Loading...
HomeMy WebLinkAboutFire Department CommentsMAYOR ROBERr D. CORRffi CouxcE. MEMBERS Wn,LIAM L.M. NARY KEIIHBIItD TAMMY DE WEERD CHERIE MCCANDLES3 RURAL FmE COM[oIISSIONERS RICHARD GREENS TERRY LEIGHTON STEVE ELLIOTT CRY OF' s.-5--~~ C~~eri~r~n ll coral Io CHEF KEN W. BOWERS DEPUTY CHIEF - FIlZE PREVENTION JOSEPH SILVA DEPUTY CHEF -TRAINING BII.L JOHNSON 540 East Franklin Road Meridian, ID 83642 (208)888-1234 Fax (208) 895-0390 MERIDIAN CITY/RURAL FIRE DEPARTMENT RECEIVED February 10, 2003 MAR 19 ?003 City Of Meridian City Clerk Office TO: Mayor, City Council and the Meridian Planning & Zoning Commission FROM: Joseph Silva, Deputy Chief, Fire Prevention SUBJECT: Havasu Subdivision No. 2- FP 03-015 The following will be the requiremerna and/or concerns to provide minimum levels of fire protection for the proposed project: 1. The project which wmprised of one and two family dwellings will require afire-flow of 1,000 gallons per minute available for duration of 2 hours to service the entire project. Fire hydranss shall be placed an average of 400' apart. 1997 UFC Appendix III-A 2. Acceptance of the water supply for fire protection will be by the Meridian Water Department. 3. Final Approval of the fire hydrant locations shall be by the Meridian Fire Department. The proposed fire hydrarn locations will be submitted to the Public Works for plan review. 4. All roads and fire lanes shall have a turning radius of 28' inside and 48' outside. 5. Insure that all yet undeveloped parcels aze maintained free of combustible vegetation per section 1103.2.4 of the Uniform Fire Code. 6. Operational fire hydrants and temporary or permanern street signs are required before combustible constmction begins. UFC 901.4.2 &901.3