Fire Dept REV Comments
MAYOR
ROBERT D. CORRIE
COUNCil.. ME:MBERS
WILLlAML.M. NARY
KEITHBIRD
TAMMY DE WEERD
CHERIE McCANDLESS
RURAL FIRE COMMISSIONERS
RICHARD GREENE
TERRY LEIGHTON
STEVE ELLIOTT
CHIEF
KENW. BOWERS
;_____ T
"....~..-.,.'^.,-,._-_... ~,-
J,
oU'eridi!C'
IDAHO ,,~
~ ,p
C'~ <
~ ... 11lE.....SI.JflE V .. f:M
MERIDIAN CITY/RURAL FIRE DEPARTMENT
DEPUTY CHIEF - FIRE PREVENTIoN
JOSEPH Sn.. VA
DEPliTY CHIEF - TRAINING
BILL JOHNSON
540 East Franklin Road
Meridian, ill 83642
(208) 888-1234
Fax (208) 895-0390
December 11, 2002
-, ~,..,,,,,,,",,,,,,\,,.,,,,,,,,",,,_,,~,~~,.,.>,,,_._,,,_,_,",,=-,,,,,.,,,,,,,,,,,,.,,,,,,,,,,;-,-~' """C~'''_'C':F
_._._"__. ~_._".__ ,"0'_.'_______'."_"",___""0_"__"""_'___ __'~'_'''~'''''__',,_m,,_,"._'m__'n_ ,,,.,,_, '''_..
RECEIVED
DEe 12 2002
City Of Meridian
City Clerk Office
TO: Mayor, City Council & Meridian Planning & Zoning Commission
FROM: Joseph Silva, Deputy Chief, Fire Prevention
SUBJECT: Treasure Valley Pediatrics Revised CUP 02-034
The following will be the requirements and/or concerns to provide minimum levels of fire
protection for the proposed project:
1. That a fire-flow as required by the Uniform Fire Code is provided to service
the entire project. Fire hydrants shall be placed an average of 350' apart.
1997 UFC Appendix ill-A
2. Acceptance of the water supply for fire protection will be by the Meridian
Water Department.
3. Final Approval of the fire hydrant locations shall be by the Meridian Fire
Department.
4. All roads shall have a turning radius of 28' inside and 48' outside.
5. Operational fire hydrants are required before combustible construction
begins. UFC 901.4.2 & 901.3
6. The proposed subdivision will have an unknown transient population and
will have an unknown impact Meridian Fire Department call volumes.
According to a report completed by Fire & Emergency Services
Consulting Group in February of 2000 our requests for service are
projected to reach 2800 in the year 2005 and 3800 by the year 2010, this is
up from 2069 responses in the year 2000.
7. All building uses and processes to comply with the fire code in effect at the
time of construction.
8. The driveway shall have a clear driving surface which is20' wide available
at all times.