Date: October 25, 2002
To: Honorable Mayor, City Council & Meridian Planning & Zoning Commission
From: Joseph Silva, Deputy Fire Chief, Fire Prevention
Subject: Moshers Farm Subdivision PUD & PP 02-021, Revised PP 02-021
The following will be the requirements and/or concerns to provide minimum levels of fire
protection for the proposed project:
1.One and two family dwellings will require a fire-flow of 1,000 gallons per
minute available for duration of 2 hours to service the entire project. Fire
hydrants shall be placed an average of 400’ apart. 1997 UFC Appendix III-A
2. Acceptance of the water supply for fire protection will be by the Meridian
Water Department.
3. Final Approval of the fire hydrant locations shall be by the Meridian Fire.
Department.
4. All roads shall have a turning radius of 28’ inside and 48’ outside.
5. All access roads within the project shall have a clear driving surface with a
minimum width of 20’ available at all times. UFC 902.2.2.1
6.Operational fire hydrants and temporary or permanent street signs are
required before combustible construction begins. UFC 901.4.2 & 901.3
7.It is recommended that no parking be allowed in front of Block 1 Lots # 9,
10, 11, 12, 13, 14, 15, 23, 26, 27.
8.It is requested that the nose of the island (Block 2 Lot 1) be moved 15’ West
to prevent the trailing axles of fire apparatus from clipping the curb.