HomeMy WebLinkAboutCC - Storm Drainage Calcs ESE CONSULTANT S ESE 03 W.Sheryl
Dr Inc.
$103 W.Sheryl Drive
ENGINEERING • PLANNING • SURVEYING • ENVIRONMENTAL Meridian,Idaho 83642
TEL: 208-424-0020
STORMWATER MANAGEMENT REPORT
FOR
DAYSPRING SUBDIVISION NO. 3
Q4��C NAL
9461370
m o
OF 10
J.
21
fa �„ m
mjN
0j. _ Anna Leigh Hirning
Professional Engineer
Idaho License No.9461370
m
_ March 2026
LOCATEDIN:
CITY OF MERIDIAN
ADA COUNTY, IDAHO
TABLE OF CONTENTS
SUBJECT SECTION
Project Overview 1
Stormwater Management Design 2
Stormwater Equations 3
Primary Conveyance & Stormwater Facility Calculations 4
Intensity-Duration-Frequency Curve 5
Pipe Flow Calculations 6
Drainage Basin Map 7
SECTION 1 - Project Overview
Dayspring Subdivision No.3 is a part of a multi-phase mixed use development located in the City
of Meridian,Ada County, Idaho. The development is situated along the south side of West Ustick
Road, between North Black Cat Road and North McDermott Road. The applicant proposes to
develop fifty-seven (57) single family residential lots with this phase of the project. The
development includes the construction of homes and infrastructure to include roads, sidewalks,
a stormwater management facility, utilities, and other improvements typical of residential
construction.
Existing Conditions
The project site is currently bound by a single-family residential development to the east(Tricia's
Crossing Subdivision) and vacant agricultural land to the west and south. The project site itself
is comprised of existing irrigated farmland with several abandoned houses and ancillary
buildings, and irrigation delivery ditches.
The existing terrain is relatively flat with slopes generally less than one percent. The site slopes
down gradient from north to south.
Geotechnical Characteristics
A Geotechnical Engineering Report was prepared by ALLWEST for the Dayspring Subdivision
(f.k.a. Porter Complex Development), dated September 2, 2020. The soils were generally
described as surficial lean clay with sand or sandy lean clays with thickness of 1 to 3 feet,
overlaying varying layers and mixtures of native silty and sandy soils. Underlying the silty and
sandy soils, were generally observed poorly graded gravels with silt and sand to test pit depths
of up to 13' bgs.
Groundwater
Groundwater was observed by ALLWEST during testing in June of 2020 at depths ranging from
7.5' -13.5' bgs. Additional groundwater monitoring performed by Geotek commenced in August
2024 and is ongoing. There are currently 30 active piezometers onsite, and groundwater is
observed at depths ranging from 3.2'-12.3' bgs. Geotek's results are summarized in the attached
report dated January 2026.
Soil Infiltration
ALLWEST performed soil infiltration tests at 8 (eight) locations within the project site which
resulted in rates ranging from a low of 0.25 in/hr to a high of greater than 20 in/hr. An infiltration
rate of 1 in/hr was utilized for design purposes.
SECTION 2 - Stormwater Management Design
Design Criteria
The Stormwater Management Plan described herein has been designed according to the Ada
County Highway District Policy Manual. The proposed Stormwater Management Design has
been prepared to meet the following requirements and guidelines:
♦ The Rational Method (Q=CiA) has been utilized to calculate peak flows. Runoff
coefficients were used per the ACHD Policy Manual. Rainfall intensities were determined
using the ACHD adopted Intensity-Duration-Frequency Curve located in Section 5 of this
report. Calculations for the requisite time of concentration (Tc) value are enclosed. The
overland flow and gutter flow segments of the Tc were calculated based on the equations
provided in the ACHD Policy Manual and enclosed within this report for reference.
♦ Pipe flow calculations are provided to demonstrate that the primary stormwater
conveyance system is sized to adequately handle stormwater flows based on the 100-yr
storm event.
♦ The residential lot grading was designed to drain approximately the front half of the lot
towards the street and is included in the stormwater basin calculations. Stormwater that
falls within the back of the lots will be retained on site. Yard drains will be installed in the
rear yards during home construction and final landscaping to facilitate infiltration of lot
drainage.
♦ High groundwater observed through the site necessitated the use of Vertical Sand Filters
for the storage and infiltration of the 100-year storm event. An infiltration rate of 1 inch
per hour has been used for the design of the vertical sand filters. Sand and grease traps
are provided for pretreatment for the vertical sand filters which have been designed so
the bottom of facility elevation is higher than the anticipated seasonal groundwater.
♦ Within Phase 3,there are five (5) proposed vertical sand filters. Basin 3.1 is located within
a future common lot on the west side of N Dayspring Way Basin 3.2 is located within
Common Lot 9C, Block 14 on the west side of N Barnstead Way, Basin 3.3 is located within
Common Lot 5C, Block 13 on the north side of W Ridgeside St, Basin 3.4 is located within
Lot 17C, Bock 11 on the south side of W Ridgeside St, and Basin 3.5 is located within 6C,
Blockon the west side of N Bebee River Way.
♦ Stormwater generated within the front halves of Lots 3 & 4, Block 13, 4,5,21 & 22, Block
12, and Lot 3, Block 11 and adjacent roadways have been accounted for in the Dayspring
Subdivision No. 2 stormwater facilities.
♦ Phase 3 includes two(2)temporary stormwater retention ponds that have been sized for
the 100-year event and designed to provide a minimum of 3' between the bottom of
facility elevation and the anticipated seasonal groundwater. Basins 3.6 & 3.7 are located
at the west end of W Belle Meade Dr. within proposed temporary storm drain easements
and will be removed and replaced with the development of future phases.
SECTION 3 - Stormwater Equations
Stormwater Conveyance ACHD Policy Manual 8011.2)
Q = iA where=
Q - Discharge rate (ofs)
_ Coefficient of Runoff(dimensionless)
i = Rainfall intensity (in/hr) for a duration equal
to the time of concentration (Tc) over the
contribuking area and for the design
frequency.
A = Site area (acres)
Tc = Time of concentration
Coefficient of Runoff(ACHD Policy Manual 8011.2.1)
Estimated Runoff Coefficients for Various Surfaces
Type of Surface Runoff Coefficients "C"
Business
Downtown areas 0.70-0.95
Urbannelghtwhoods 0.50-0.70
Residential
Single Family 0.35.0.50
Multifamily 0.60.0.75
Residential1Fural) 0.25.0.40
ApartmentDwellingAreas 0.70
Industrial and Commerclal
Light areas 0.80
Heavy areas 0.90
Parks,{emeterles 0.10-0.25
Playgrounds 0.20-0.35
Railroad yard areas 0.20.0.40
UnlmpFaved areas 0.10.0.30
StFBBtS
Asphalt 0.95
Gan{Fete 0.95
Brick 0.95
Roofs 0.95
Grant 0.75
Fields:Sandy sail Soll Type
Slope A B {
Flat 0.2% 0.04 0.07 0.11 0.1S
Average,2.6% 0.09 0.12 0.15 4.20
Steep' % 0.13 0.18 0.2n :'.?a
Adapted from ASCE
Design Storm Runoff Volume (ACHD Policy Manual 8011.3.2)
V=CiA(3600)
V: Design storm runoff volume required for storage
C: Coefficient of Runoff
is Rainfall Intensity per IDF Curve
1-hour 100-year storm event, i=0.96
1-hour 2-year storm event, i=0.26
A: Total catchment area(acres)
Time of Concentration
Tc=Tc-G+Tc-s
Tc : Total time of concentration
LG
Tc-c — 60 • VG
Tc-G : Gutter time of concentration
LG : Length of gutter flow
VG : Gutter flow velocity
VG=K„k Sr0.5
Ku : Empirical coefficient(3.281)
k : Intercept coefficient(0.619)
Sr : Slope (percent)
0.007(nL)0-8
Tc—S — (p2)0.5So.4
Tc-s : Overland time of concentration
L : Length of overland(sheet) flow
n : Manning's Roughness Coefficient(0.24)
P2 : 2-year 24-hour rainfall (1.2 in.)
S : Slope (ft/ft)
Manning's Roughness Coefficient(ACHD Policy Manual 8011.5.3)
Typical Range of Manning's Coefficient (n) for Channels and Pipet,
CandUii Matoridl Mann ing's n'
Closed Conduits
Concrete pipe 0.010- 0.015
CMP 0.017 -0.037
Plastic pips(SM001h) 0.009-0.015
Plastic ppe(corrugated) D_018-0.025
PavemenUgutter sections OmM-0.016
ma to Open Chenriel5
Concrete 0.01 i -0.015
Rubble or riprap 0_d20-d_D35
V aget a ban d.020=0.150
Base Soil 0.01fi-0.025
Rack Cut 0.025-0.045
Natural channels(minor streams, lop avudth at none saga <30 m(100 h))
Fairiy regular s,wjo a 0.025- 0.050
Irregular 9Ocban with N!S 0.040-0.150
'Lower values are usually For well-constructed and maintained 1;&mDotherj pipes
and channels
Table 3-2. Manning's Roughness Coefficient(n)for Overland Sheet Flow,`'
Surface Description n
Smooth asphalt 0.011
Smooth concrete 0.012
Ordinary concrete lining 0.013
Good wood 0.014
Brick with cement mortar 0.014
Vitrified clay 01015
Cast iron 0.015
Corrugated metal pipe 0,024
Cement rubble surface M24
Fallow (no residue) 0.05
Cultivated soils
Residue cover s 20% 0_06
Residue cover> 20°fo 0.17
Range(natural) 0_13
Grass
Short grass prairie 0.15
Dens@ grasses 0.24
Bermuda grass 0.41
Woods'
Light underbrush 0.40
Dense underbrush 4_$4
-When selecting n, consider cover to a height of about K mm. This is only part of
the plant cover that will obstruct sheet Flow,
SECTION 4
Primary Conveyance & Stormwater Facility Calculations
BASIN CATCHMENT AREA 3.1
BASIN CHARACTERISTICS
Basin Area: 0.73 Acres
Runoff Coefficient, C: 0.65
Rainfall Intensity, is 0.96 in/hr
Infiltration Rate, r: 1.0 in/hr
TIME OF CONCENTRATION
Overland Flow Gutter Flow
Sub-Catchment Length, L Slope, s TC-5 Elev 1 Elev 2 Length, LG Slope, Sp Gutter Velocity,VG Tc-G Total Tc
(ft) M (min.) (ft) (ft) (ft) M (ft/sec) (min.) (min.)
3.1A 40.0 1.00 14.8 2544.0 2542.8 265 0.44 1.34 3.3 18.1
3.113 40.0 1.00 14.8 2544.0 2542.8 271 0.44 1.35 3.3 18.1
CONVEYANCE
Sub-Catchment C Area, A i2 i25 i100 Q2 Q25 Q100
(acres) (in/hr) (in/hr) (in/hr) (cfs) (cfs) (cfs)
3.1A 0.65 0.30 0.53 1.40 1.95 0.10 0.27 0.38
3.113 0.65 0.43 0.53 1.40 1.95 0.15 0.39 0.55
Total 0.73 0.25 0.66 0.93
SAND & GREASE TRAP
No. of S&G Baffle Throat
Vault Size Traps Spacing Width Throat Area Flow Rate, Q100 Throat Velocity, V Flow Rate Check Velocity Check
(galon) (inch) (inch) (ft) (cfs) (fps) Q100< 3.33 cfs V<0.5 fps
1000 1 20 48 6.67 0.93 0.14 TRUE TRUE
STORAGE VOLUMES (Vertical Sand Filter)
Chamber 1
Req'd Volume, V2-YR L1 W1 d1 Pipe Volume, VP1 Volume, VR1 Storage Volume,V1
(ft) (ft) (ft) (ft) (ft) (ft) (ft)
444 90 3.5 4.5 157 504 661
Chamber 2
Rock Void Design Infiltration Bed Infiltration Time to Drain
Req'd Volume, V100-YR L2 W2 dz Pipe Volume, VPZ Volume, VRz Rate, I Volume,VZi Storage Volume,VZ 90%
(ft) (ft) (ft) (ft) (ft) (ft) (in/hr) (ft) (ft) (hrs)
1,640 90 10 4.5 70 1,592 1.0 75 1,737 19.68
BASIN CATCHMENT AREA 3.2
BASIN CHARACTERISTICS
Basin Area: 2.08 Acres
Runoff Coefficient, C: 0.50
Rainfall Intensity, is 0.96 in/hr
Infiltration Rate, r: 1.0 in/hr
TIME OF CONCENTRATION
Overland Flow Gutter Flow
Sub-Catchment Length, L Slope, s TC-5 Elev 1 Elev 2 Length, LG Slope, Sp Gutter Velocity,VG Tc-G Total Tc
(ft) M (min.) (ft) (ft) (ft) M (ft/sec) (min.) (min.)
3.2A 40.0 1.50 12.6 2544.0 2541.0 517 0.59 1.55 5.5 18.1
3.2B 15.0 2.00 5.1 2542.9 2541.0 394 0.49 1.43 4.6 9.7
CONVEYANCE
Sub-Catchment C Area, A i2 i25 i100 Q2 Q25 Q100
(acres) (in/hr) (in/hr) (in/hr) (cfs) (cfs) (cfs)
3.2A 0.50 1.12 0.53 1.40 1.95 0.30 0.78 1.09
3.2B 0.50 0.96 0.69 1.85 2.58 0.33 0.89 1.24
Total 2.08 0.63 1.67 2.33
SAND & GREASE TRAP
No. of S&G Baffle Throat
Vault Size Traps Spacing Width Throat Area Flow Rate, Q100 Throat Velocity, V Flow Rate Check Velocity Check
(galon) (inch) (inch) (ft) (cfs) (fps) Q100< 3.33 cfs V<0.5 fps
1000 1 20 48 6.67 2.33 0.35 TRUE TRUE
STORAGE VOLUMES (Vertical Sand Filter)
Chamber 1
Req'd Volume, V2-YR L1 W1 d1 Pipe Volume, VP1 Volume, VR1 Storage Volume,V1
(ft) (ft) (ft) (ft) (ft) (ft) (ft)
973 100 5.5 4 175 810 985
Chamber 2
Rock Void Design Infiltration Bed Infiltration Time to Drain
Req'd Volume, V100-YR L2 W2 dz Pipe Volume, VPZ Volume, VRz Rate, I Volume,VZi Storage Volume,VZ 90%
(ft) (ft) (ft) (ft) (ft) (ft) (in/hr) (ft) (ft) (hrs)
3,594 100 22 4 78 3,489 1.0 183 3,750 17.64
BASIN CATCHMENT AREA 3.3
BASIN CHARACTERISTICS
Basin Area: 2.41 Acres
Runoff Coefficient, C: 0.50
Rainfall Intensity, is 0.96 in/hr
Infiltration Rate, r: 1.0 in/hr
TIME OF CONCENTRATION
Overland Flow Gutter Flow
Sub-Catchment Length, L Slope, s TC_5 Elev 1 Elev 2 Length, LG Slope, Sp Gutter Velocity,VG Tc_G Total Tc
(ft) M (min.) (ft) (ft) (ft) M (ft/sec) (min.) (min.)
3.3 70.0 1.00 23.1 2545.1 2541.6 659 0.54 1.50 7.3 30.5
CONVEYANCE
Sub-Catchment C Area,A i2 i25 i100 Q2 Q25 Q100
(acres) (in/hr) (in/hr) (in/hr) (cfs) (cfs) (cfs)
3.3 0.50 2.41 0.4 1.06 1.48 0.48 1.28 1.78
Tota 1 2.41 0.48 1.28 1.78
SAND & GREASE TRAP
No. of S&G Baffle Throat
Vault Size Traps Spacing Width Throat Area Flow Rate, Q100 Throat Velocity, V Flow Rate Check Velocity Check
(galon) (inch) (inch) (ft) (cfs) (fps) Q100< 3.33 cfs V<0.5 fps
1000 1 20 48 6.67 1.78 0.27 TRUE TRUE
STORAGE VOLUMES (Vertical Sand Filter)
Chamber 1
Req'd Volume, V2-YR L1 W1 d1 Pipe Volume, VP1 Volume, VR1 Storage Volume,V1
(ft') (ft) (ft) (ft) (ft') (ft') (ft)
1,128 170 3.5 4 298 833 1,131
Chamber 2
Rock Void Design Infiltration Bed Infiltration Time to Drain
Req'd Volume, V100-YR L2 W2 d2 Pipe Volume, VP2 Volume, VR2 Rate, I Volume,V21 Storage Volume,V2 90%
(ft) (ft) (ft) (ft) (ft) (ft) (in/hr) (ft) (ft) (hrs)
4,164 170 15 4 133 4,027 1.0 213 4,372 17.64
BASIN CATCHMENT AREA 3.4
BASIN CHARACTERISTICS
Basin Area: 2.66 Acres
Runoff Coefficient, C: 0.50
Rainfall Intensity, is 0.96 in/hr
Infiltration Rate, r: 1.0 in/hr
TIME OF CONCENTRATION
Overland Flow Gutter Flow
Sub-Catchment Length, L Slope, s TC_5 Elev 1 Elev 2 Length, LG Slope, Sp Gutter Velocity,VG Tc_G Total Tc
(ft) M (min.) (ft) (ft) (ft) M (ft/sec) (min.) (min.)
3.4 70.0 1.00 23.1 2544.3 2541.6 511 0.53 1.48 5.7 28.9
CONVEYANCE
Sub-Catchment C Area,A i2 i25 i100 Q2 025 Q100
(acres) (in/hr) (in/hr) (in/hr) (cfs) (cfs) (cfs)
3.4 0.50 2.66 0.41 1.09 1.53 0.55 1.45 2.03
Tota 1 2.66 0.55 1.45 2.03
SAND & GREASE TRAP
No. of S&G Baffle Throat
Vault Size Traps Spacing Width Throat Area Flow Rate, Q100 Throat Velocity, V Flow Rate Check Velocity Check
(galon) (inch) (inch) (ft) (cfs) (fps) Q100< 3.33 cfs V<0.5 fps
1000 1 20 48 6.67 2.03 0.31 TRUE TRUE
STORAGE VOLUMES (Vertical Sand Filter)
Chamber 1
Req'd Volume, V2-YR L1 W1 d1 Pipe Volume, VP1 Volume, VR1 Storage Volume,V1
(ft') (ft) (ft) (ft) (ft') (ft') (ft)
1,245 100 7 4.5 175 1,190 1,365
Chamber 2
Rock Void Design Infiltration Bed Infiltration Time to Drain
Req'd Volume, V100-YR L2 W2 d2 Pipe Volume, VP2 Volume, VR2 Rate, I Volume,V21 Storage Volume,V2 90%
(ft) (ft) (ft) (ft) (ft) (ft') (in/hr) (ft) (ft) (hrs)
4,596 100 25.5 4.5 78 4,559 1.0 213 4,849 19.47
BASIN CATCHMENT AREA 3.5
BASIN CHARACTERISTICS
Basin Area: 1.90 Acres
Runoff Coefficient, C: 0.50
Rainfall Intensity, is 0.96 in/hr
Infiltration Rate, r: 1.0 in/hr
TIME OF CONCENTRATION
Overland Flow Gutter Flow
Sub-Catchment Length, L Slope, s TC-5 Elev 1 Elev 2 Length, LG Slope, Sp Gutter Velocity,VG Tc-G Total Tc
(ft) M (min.) (ft) (ft) (ft) M (ft/sec) (min.) (min.)
3.5A 70.0 1.00 23.1 2544.3 2542.1 438 0.50 1.44 5.1 28.2
3.5B 70.0 1.00 23.1 2544.3 2542.1 438 0.50 1.44 5.1 28.2
CONVEYANCE
Sub-Catchment C Area, A i2 i25 i100 Q2 Q25 Q100
(acres) (in/hr) (in/hr) (in/hr) (cfs) (cfs) (cfs)
3.5A 0.50 0.87 0.42 1.10 1.54 0.18 0.48 0.67
3.5B 0.50 1.03 0.42 1.10 1.54 0.22 0.57 0.79
Tota 1 1.90 0.40 1.05 1.46
SAND & GREASE TRAP
No. of S&G Baffle Throat
Vault Size Traps Spacing Width Throat Area Flow Rate, Q100 Throat Velocity, V Flow Rate Check Velocity Check
(galon) (inch) (inch) (ft) (cfs) (fps) Q100< 3.33 cfs V<0.5 fps
1000 1 20 48 6.67 1.46 0.22 TRUE TRUE
STORAGE VOLUMES (Vertical Sand Filter)
Chamber 1
Req'd Volume, V2-YR L1 W1 d1 Pipe Volume, VP1 Volume, VR1 Storage Volume,V1
(ft) (ft) (ft) (ft) (ft) (ft) (ft)
889 207 2 5.75 364 807 1,171
Chamber 2
Rock Void Design Infiltration Bed Infiltration Time to Drain
Req'd Volume, V100-YR L2 W2 dz Pipe Volume, VPZ Volume, VRz Rate, I Volume,VZi Storage Volume,VZ 90%
(ft) (ft) (ft) (ft) (ft) (ft) (in/hr) (ft) (ft) (hrs)
3,283 207 6.5 5.75 162 3,030 1.0 112 3,304 26.35
TEMPORARY BASIN CATCHMENT AREA 3.6
BASIN CHARACTERISTICS
Basin Area: 0.28 Acres
Runoff Coefficient, C: 0.55
Rainfall Intensity, is 0.96 in/hr
STORAGE VOLUMES
Temporary Basin
Req'd Volume Botom Top Area Basin
V100YR Depth Area Volume
(ft3) (ft) (ftz) (ftz) (ft)
532 - 0 617.00 1046.0 831.5
TEMPORARY BASIN CATCHMENT AREA 3.7
BASIN CHARACTERISTICS
Basin Area: 0.07 Acres
Runoff Coefficient, C: 0.55
Rainfall Intensity, is 0.96 in/hr
STORAGE VOLUMES
Temporary Basin
Req'd Volume Botom Basin
V100YR Depth Area Top Area Volume
(ft) (ft) (ft2) (ft) (ft)
135 _._ 221.00 347.0 142.0
SECTION 5
Intensity-Duration-Frequency Curve
ACHD Intensity-Duration-Frequency
Intensity(inches per hour)
Design Storm 2 5 10 25 50 100
Tc(hr) Tc(min)
0.17 10 0.69 1.15 1.48 1.85 2.20 2.58
0.25 15 0.59 0.97 1.22 1.56 1.86 2.18
0.33 20 0.49 0.81 1.01 1.30 1.54 1.81
0.42 25 0.43 0.71 0.89 1.14 1.35 1.58
0.50 1 30 0.41 0.67 0.85 1.08 1 1.29 1.51
0.58 35 0.34 0.56 0.70 0.90 1.07 1.25
0.67 40 0.31 0.51 0.64 0.82 0.98 1.15
0.75 45 0.29 0.48 0.60 0.77 0.91 1.07
0.83 50 0.27 0.45 0.56 0.72 0.85 1.00
0.92 55 0.26 0.43 0.54 0.69 0.82 0.96
1 60 0.26 0.43 0.54 0.69 0.82 0.96
2 120 0.16 0.25 0.31 0.39 0.46 0.54
3 180 0.13 0.19 0.23 0.29 0.34 0.40
6 360 0.09 0.12 0.14 0.18 0.21 0.25
12 720 0.06 0.08 10.10 0.12 0.14 0.16
24 1440 0.04 0.06 1 0.06 0.08 0.09 0.10
Intensity Duration Frequency
3
- 2
-x-5
-x-to
2.5
-�25
t so
2
f 100
s
v
u 1.5
c
T
a+ x�
a 1
c \X�X
�����\X�X� _
0.5 - _ \x-- -X X-X-X
_ =�,3
10 15 20 25 30 35 40 45 50 55 60 120 180 360 720 1440
Duration (minutes)
SECTION 6
Pipe Flow Calculations
Channel Report
Hydraflow Express Extension for Autodesk®Civil 3D®by Autodesk, Inc. Thursday, Feb 19 2026
100 YR - SDCB MA TO SDMH 3.1
Circular Highlighted
Diameter (ft) = 1.00 Depth (ft) = 0.37
Q (cfs) = 0.930
Area (sqft) = 0.27
Invert Elev (ft) = 100.00 Velocity (ft/s) = 3.51
Slope (%) = 0.50 Wetted Perim (ft) = 1.31
N-Value = 0.010 Crit Depth, Yc (ft) = 0.41
Top Width (ft) = 0.97
Calculations EGL (ft) = 0.56
Compute by: Known Q
Known Q (cfs) = 0.93
Elev (ft) Section Depth (ft
102.00 2.00
101.50 1.50
101.00 1.00
100.50 0.50
100.00 0.00
99.50 -0.50
0 1 2 3
Reach (ft)
Channel Report
Hydraflow Express Extension for Autodesk®Civil 3D®by Autodesk, Inc. Thursday, Feb 19 2026
100 YR - SDCB 3.1 B TO SDCB 3.1A
Circular Highlighted
Diameter (ft) = 1.00 Depth (ft) = 0.28
Q (cfs) = 0.550
Area (sqft) = 0.18
Invert Elev (ft) = 100.00 Velocity (ft/s) = 3.02
Slope (%) = 0.50 Wetted Perim (ft) = 1.12
N-Value = 0.010 Crit Depth, Yc (ft) = 0.31
Top Width (ft) = 0.90
Calculations EGL (ft) = 0.42
Compute by: Known Q
Known Q (cfs) = 0.55
Elev (ft) Section Depth (ft
102.00 2.00
101.50 1.50
101.00 1.00
100.50 0.50
v
100.00 0.00
99.50 -0.50
0 1 2 3
Reach (ft)
Channel Report
Hydraflow Express Extension for Autodesk®Civil 3D®by Autodesk, Inc. Thursday, Feb 19 2026
100 YR - SDCB 3.2A TO SDMH 3.2
Circular Highlighted
Diameter (ft) = 1.00 Depth (ft) = 0.63
Q (cfs) = 2.330
Area (sqft) = 0.52
Invert Elev (ft) = 100.00 Velocity (ft/s) = 4.47
Slope (%) = 0.50 Wetted Perim (ft) = 1.83
N-Value = 0.010 Crit Depth, Yc (ft) = 0.66
Top Width (ft) = 0.97
Calculations EGL (ft) = 0.94
Compute by: Known Q
Known Q (cfs) = 2.33
Elev (ft) Section Depth (ft
102.00 2.00
101.50 1.50
101.00 1.00
IL
100.50 0.50
100.00 0.00
99.50 -0.50
0 1 2 3
Reach (ft)
Channel Report
Hydraflow Express Extension for Autodesk®Civil 3D®by Autodesk, Inc. Thursday, Feb 19 2026
100 YR - SDCB 3.2B TO SDCB 3.2A
Circular Highlighted
Diameter (ft) = 1.00 Depth (ft) = 0.43
Q (cfs) = 1.240
Area (sqft) = 0.33
Invert Elev (ft) = 100.00 Velocity (ft/s) = 3.81
Slope (%) = 0.50 Wetted Perim (ft) = 1.43
N-Value = 0.010 Crit Depth, Yc (ft) = 0.47
Top Width (ft) = 0.99
Calculations EGL (ft) = 0.66
Compute by: Known Q
Known Q (cfs) = 1.24
Elev (ft) Section Depth (ft
102.00 2.00
101.50 1.50
101.00 1.00
100.50 0.50
100.00 0.00
99.50 -0.50
0 1 2 3
Reach (ft)
Channel Report
Hydraflow Express Extension for Autodesk®Civil 3D®by Autodesk, Inc. Thursday, Feb 19 2026
100 YR - SDCB 3.3 TO SDMH 3.3
Circular Highlighted
Diameter (ft) = 1.00 Depth (ft) = 0.53
Q (cfs) = 1.780
Area (sqft) = 0.42
Invert Elev (ft) = 100.00 Velocity (ft/s) = 4.19
Slope (%) = 0.50 Wetted Perim (ft) = 1.63
N-Value = 0.010 Crit Depth, Yc (ft) = 0.57
Top Width (ft) = 1.00
Calculations EGL (ft) = 0.80
Compute by: Known Q
Known Q (cfs) = 1.78
Elev (ft) Section Depth (ft
102.00 2.00
101.50 1.50
101.00 1.00
100.50 _ 0.50
100.00 0.00
99.50 -0.50
0 1 2 3
Reach (ft)
Channel Report
Hydraflow Express Extension for Autodesk®Civil 3D®by Autodesk, Inc. Thursday, Feb 19 2026
100 YR - SDCB 3.4 TO SDMH 3.4
Circular Highlighted
Diameter (ft) = 1.00 Depth (ft) = 0.57
Q (cfs) = 2.030
Area (sqft) = 0.46
Invert Elev (ft) = 100.00 Velocity (ft/s) = 4.37
Slope (%) = 0.50 Wetted Perim (ft) = 1.71
N-Value = 0.010 Crit Depth, Yc (ft) = 0.61
Top Width (ft) = 0.99
Calculations EGL (ft) = 0.87
Compute by: Known Q
Known Q (cfs) = 2.03
Elev (ft) Section Depth (ft
102.00 2.00
101.50 1.50
101.00 1.00
100.50 - 0.50
100.00 0.00
99.50 -0.50
0 1 2 3
Reach (ft)
Channel Report
Hydraflow Express Extension for Autodesk®Civil 3D®by Autodesk, Inc. Thursday, Feb 19 2026
100 YR - SDCB 3.5A TO SDMH 3.5
Circular Highlighted
Diameter (ft) = 1.00 Depth (ft) = 0.47
Q (cfs) = 1.460
Area (sqft) = 0.36
Invert Elev (ft) = 100.00 Velocity (ft/s) = 4.00
Slope (%) = 0.50 Wetted Perim (ft) = 1.51
N-Value = 0.010 Crit Depth, Yc (ft) = 0.51
Top Width (ft) = 1.00
Calculations EGL (ft) = 0.72
Compute by: Known Q
Known Q (cfs) = 1.46
Elev (ft) Section Depth (ft
102.00 2.00
101.50 1.50
101.00 1.00
100.50 0.50
100.00 0.00
99.50 -0.50
0 1 2 3
Reach (ft)
Channel Report
Hydraflow Express Extension for Autodesk®Civil 3D®by Autodesk, Inc. Thursday, Feb 19 2026
100 YR - SDCB 3.5B TO SDCB 3.5A
Circular Highlighted
Diameter (ft) = 1.00 Depth (ft) = 0.34
Q (cfs) = 0.790
Area (sqft) = 0.24
Invert Elev (ft) = 100.00 Velocity (ft/s) = 3.32
Slope (%) = 0.50 Wetted Perim (ft) = 1.25
N-Value = 0.010 Crit Depth, Yc (ft) = 0.38
Top Width (ft) = 0.95
Calculations EGL (ft) = 0.51
Compute by: Known Q
Known Q (cfs) = 0.79
Elev (ft) Section Depth (ft
102.00 2.00
101.50 1.50
101.00 1.00
100.50 0.50
100.00 0.00
99.50 -0.50
0 1 2 3
Reach (ft)
SECTION 7
Drainage Basin Map
\ _
DAYSPRING
SUBDIVISION NO. 2
\ ` I
I ❑ ® 22 '
19
® I I I
FUTURE PHASE 3.2
— _ —.os° I 18 ❑ I I ❑ 21
- - -- 9C
LEGEND 3.2A 3.2E 1
96 4
BASIN BOUNDARY LINE 3 1 10 I I I a 7 ❑ ❑7 20 ❑
SUB—BASIN BOUNDARY LINE a.sA 3.ae
BLOCK 14 08 I I
I
TIME OF CONCENTRATION I 11 3 16 ❑7
I } 19 I
3.1 BASIN NUMBER 3
3.1 A . 12 I IJI
,0.73. BASIN AREAI I
5
O
31A 15 8
SUB—BASIN NUMBER Q 9
oc m 3
o.ao o SUB—BASIN AREA Z BLOCK 13 Z
I BLOCK 12 18 I I
® ® ROADWAY INLET 3
3 13 I I 14 I 9LU
I
LIJ
13 10 m
c I ❑ 11 � I I
II) I 16 I I
W BELLE MEAD DR
FUTURE PHASE
I I I 7
L II I
� 5C I I I 12 13 15
❑ ❑ II ❑
3.3
23
• •41 ° 14C
3.6 8
.28 W RIDGESIDE ST
/ / 3.4
22
20C 19 8 � 17Ci 6 15 14 13 2 1 10C
N
24C 21
FEET BLOCK 11 ❑9
I
I I
100 0 50 100 —
SAFFORD LATERAL
GRAPHIC SCALE
----------------------
1 inch A00 ft.Horizontal � TOP T^o --
CESCE 00H,%UL4La14Z DAYSPRING SUBDIVISION NO. 3 Toll Brothers
ENGINEERING PLANNING SURVEYING ENVIRONMENTAL DRAINAGE CATCHMENT PLAN
ESE Consultants,Inc.
3103 W.Sheryl Drive•Suite 100•Meridian,ID 83642 February 19, 2026 - Meridian, Idaho AMERICA'S LUXURY HOME BUILDER*
T:208-424-0020