HomeMy WebLinkAboutC5.50 Drainage Details V15
Concrete Collar Detail
SCALE: NTS
LID PER PLANS.
8"
T
S
A
L
P
O
L
Y
N
D
U
C
T
I
L
E
I
R
O
N
LID PER PLANS.
TWO (2) #4 REBAR HOOPS.
SEE NOTE 2.
NOTES:
1. TOP OF CONCRETE COLLAR TO BE FLUSH WITH COVER.
2. FIBRILLATED POLYPROPYLENE FIBER (ADDED PER MANUFACTURERS
RECOMMENDATIONS) MAY BE USED IN LIEU OF #4 REBAR IN CONCRETE COLLARS.
3. ALL CONCRETE TO BE 4000 PSI (MIN).
4. FILTER FABRIC AND ALL SEDIMENT TO BE REMOVED AFTER ALL CONSTRUCTION IS
COMPLETE.
5. FOR ALL RIMS IN CONCRETE FLATWORK REFER TO DETAIL X/C2.XX.
9"
9"
4.5"
2"
MINIMUM OF FIVE (5) OR 20" MAX O.C.
SPACING (WHICHEVER IS GREATER) #4
REBAR VERTICALS.
SEE NOTE 2.
TWO (2) #4 REBAR HOOPS.
SEE NOTE 2.
MINIMUM OF FIVE (5) OR 20" MAX O.C.
SPACING (WHICHEVER IS GREATER) #4
REBAR VERTICALS.
SEE NOTE 2.
20" (MAX)
VARIES (EXTEND MIN. 1 ' BELOW BOTTOM OF ASTM C-33 FILTER SAND)
WELL
CAP
WELL
CAP
3/4"-MINUS, 1.5"-2" DRAIN
ROCK, OR ASTM C-33 FILTER
SAND
PVC END CAP, SOLVENT WELD OR
GASKETED (WATERTIGHT)
12"
6"
FINISH GRADE
18"
18"
24" DIA.
24"
6"
PLAN VIEW
CONCRETE COLLAR IN NON-TRAFFIC AREAS
PLAN VIEW
CONCRETE COLLAR IN TRAFFIC AREAS
SECTION
CONCRETE COLLAR
(2) #4 REBAR
HOOPS WITH
#4 VERTICALS
12"
36" 12"
WELL COVER. 8" Ø WATERTIGHT
GALVANIZED STEEL COVER AND
CANISTER
PVC CAP, GASKETED (WATERTIGHT)
CONCRETE COLLAR, CLASS
3000 (ISPWC 703)
THREE 6" Ø COILS
6" Ø PVC
(ASTM D-3034 SDR 35)
2 STAINLESS STEEL HOSE CLAMPS
AT 3" SPACING. SECURE
GEOTEXTILE IN PLACE
WRAP PORTION OF PIPE IN SAND WITH
GEOTEXTILE
(TYPE 1 PER ISPWC SECTION 2050)
6" Ø PERFORATED PIPE
(ASTM D-3035 SDR 35 WITH 6 3/8" Ø
HOLES SPACED 3" O.C.
ASTM C-33 FILTER SAND
NO. 12 AWG. GALVANIZED
FINDER WIRE
NOTE:
1. CONTRACTOR SHALL NOTIFY THE ENGINEER
IMMEDIATELY IF GROUNDWATER IS
ENCOUNTERED WITHIN 3 FEET OF THE
BOTTOM DESIGN ELEVATION FOR ANY
INFILTRATION FACILITY.
2. MONITORING WELLS LOCATED WITHIN
ACHD RIGHT-OF-WAY SHALL BE INSTALLED
3 PER ISPWC (ACHD SUP) SD-627.
Monitoring Well
Scale: NTS
8'-10"
5" 5'-7" ID 6"
6'-6"
3'-11"
1'-8"
2' 3'-7"
6'
4'-10"
1'-6" CL
8'-10-1/2"
8'-3"
4'-3"
4'-10-1/2"
(6) - 18" x 24" KNOCKOUT PANELS
(2X) 1 EACH SIDE
(4x) 2 EACH SIDE
SEE NOTE 1
(2) - 24" Ø HOLE THRU FOR MANHOLE
ACCESS. SEE NOTES 2 AND 3
NOTES:
1. ALL HOLES FOR INLET/OUTLET PIPES SHALL BE CORE
DRILLED. PROVIDE A FLEXIBLE MANHOLE
CONNECTOR (KOR-N-SEAL OR APPROVED
SUBSTITUTION).
2. PROVIDE STANDARD MANHOLE FRAME, COVER AND
RISER PER ISPWC SD-617. CONSTRUCT CONCRETE
COLLAR PER ISPWC SD-616.
3. COORDINATE WITH SITE GRADING AND DRAINAGE
PLAN FOR LOCATIONS OF GRATED INLETS.
INLET SIZE AND LOCATION VARY.
REFER TO DRAINAGE PLAN (TYP. ALL)
A A
PLAN
SECTION AA PROFILE
4'
3'-8"
SUMP ELEVATION PER PLANS
IE IN
PER PLANS
IE OUT PER
PLANS
2
Oldcastle 1000 Gal. S/G Trap
Scale: NTS
20213
3 1 0 0 B R I S T O L S T R E E T , S U I T E 4 0 0
C O S T A M E S A , C A 9 2 6 2 6
W W W . N G G P A R T N E R S . C O M
T 9 4 9 . 7 5 6 . 0 8 1 8 F 9 4 9 . 7 5 6 . 0 1 4 5
A R C H I T E C T U R E ● P L A N N I N G ● I N T E R I O R S
REV DESCRIPTION DATE
2700 E. Overland Rd.
Meridian, ID 83642
SEASONS AT MERIDIAN
NEWMAN GARRISON + PARTNERS, INC
COPY RIGHT 2019 NEWMAN GARRISON + PARTNERS
MORGAN HOLDINGS &
STONE HILL
38 Glen Gary Dr., Ste. 200
Aspen, CO 81611
7301 Peak Dr., Ste. 200
Las Vegas, NV 89128
TLG PN: 120124
A DELTA A 07/22/2022
C5.50
Drainage Details
SOLID WALL PVC PIPE. EXTEND 1
FOOT INTO DRAIN ROCK.
LENGTH VARIES. SEE PLANS
WIDTH VARIES.
SEE PLANS
PLAN
PROFILE
SAND AND GREASE TRAP. INLET
AND OUTLET LOCATIONS VARY.
SEE PER PLANS
PERFORATED STORM DRAIN PIPE. SIZE
AND ELEVATION PER PLANS.
FINISH GRADE VARIES
1-FT MIN. COVER
ACHD REQUIREMENTS:
OUTSIDE ROADWAY - 1.5-FT MIN. COVER
INSIDE ROADWAY - 1-FT MIN. COVER BELOW ROAD SUBGRADE
6" MIN.
TOP OF ROCK
ELEVATION
PER PLANS.
BOTTOM OF ROCK.
ELEVATION PER PLANS.
18" OF ASTM C33
FILTER SAND
SEASONAL HIGH GROUND WATER
NATIVE FREE DRAINING SOILS.
OVER-EXCAVATE TO FREE DRAINING
SOILS PER PLAN (WHERE INDICATED)
NATIVE FREE DRAINING SOILS.
OVER-EXCAVATE TO FREE DRAINING
SOILS PER PLAN (WHERE INDICATED)
DESIGN INFILTRATION RATE = 8-IN/HR
LAP 1 '
MIN.
AASHTO M288 CLASS 2 NON-WOVEN
GEOTEXTILE ON TOP AND SIDES, INSTALL
NILEX HDPE 40 MIL LINER, OR ENGINEER
APPROVED EQUAL, OUTSIDE OF FILTER
FABRIC ON SIDE OF SEEPAGE BED
CLOSER THAN 25-FT TO WATER MAIN.
FOR FACILITIES LOCATED IN ACHD
R.O.W., GEOTEXTILE SHALL MEET
REQUIREMENTS OF ACHD BMP 20 AND
SECTION 8202.23 OF THE ACHD
STORMWATER DESIGN MANUAL.
3 INCH WASHED DRAIN ROCK
PER ISPWC SECTION 801.
FACILITIES LOCATED IN THE
R.O.W. SHALL USE 3/4" TO 2"
ANGULAR ROCK.
PERFORATED PIPE
SIZE AS NOTED ON PLANS, SEE
PERFORATION SCHEDULE BELOW.
FACILITIES WITHIN THE R.O.W.
SHALL USE 18" PERFORATED PIPE.
FINISH GRADE
WIDTH VARIES.
SEE PLANS
DEPTH PER
PLANS
SECTION A-A
A
A
1 ', MIN. (5' MIN. FOR
ACHD SEEPAGE BEDS)
END
CAP
NOTES:
1. CONTRACTOR SHALL NOTIFY ENGINEER PRIOR TO TRENCH CONSTRUCTION AND SHALL
VERIFY ALL MATERIALS, LOCATIONS AND SIZES.
2. MINIMUM SEPARATION FROM THE BOTTOM OF ANY INFILTRATION FACILITY TO SEASONAL
HIGH GROUND WATER OR BED ROCK IS 3 FEET. CONTRACTOR SHALL NOTIFY THE
DESIGNER ENGINEER IMMEDIATELY IF GROUND WATER OR BEDROCK IS ENCOUNTERED
WITHIN 3 FEET OF THE BOTTOM DESIGN ELEVATION OF ANY INFILTRATION FACILITY.
3. CONTRACTOR TO HAVE PERCOLATION TEST PERFORMED BY SOILS ENGINEER AFTER
SEEPAGE TRENCH IS FULLY EXCAVATED. IF THE PERCOLATION IS LESS THAN THE DESIGN
INFILTRATION RATE OF 8 INCHES PER HOUR AS SPECIFIED BY THE SOILS REPORT AND
ENGINEER, CONTRACTOR MUST NOTIFY THE ENGINEER IMMEDIATELY.
4. GROUND WATER AND SOIL DATA FOR THIS SITE IS BASED UPON ATLAS's GEOTECHNICAL
ENGINEERING REPORT FILE NO. B201400g DATED 10-19-2020 AND SUBSEQUENT
AMENDMENTS.
5. FOR ALL SEEPAGE BEDS LOCATED WITHIN THE RIGHT-OF-WAY, CONTRACTOR SHALL
COORDINATE WITH ACHD INSPECTION FOR PLACEMENT OF ELECTRONIC MARKERS ON
EACH CORNER OF THE FACILITY DURING CONSTRUCTION AND PRIOR TO BACKFILLING.
6. ALL SEEPAGE BEDS LOCATED WITHIN THE RIGHT-OF-WAY SHALL BE INSTALLED PER ACHD
STORMWATER BMP 20 STANDARDS AND SPECIFICATIONS.
1
Standard Seepage Bed
SCALE: NTS
MONITORING WELL PER
DETAIL 3 THIS SHEET
3' MIN.
24" MIN.
NOTE:
1. ALL PIPE CONNECTIONS/JOINTS SHALL BE SEALED WATER TIGHT.
8”x8”x
3
16” GALVANIZED STEEL PLATE WITH
CUTOUT MATCHING PROFILE OF DOWNSPOUT.
PLATE SHALL LIE FLAT ON SURFACE OF FINISHED
GRADE AND BE ABLE TO SLIDE UP DOWNSPOUT
FOR MAINTENANCE. DOWNSPOUT SHALL
PROTRUDE DOWN THROUGH PLATE SO THE
PLATE CANNOT BE REMOVED WITHOUT FIRST
REMOVING DOWNSPOUT. PAINT SIDES AND
EDGES OF PLATE TO MATCH COLOR OF
DOWNSPOUT.
COVER PLATE. SEE ENLARGEMENT.
8" SQ.
R
1
2
" (TYP)
PVC PIPE BELOW CUT FLUSH
WITH FINISHED GRADE
BUILDING WALL
PIPE CUT FLUSH
WITH FINISHED
GRADE
STORM DRAIN PIPING,
BEND AND REDUCER
AS NEEDED TO
ESTABLISHED DEPTH.
SLOPE AT 2.0% MIN.
EXTEND PER PLAN. PROVIDE APPROPRIATELY
SIZED TEE, WYE, CROSS OR REQUIRED FITTINGS
AS NEEDED AT CONNECTION POINT WITH
MAINLINE STORM DRAIN.
DOWNSPOUT PER
ARCHITECT
FINISH GRADE
PER PLAN
Scale: NTS
Gutter Downspout Connection
6
A SECTION A-A
A
PROFILE
MECHANICAL PLUG
45° BEND
WYE FITTING
12" 4" 12"
4"
6"
6"
FIBER JOINT PACK
6" Ø SOLID BRASS BOLT-DOWN COVER WITH
FRAME. COVER TO BE STAMPED "STORM".
SEE NOTES 5 AND 6.
TYPE 1 BEDDING MATERIAL
12"
(SEE NOTES
5 AND 6)
18" MIN.
MISSION COUPLER OR APPROVED EQUAL
SERVICE LINE PER PLAN
1 '-6"
(SEE NOTES 5 AND 6)
NOTES:
1. ALL FITTINGS SHALL BE WATER TIGHT.
2. ALL REDUCING TEES AND COUPLERS SHALL BE ECCENTRIC
WITH MATCHING INVERT ELEVATIONS.
3. ALL PIPE SHALL BE INSTALLED PER ISPWC SD-301 AND
SD-302.
4. ALL PIPE SHALL BE ASTM D 3034 SDR 35 SOLID WALL PVC
OR AASHTO M 252 TYPE S OR D HDPE (ADS N-12 OR
EQUAL). SIZE PER PLAN.
5. OMIT CONCRETE COLLAR IN CONCRETE PAVEMENT AREAS.
COORDINATE WITH SITE LAYOUT AND MATERIALS PLAN.
6. COLLAR, FRAME, AND COVER SHOWN IN NON-TRAFIC
AREAS. INSTALL CLEANOUT PER ISPWC SD-506A IN ALL
TRAFFIC AREAS.
4
Cleanout Detail
Scale: NTS
07-22-2022 (100% CD)
1 ' MIN. BEYOND
BOTTOM OF SAND
1' MIN. BEYOND
BOTTOM OF SAND
PIPE PERFORATION SCHEDULE
60°'
(TYP.)
PERFORATIONS
TO BE 1/4" AT
3" O.C., 6 ROWS
Ø PER PLANS
FINISHED SIDEWALK OR ROAD
SURFACE & MATERIALS PER PLAN
BACKFILL OVER BED WITH 6-IN MIN.
8-INCH MINUS GRANULAR STRUCTURAL
BACKFILL MATERIAL TO BOTTOM OF
ROADWAY SUBGRADE PER ACHD BMP 20
WOVEN GEOTEXTILE FABRIC
REQUIRED OVER TOP OF BED IN
PUBLIC ROW PER ACHD BMP 20
ZONE OF
INFLUENCE
4-INCH PERFORATED PVC PIPE, GRADE TO DRAIN
(0.5% MIN.), CONNECT TO NEAREST ROOF DRAIN
OR STORM DRAIN FACILITY WITH BACKWATER
VALVE AND APPROPRIATE TRANSITION FITTINGS.
TOP OF PIPE SHALL BE INSTALLED BELOW TOP OF
FOOTING. WHERE PIPE GRADE IS BELOW BOTTOM
OF FOOTING, PIPE SHALL BE INSTALLED OUTSIDE
ZONE OF INFLUENCE AS SHOWN.
45°
3" WASHED DRAIN ROCK
PER ISPWC SECTION 801
NON-WOVEN GEOTEXTILE FABRIC
PER ISPWC SECTION 2050
BUILDING
FOUNDATION
(SHOWN APPROX.,
SEE STRUCTURAL)
FINISH GRADE
BUILDING STRUCTURE
AND FOUNDATION
(SHOWN APPROX., SEE
ARCHITECTURAL AND
STRUCTURAL FOR MORE
INFORMATION)
6" MIN. ALL AROUND PIPE
Scale: NTS
Foundation Drainage at Building Wall - Typical Section
7
A
0 8 / 0 3 / 2 2
08/03/2022
09/27/22
FPS-2022-0022