. Additionally system shall be capable of assembling page 44 of 61 multiple zones for single entry scheduling for specific functions. For example a Council Meetings Group could be used for single entry scheduling of all zone equipment required for the City Council Meetings etc. Another example would q p d be a group of rooms used by a department that regularly requires scheduling during times when the building would be otherwise scheduled for unoccupied setback. 3. The system shall be capable of setting specific equipment to ignore schedules for the rest of the building, e.g. Server Room equipment. 4. System shall be capable of setting schedules for weekly reoccurring occupancy, dated week) date, date range, wildcard or continuous. y' 5. The system shall be capable of scheduling for multiple years in advance. 6. Timed Local Override (TLO) at the local zone sensor, where required, shall override unoccupied schedule, placing equipment in occupied operation for the programmed time period. G. Unoccupied Operation 1. Whenever system operation is required during unoccupied hours of operation, PID control of heating or cooling function shall be bypassed and systems shall go to 100% operation until setpoint is satisfied. 2. Capability shall be in the software to set an On/Off differential greater than occupied differential to reduce the frequency of unoccupied cycling, e.g. heating might be set to cycle on at 550 and remain on until 580 is reached. H. Optimal Start 1. The system shall have optimal start capability so that zone start time will be adjusted based on indoor and outdoor temperatures so as to achieve occupied temperatures at the scheduled occupancy time. 2. Optimal start shall be based on zone heat capacitance. The capacitance value shall be adjustable for each zone in the program. 3. System shall be capable of a learning adaptive feature allowing the zone control to automatically adjust the capacitance to optimize start times. 4. Both optimal start and learning shall be able to be disabled. I. Load to Source Control 1. Central air handling equipment serving multiple zones shall operate based on Run Requests from connected zones. 2. Central systems such as boilers, chillers and pumps shall operate based on Heating, Cooling or Run Requests from connected air handlers or zones as required. 3. Central systems shall have the capability of resetting Heating Water and Chilled Water temperature setpoints, resetting Supply Air temperature or pressure setpoints or Ventilation Air damper position based on the PID output of associated zones. page 45 of 61 J. Night Purge (Flush) Operation 1. 1/0 control modules programming shall include logic for Night Purge operation designed to re - cool the facility during warm weather periods. Night Purge g pre- cool g u ge programming shall consist of a Global Broadcast to initiate three levels of purge at the zone level. Each zone shall be programmed to receive Night Purge level broadcasts and initiate logic as described below. 2. Each night the EMCS shall query the nearest National Weather Service webserver to obtain temperature forecast for the following day to provide Purge logic for initiation of Night e operation. When forecast high Pur is greater than 80°F Purge L g g 9 g Level III shall be broadcast to each zone. If the forecast is between 75°F and 80°F a Level II broadcast shall be sent and when forecast is between 70°Fand 75°F a Level I broadcast shall be sent. 3. Zones shall have the capability to determine action taken for each level of night purge. This is described at the zone level. 4. Central systems programmed logic shall include the capability of receiving Night Purge broadcast to initiate the appropriate response, e.g. Central mechanical cooling equipment such as Chillers will be disabled during Night Purge operation. 5. System shall include capability of deactivating Night Purge through the EMCS by time of year (month and day) or manually through DDC. K. Alarming 1. Programs shall include alarms for conditions as specified. Additionally programs shall include alarms for all 1/0 points. Only those alarms specified are to be initially enabled. 2. The system shall have the ability for the operator to enable or disable all alarms without program change or memory download. 3. All alarms shall be set with default messages. The system shall have the ability for the operator to create custom messages without program change or memory download. 4. All alarms generated shall have the capability of setup for the following actions: a. Alarm Popup b. Print c. Propagate To Server d. Run External Program e. Send Alphanumeric Page f. Send E -Mail g. Write to File Zone Sequences A. General Zone Sequences (Common to All Zone Sequences) page 46 of 61 1. Run Conditions a. Zone shall have independent schedule capability. System shall have the abilityto write scheduling from a global schedule input, from local schedule p edule or from a group schedule. b. Outside air temperature shall be available from a global broadcast for local control options. c. Zone control programs shall include the ability to receive a global broadcast of three escalating demand levels. The program shall be capable of initiating zone setpoint offset in response to each demand level. Each zone shall have the ability of enabling demand response and to be directed to alternate demand broadcast sources. 2. Zone Setpoint Control a. Standard zone sensors, except those noted below, shall include setpoint adjustment and timed local override. Setpoint adjustment shall be J p � by means of an adjustable slide lever and setback override shall be from a button located on the sensor. Program shall have the capability of canceling setback override by holding the momentary contact button down for 3 seconds. Default set point adjustment shall be plus or minus 1 OF and timed override shall be 30 minutes per pulse with a maximum override of 180 minutes. Adjustment values and override times shall be individually programmable for each sensor. b. Zone sensors located in hallways and other common areas shall not include setpoint adjustment or local override options. Sensors in r p p estrooms shall have the appearance of a blank single gang electrical box cover with the thermistor mounted on the back side, inside the function box. c. Zones programs shall include the ability to program independent cooling and heating setpoints. Heating and coolingsetpoint offsets from p a common setpoint is not acceptable. d. Zone set point control shall use a modified Zone PID algorithm to provide a smooth modulated variable for cooling and heating. e. Zone control shall alarm on high or low zone temperature. Zone temperature alarms shall be disabled during Optimal Start, during first 30 minutes of scheduled occupancy or during setback override. f. Supply air temperature (SAT) shall be monitored for all zones where local equipment has heating or cooling capability. Terminal Unit zones without heat and that use primary SAT for cooling or warmup do not require SA sensors. g. Program shall have the capability of initiating an alarm or message when SAT differential from space or return air temperature exceeds preset values. 3. Night Purge Mode a. Night Purge setpoints shall be set by purge level from Global Night Purge Broadcast. 1) Level 1 Night Purge cooling setpoint shall be 69°F. 2) Level 2 Night Purge cooling setpoint shall be 67°F. page 47 of 61 3) Level 3 Night Purge cooling setpoint shall be 65°F. b. Night Purge heating setpoint shall be offset down by 5°F until scheduled occupancy. On initiation of occupancy, heatingsetpoint shall be reset y p up 1°F every 20 minutes until occupied heating setpoint is reached. This is to prevent reheating a zone that has just night purged. c. Night purge shall begin 5 hours before scheduled occupancy when: 1) A Night Purge Mode broadcast is received. 2) Zone temperature is 1' or more above night purge setpoint. 3) Outside air (OA) temperature is above 450 and more than 50 below zone temperature. d. Night Purge Mode shall end one hour prior to scheduled occupancy. B. General VAV Terminal Unit Sequence (Common to All VAV Zones) 1. Programming for 1/0 control modules on central Air Handling Units (AHU) and associated Terminal Units (TU) shall include network 1/0 points for communication of AHU and Zone conditions. a. The following network points shall be broadcast by each TU to the associated AHU for load to source optimization. 1) Occupied Run time 2) Unoccupied Run time 3) Zone Heating and Cooling PID Percent 4) Zone Damper Position 5) Night Flush request 6) CO2 level b. The following network points shall be broadcast by each AHU to associated TUs for load to source optimization routines. 1) AHU Supply Air Temperature 2) AHU Supply Static Pressure C. Underfloor VAV Terminal Units (York Boxes w/Out Fans and HW Coil) 1. Cooling Control page 48 of 61 a. The supply air damper shall modulate, using Analog or Floating Motor (TriState) control, to maintain cooling setpoint except when the AHU supply air temperature exceeds zone temperature. D. Underfloor Fan Powered Terminal Units (York Boxes w/Fans and HW Coil) 1. Cooling Control a. The supply air damper shall modulate, using Analog or Floating Motor (TriState) control, to maintain cooling setpoint except when the AHU supply air temperature exceeds zone temperature. 2. Heating Control w/Heating Water a. When zone heating PID reaches 10% the underfloor inlet dampers shall close completely and the supply fan shall start. b. Heating water valve shall modulate from 0 to 100% as zone heating PID increases from 10 to 100% to maintain heating set point. Heating shall be locked out when outside air temperature is above 65°F. E. VAV Fan Powered Terminal Units (Basement VAV Boxes) 1. Cooling Control a. The supply air damper shall modulate, using Analog or Floating Motor (TriState) control, to maintain cooling set point except when the AHU supply air temperature exceeds zone temperature. 2. Heating Control w/Heating Water (Not Included in Underfloor VAV Sequence) a. When zone heating PID reaches 10% the underfloor inlet dampers shall close completely and the supply fan shall start. b. Heating water valve shall modulate from 0 to 100% as zone heating PID increases from 10 to 100% to maintain heating set point. Heating shall be locked out when outside air temperature is above 65°F. Variable Air Volume Air Handling Units A. Run Conditions 1. System shall operate based on requests from zones served by each AHU. 2. Outside air temperature from a LAN broadcast is available for control options. 3. Optimal start shall be based on optimal start requests from associated zones. Optimal stop shall end AHU operation 5 minutes before the last VAV box goes into setback. B. Supply Fan Enable 1. The supply fan shall be continuously enabled whenever any zone is operating in an occupied mode and shall cycle on zone demand for cooling to maintain unoccupied zone setpoints. page 49 of 61 2. If supply air flow from the AHU is required for unoccupied heating at the zones, the fan shall cycle on demand for zone heating to maintain unoccupied zone heating setpoints. 3. During Night Purge operation fan shall run when requested for Night Purge cooling. 4. Fan motor status shall be monitored. If supply fan has been commanded to run by the DDC system and the fan status is not indicated, the DDC system shall send an alarm to the operator workstation. C. Return Fan Enable 1. Return fan shall run whenever supply fan has proven status. 2. Return fan motor status shall be monitored. If return fan has been commanded to run by the DDC system and the fan status is not indicated, the DDC system shall send an alarm to the operator workstation. D. Supply Air Temperature Setpoint Reset 1. Occupied Mode a. Reset of SA temperature shall be based on cooling demand from VAV zones. The cooling PID value from each box shall be broadcast to this AHU controller. The PID value from the boxes with the highest cooling PIDs shall be used for reset. b. Initial setpoint for supply air temperature shall be 75°F. c. When any box has a cooling PID more than 10%, SA temperature shall be reset to 65°F. d. When cooling PID for two or more zones reach 100%, SAT setpoint shall be reset down 1°F every five minutes to a minimum of 55°F. e. When cooling PID for all zones drops to zero, cooling demand shall be reset up 1 OF every five minutes. Five minutes after cooling setpoint reaches 68°F, setpoint will be reset to 75°. f. When OA ventilation causes SA to fall below cooling setpoint the heating setpoint shall be cooling setpoint minus 50 . g. During morning warmup SA heating setpoint shall be 1200 . h. The cooling PID value from the zones shall only be requested every 3 minutes to minimize narrow range hunting. 2. Unoccupied Mode a. Cooling and heating operation shall be disabled except when two or more zones are requesting operation to meet unoccupied conditioning setpoints. b. When the AHU operation is required by two or more zones to maintain zone cooling unoccupied setpoint, cooling SA cooling setpoint shall be 55°. page 50 of 61 c. When the AHU operation is required by two or more zones to maintain zone night purge, cooling SA setpoint 500 . d. When the AHU operation is required by two or more zones to maintain zone heating unoccupied setpoint, heating SA setpoint shall be 1200 . E. Supply Air Static Pressure Setpoint Reset 1. Initial supply air static pressure setpoint shall be 0.5". 2. Maximum pressure setpoint, P -max, shall be determined as follows: a. Set all VAV boxes to maximum occupied cfm. b. Starting at 0.511wc static pressure, adjust setpoint up until all boxes can maintain maximum occupied cfm. 3. Static pressure setpoint shall be reset between 0.5"wc and P -max using trim and respond logic: a. If any 2 VAV boxes are 100% open, increase the static pressure setpoint by 0.05" every 5 minutes until only one VAV box is 100% open or until P -Max is met. b. If there are no VAV boxes reporting 100% open, decrease the pressure setpoint by 0.05" every 5 minutes until SA static pressure reaches .5"wc. If any box opens to 100% hold the current pressure until a second box opens to 100% or all boxes again are below 100% open. F. Supply Air Static Pressure Control 1. Supply air pressure shall be monitored in the SA duct at a location approximately 2/3 of the length of the longest run. 2. Supply fan VFD (s) shall modulate fan speed to maintain supply static setpoint. 3. Minimum fan speed shall be 20% (12 hz). 4. Fan status shall be monitored and shall alarm if fan is enabled by the control module and fan status is not verified. G. Building Static Control w/Return Fan and Relief Damper Control 1. Return Fan VFD shall modulate fan speed to maintain .05" we in the return/relief plenum. The location of the pressure sensor inlet shall be between the return fan outlet and the return air dampers. 2. The relief dampers shall modulate to maintain building space static of.03"wc. The building static pressure sensor shall be referenced to outside air static pressure. The OA reference input opening shall be shielded from the wind. 3. If both return air and relief dampers are closed the return fan shall be shutdown. page 51 of 61 H. Cooling Control 1. Economizer and chiller water valve control shall operate in a coordinated fashion from a single cooling PID to maintain supply air temperature setpoint (see setpoint reset above. 2. When economizer cooling is available the system shall utilize OA cooling to the maximum extent possible. I. Cooling Control w/Chilled Water 1. Mechanical Cooling shall be enabled when the following conditions exist: a. Outside air temperature is more than 2°F above supply air cooling setpoint b. Supply fan is commanded on and fan status is proven. c. Night Flush is not enabled 2. The Chilled Water Valve shall modulated based on PID control as follows: a. When economizer is enabled the Chill water valve shall modulate from 0% to 100% as cooling PID rises from 50% to 100%. b. When economizer is disabled the Chill water valve shall modulate from 0% to 100% as cooling PI D rises from 0% to 100%. 3. A cooing request shall be sent to the chilled water system when cooling valve is greater than 10% open. J. Economizer Control 1. Economizer operation shall be enabled when OA temperature is more than 40 below return air temperature. 2. When enabled economizer control shall modulate OA and RA to maintain SA cooling setpoint. 3. OA dampers shall modulate from 0% to 100% and RA dampers shall modulate from 100% to 0% open on rise of cooling PID from 0 to 50%. 4. When OA temperature is below 500, a temperature sensor in the mixed air plenum shall limit OA/RA modulation to maintain MA temperature low limit of 500 . 5. Economizer shall be disabled when outside air temperature is within 1'F of return air temperature. 6. Supply air low limit shall close outside air dampers if SA falls below 42°F. 7. Supply Fan Proof is off or freeze protection is active. 8. If mixed air temperature falls below 36°F for more than 5 minutes the OA dampers shall go to a fully closed and RA shall open to 100%. page 52 of 61 9. Outside air dampers and RA damper shall open to 100% during unoccupied periods of operation except when the supply fan is enabled to maintain night setback temperatures at the zones, or for night purge operation. K. Minimum Outside Air Damper 1. When the building is occupied a minimum outside air damper shall modulate to maintain minimum ventilation air, measured by an air flow station in the OA intake. 2. The minimum OA damper shall be fully closed whenever the building is in an unoccupied mode, except when enabled to maintain unoccupied cooling setpoint or night flush cooling setpoint. During these unoccupied operations the minimum OA damper will modulate with the other OA dampers for SA setpoint control. 3. If mixed air temperature falls below 50° and the OA dampers are fully closed the min OA damper shall modulate to maintain MA low limit of 50 4. Min OA damper shall close if any other low limit or fan failure occurs as described in the Economizer section above. L. Heating Control 1. A heating water coil is provided to reheat OA ventilation air to SA temperature setpoints when necessary, and to provide morning warmup assistance for internal VAV boxes without reheat. 2. The Heating water valve shall modulate from 0 to 100% as the heating PID rises from 0 to 100% to maintain discharge air temperature set point. 3. If SA safety low limit is reached or the freeze stat trips the HW valve shall open to a preset position sufficient to maintain Heating water flow in the HW coil. The degree of opening is to be determined during Functional Testing 4. A heating request shall be sent to the heating water system when Heating valve is greater than 10% open. M. Safeties 1. Following safety control devices shall be wired into the fan starter coil circuit for shutdown of Supply and Return Fan/Relief Fan when an alarm condition occurs. These control devices shall include an auxiliary contact to be wired for building automation input. DDC controller shall also open binary relays terminating fan operation and shall send an alarm to the webserver. a. Freeze Stat — Requires manual reset b. High static pressure at supply fan discharge — Requires manual reset c. Smoke and/or Fire Alarm — Reset from Fire System Safety 2. The following software safeties shall be available to receive broadcasts from other control modules on the network. a. Fire Alarm page 53 of 61 b. Building Fire Alarm broadcast. c. High duct static pressure at location of duct static pressure control input. 3. The following safety control routines shall be included in software programs. a. Supply air low limit alarm shall initiate if SA temperature remains below 420 for more than 5 minutes. 1) SA and RA fans shall shutdown 2) Outside air and relief air dampers shall close completely and return air dampers will full open. 3) HW valve shall open to a preset position sufficient to maintain Heating water flow in the HW coil. The degree of opening is to be determined during Functional Testing. 4) Requires software reset b. High duct static alarm shall initiate whenever SA static at static control location exceeds 25% of setpoint pressure. 1) SA and RA fans shall shutdown 2) Requires software reset c. Low duct static alarm shall initiate whenever SA static at static control location drop below 75% of setpoint pressure. 1) Alarm point only Underfloor Pressurization Control (Air Highway Terminals) A. Variable Air Volume Control 1. VAV terminals shall control air flow from the primary air plenums into the underfloor pressurized plenum to maintain local pressure control. 2. Underfloor pressure control terminal units shall be associated with local zone VAV boxes for underfloor pressure reset. 3. Initial underfloor pressure setpoint shall be .03" we 4. If the maximum cooling PID for associated zones falls below 50% the underfloor pressure setpoint shall be reset up by .005" we every 5 minutes until setpoint is reset to .01" wc. If any associated zone PID rises above 50% setpoint shall be reset up by .05" we until setpoint rises to .03" wc. page 54 of 61 B. Underfloor Temperature Control 1. When there are no associated zones calling for cooling and any associated zone heating PID rises to 10% a heating PID will be enabled to temper the underfloor plenum temperature. 2. Initial setpoint shall be 620 and shall rise from 620 to 700 as maximum heating PID from associated zones rises from 10% to 90%. Heating Water System A. Heating Water System Operation 1. Heating Water System Enable/Disable a. The heating PID from associated zones and/or Air Handling Units shall be monitored and the heating water sequence initiated when any associated equipment heating PID reaches 10%. b. Heating water system shall be disabled when OA is above 650 . 2. Heating Water Temperature Reset a. Heating water setpoint temperature shall be automatically reset based on heating requests from equipment that directly use the heating water from the associated boiler (s). Initial setpoint shall be 1000 b. When the heating PID loop output from any associated zone reaches 90% the heating water setpoint will increase 50 every 5 minutes until heating setpoint reaches maximum setpoint temperature of 1500, or until the highest heating PID falls to 50%. c. When the maximum heating PID from associated equipment falls to 50% the heating water setpoint shall be reset down 50 ever 5 minutes until maximum heating PID stops decreasing at which point the setpoint shall remain at the last command until the max heating PID either rises again to 90% or falls below 50%. d. The requesting units heating demand shall be requested no less than every 3 minutes 3. Heating water sequence shall end when all associated equipment PIDs fall to 0% 4. Unoccupied Mode a. If Heating Water Pumps run for freeze protection with no zone requesting heat, the HWT setpoint shall be 100°F. B. Heating Water Pumps (HWP) 1. The lead heating water pump shall start when the Heating Water Sequence is initiated. 2. Heating Water Pump Lead/Standby Operation: a. The two Heating water pumps shall be redundant and shall operate in a lead/standby fashion. page 55 of 61 b. On failure of the lead pump, the standby pump shall run and the lead pump shall turn off and alarm shall be sent to the webserver. c. If on a subsequent call for lead pump operation the lead pump fails again it shall be locked out and a software reset required before it is allowed to operate again. d. The designated lead pump shall rotate upon one of the following conditions (user selectable): 1) Manually through a software switch 2) If pump runtime has exceeded an initial value of 300 hrs 3) Daily 4) Weekly 5) Monthly C. Heating Water Pump Speed 1. Heating water loop pressure differential shall be maintained at 30 psi by varying pump speed using a variable frequency drive. 2. Loop pressure control will use PID logic. 3. On an initial call for pump operation the pump will start at 50% (30 hz) and modulate to maintain setpoint. 4. Pump speed shall not vary up or down more than 1 % every 4 seconds. 5. When pumps are commanded to switch Lead Pump while pumps are running, the incoming lead pump shall ramp up while the outgoing pump ramps down to minimize disturbance on the loop. D. Boiler Control 1. The Boiler Management System shall be enabled when the Heating Water Sequence is initiated and status is proven on either HWP. 2. An analog output from the ATC system shall reset the BMS setpoint based on setpoint per reset schedule (see above). E. Night Purge 1. Boilers and heating water pumps shall be disabled following a morning purge level 2 or 3. F. Emergency Shut Down Switches 1. Emergency shutdown switches (if provided) located at each exit of the mechanical room shall be wired to each boiler's primary control circuit to shut down the boilers when depressed. page 56 of 61 2. DDC system shall pick up a status point from the Emergency shutdown switches and provide redundant boiler shut down when depressed. G. Alarms 1. Alarms shall be provided as follows: a. Boiler alarms as provided though Modbus by the boiler manufacturer in addition to: 1) High Heating water supply temperature. 2) Low Heating water supply temperature after system has been running for 30 minutes. b. Heating Water Pump 1 1) Failure: Commanded on, but the status is off. 2) Running in Hand: Commanded off, but the status is on. 3) Runtime Exceeded: Status runtime exceeds a user definable limit. c. Heating Water Pump 2 1) Failure: Commanded on, but the status is off. 2) Running in Hand: Commanded off, but the status is on. 3) Runtime Exceeded: Status runtime exceeds a user definable limit. Chilled Water System A. Chilled Water System 1. Chilled Water System Enable/Disable a. The cooling PID from associated zones and/or Air Handling Units shall be monitored and the chilled water sequence initiated when any associated equipment Chilled PID reaches 10%. b. Chilled water system shall be disabled when OA is below 50°. 2. Chilled Water Temperature Reset a. Chilled water setpoint temperature shall be automatically reset based on cooling requests from equipment that directly use the chilled water from the chilled water system. Initial setpoint shall be 650 b. When the cooling PID loop output from any associated zone reaches 90% the chilled water setpoint will decrease 2° every 5 minutes until the chilled water setpoint reaches minimum setpoint temperature of 50°, or until the highest cooling PID falls to 50%. page 57 of 61 c. When the maximum cooling PID from associated equipment falls to 50% the chilled water setpoint shall be reset up 20 ever 5 minutes until maximum cooling PID stops decreasing at which point the setpoint shall remain at the last command until the max cooling PID either rises again to 90% or falls below 50%. d. The requesting units cooling demand shall be requested no less than every 3 minutes 3. Chilled water sequence shall end when all associated equipment PIDs fall to 0% 4. Unoccupied Mode a. The chilled water pumps shall be enabled when the zone cooling PID for any zone rises to 90%. b. When enabled in unoccupied mode the chilled water setpoint shall be 50°F. B. Chilled Water Pumps (CHWP) 1. The lead chilled water pump shall start when the Chilled Water Sequence is initiated. 2. Chilled Water Pump Lead/Standby Operation: a. The two chilled water pumps shall be redundant and shall operate in a lead/standby fashion. b. On failure of the lead pump, the standby pump shall run and the lead pump shall turn off and alarm shall be sent to the webserver. c. If on a subsequent call for lead pump operation the lead pump fails again it shall be locked out and a software reset required before it is allowed to operate again. d. The designated lead pump shall rotate upon one of the following conditions (user selectable): 1) Manually through a software switch 2) If pump runtime has exceeded an initial value of 300 hrs 3) Daily 4) Weekly 5) Monthly C. Chilled Water Pump Speed 1. Chilled water loop pressure differential shall be maintained at 30 psi by varying pump speed using a variable frequency drive. 2. Loop pressure control will use PID logic. page 58 of 61 3. On an initial call for pump operation the pump will start at 50% (30 hz) and modulate to maintain setpoint. 4. Pump speed shall not vary up or down more than 1 % every 4 seconds. 5. When pumps are commanded to switch Lead Pump while pumps are running, the incoming lead pump shall ramp up while the outgoing pump ramps down to minimize disturbance on the loop. D. Chiller Control 1. The Chiller Management System shall be enabled when the Chilled Water Sequence is initiated and status is proven on either CHWP. 2. An analog output from the ATC system shall reset the BMS setpoint based on setpoint per reset schedule (see above). E. Night Purge 1. Chillers and chilled water pumps shall be disabled during Night Purge operation. F. Alarms 1. Alarms shall be provided as follows: a. Low chilled water supply temperature. b. Low chilled water supply temperature after system has been running for 30 minutes. c. Chilled Water Pump 1 1) Failure: Commanded on, but the status is off. 2) Running in Hand: Commanded off, but the status is on. 3) Runtime Exceeded: Status runtime exceeds a user definable limit. d. Chilled Water Pump 2 1) Failure: Commanded on, but the status is off. 2) Running in Hand: Commanded off, but the status is on. 3) Runtime Exceeded: Status runtime exceeds a user definable limit. page 59 of 61 Clima-Tech Remote Access to WebCTRL Objectives • Remote access using two factor authentication to the WebCTRL web interface using http and the City's SSL VPN. • Accessible from any secure internet connection, including the City's public wireless at City Hall. (Computers infected with malicious software may be blocked) • Clima-Tech will be able to use this remote access method for the initial configuration and for remote support/maintenance over the life of the contract. Out of Scope • Remote access to the WebCTRL server via RDP or any other protocols. • Remote access to the WebCTRL databases. • Remote access to any other City systems or infrastructure maintained by IT. • Access to log into City computers with the user accounts provided. Methods and Tools Used • Two factor authentication with user account/password combination and an RSA SecurelD token (fob). • RSA SecurelD token (software or hardware) will provided by the City. Public Works will cover the cost of the RSA SecurelD token. • The City's SSL VPN will be utilized to provide a secure and encrypted medium for this access. • The City will provide user accounts and passwords to Clima-Tech to access the SSL VPN. Caveats • The CIO or IT director must approve this solution before IT can move forward. They must also approve moving forward with software tokens in place of hardware tokens. o Dave will discuss this with Terry on or before 8/3/11. o If Terry is not available by the end of the day on 8/3/11, Dave will proceed with getting approval through Bill Nary. • Access to the WebCTRL system over the SSL VPN needs to be tested. (IT will collaborate with Eric to do this testing once the remote access method has been configured.) • Configuration and testing will not take place until the proposed solution has been approved. • If software tokens are not available due to the approval process, costs, or other issues, hardware tokens will be utilized. Notes • RSA does not support the two factor authentication on tomcat. This leaves us with the SSL VPN as the only option to provide two factor authentication to the system. There is little to no risk to other City systems/infrastructure using this method. • There is minimal risk to the WebCTRL system using this method. (Password + RSA token would need to be compromised) FYI - Overview of Logon Process • Open web browser and navigate to the City's SSL VPN web site • Enter username and password • Enter RSA token pin • New web browser window opens, directed to the WebCTRL logon screen The SSL VPN window must remain open to use the WebCTRL system page 60 of 61 Exhibit B MILESTONE / PAYMENT SCHEDULE A. Total and complete compensation for this Agreement shall not exceed $479,441.00 to furnish and install an Automated Logic Corporation Automatic Temperature Control System per the attached DDC System Specifications (Exhibit A). Total amount includes Payment and Performance Bonds in the amount of 100% of Contract Total. TASK DESCRIPTION DATE AMOUNT Supply and Installation of Automated Logic Corporation Direct Digital Control System per Exhibit A A. Initialization &Materials Delivered and Stored $215,241.00 B. Software Engineering $6,600.00 C. Installation $248,100.00 D. Download &Commissioning $4,700.00 E. Project Closeout and O&M Manuals $4,800.00 TOTAL $479,441.00 Travel expenses, if any listed above, will be paid at no more than the City of Meridian's Travel and Expense Reimbursement Policy. page 61 of 61