DATE: 1 /20/2022
TO: Joseph Dodson
MERIDIAN FIRE DEPARTMENT
STAFF REPORT
REVIEWER: Joseph Bongiorno, Deputy Chief of Prevention 208-888-1234
SUBJECT: H-2021-0096
PROJECT NAME: Aviation Subdivision
Fire Department Summary of Report:
Overview: This project can be serviced by the Meridian Fire Department, however, the current traffic
situation at Franklin and B1ackCat and B1ackCat and Aviator is not ideal because of school impacts to the
intersections.
1. Fire Response Time Travel time from nearest fire station (level of service expectation goal = 5 minutes)
This development currently falls just outside the 5 minute response time area as shown on the priority
growth map. The fire department is currently working to find land for a future fire station in this
area. It is currently nearest to Fire Station 2. This fire station is approximately 2.5 miles from the
project.
d
z
Z'_
W BU
z
(E IDS IAN,_
APPROVED
oar 04/27/22 source reliabili Current reliability of closest fire station (Reliability Goal is 80% or greater)
FILE NUMRER:H-�1oM levelopment is closest to Fire Station #2. Current reliability is 85% from this station and does
meet the targeted goal of 80% or greater.
MFD Station 31
506
384
76%
MFD Station 32
639
541
85%
MFD Station 33
687
547
80%
MFD Station 34
704
547
78%
MFD Station 35
506
423
84%
MFD Station 36
320
272
85%
3. Risk Identification Risk Factor (1=residential, 2=residential with hazards, 3=commercial,
4=commercial with hazards, 5=industrial)
This proposed commercial development has a risk factor of 2, in which current resources would not
be adequate to supply service to this propose project. Risk factors include an open waterway on the
project site and railroad treacks north of the project. Water rescue teams would have to be mutal
aided from another department. Other hazards may be found once the development is completed.
4. Accessibility Roadway Access, traffic, Radio Coverage
This project, as of the submittal of this report, does not meet all required access, road widths and
turnarounds as presented in the preliminary plat. Because this subdivision is at a dead end road with
no secondary access, ALL single family units constructed shall have fire sprinklers installed in them
per the 2018 IFC and NFPA 13, unless an approved secondary fire department access is provided.
D107.1 One- or two-family dwelling residential developments.
Developments of one- or two-family dwellings where the number of dwelling units exceeds 30 shall be provided
with two separate and approved fire apparatus access roads.
Exceptions:
1. Where there are more than 30 dwelling units on a single public or private fire apparatus access road
and all dwelling units are equipped throughout with an approved automatic sprinkler system in accordance
with Section 903.3.1.1, 903.3.1.2 or 903.3.1.3, access from two directions shall not be required.
The multifamily portion will have fire sprinklers installed anyway per the IFC and NFPA.
Any changes shall require fire department approval if any roadways or accesses are changed. The
shared drives for the multifamily area shall have a lighted address sign with map at each entrance
and the roadways shall be maintained 365 days a year for fire, EMS and police responses. The alley
shall be signed "No Parking Fire Lane" per appendix D of the 2018 IFC and ACHD sign Standards.
The termination of Aviator drive shall be at the approval of ACHD and the Meridian Fire
Department for a fire department approved access. There is currently no turn around shown in the
plans.
Page 2 of 9
(E IDI� I.�111
APPROVED -----------------
s �•
DATE 04/27/22
i
i
RE NLNKP
�
, tlaK►
�
• r f
1
I
Itlodltl „ 'ILV{fti ��
,, ,� �
�,��,��
1
1 11
to
l
1
777
7
1 ;\ •S �� 1 M([k•
y /I.
1 I
� _ , I R.IICIC• r � i � r
_ _
�
1
fix{ '. ��i'- � _ /LfICI�• tl11M.k.
��
.'ter.•
5. SpecialtyMesource needs
a. Aerial device needed for development (more than 30' in height)?
i. If yes, is one available within a 12 minute travel time goal
This proposed project will require an aerial device. The closest truck company is 8 minutes travel
time (under ideal conditions) to the proposed development, and therefore the Fire Department can
meet this need in the required timeframe if a truck company is required. This fire station is
approximately 3.5 miles from the project.
b. Other specialty needs (water rescue, hazmat, and technical rescue)?
i. If yes, is one available within a 5 minute travel time?
In the event of a hazmat event, there will need to be mutual aid required for the
development. In the event of a structure fire an additional truck company will be required. This
will require additional time delays as a second truck company is not available in the city. Water
rescue teams would have to be mutal aided from another department in the event of a water
rescue.
6. Water Supply (list expectations)
Water supply for this proposed development requires 1000 gallons per minute for one hour for the
single family area. Commercial and office occupancies will require a fire -flow consistent with
International Fire Code Appendix B to service the proposed project. (Approximate — see appendix B
Page 3 of 9
(E IDS IAN�-
APPROVED 12018International Fire Code) The fire flow requirements may be less if the building is fully
DATE: 04/27/22 11 —
FILE NUMBER: "-�1oM
Other Comments
Project specific comments are listed below.
***All IFC code sections per 2018 IFC or as noted***
RESOURCE AVAILABILITY - Fire Flow and Water Supply:
1. Fire Flow: One and two family dwellings not exceeding 3,600 square feet require a fire -
flow of 1,000 gallons per minute for a duration of 1 hours to service the entire project.
One and two family dwellings in excess of 3,600 square feet require a minimum fire flow
as specified in Appendix B of the International Fire Code. Fire Hydrant spacing shall be
provided as required by Appendix C of the International Fire Code.
2. Fire Flow: Commercial and office occupancies will require a fire -flow consistent with
International Fire Code Appendix B to service the proposed project. Fire hydrants shall
be placed per Appendix C.
3. Water Supply: Final Approval of the fire hydrant locations shall be by the Meridian Fire
Department or their designee in accordance with International Fire Code Section (IFC)
507.5.4 as follows:
a. Fire hydrants shall have a Storz LDH connection in place of the 4 '/2" outlet. The
Storz connection may be integrated into the hydrant or an approved adapter may be
used on the 4 1/2" outlet.
b. Fire hydrants shall have the Storz outlet face the main street or parking lot drive aisle.
c. Fire hydrants shall be placed on corners when spacing permits.
d. Fire hydrants shall not have any vertical obstructions to outlets within 10'.
e. Fire hydrants shall be placed 18" above finished grade to the center of the Storz
outlet.
f. Fire hydrants shall be provided to meet the requirements of the Meridian Water Dept.
Standards.
g. Show all proposed or existing hydrants for all new construction or additions to
existing buildings within 1,000 feet of the project.
4. Water Supply: Where a portion of the facility or building hereafter constructed or moved
into or within the jurisdiction is more than 400 feet (122 m) from a hydrant on afire apparatus
access road, as measured by an approved route around the exterior of the facility or building,
on -site fire hydrants and mains shall be provided where required by the code official as
set forth in International Fire Code Section 507.5.1. For buildings equipped throughout
with an approved automatic sprinkler system installed in accordance with Section
903.3.1.1 or
903.3.1.2 the distance requirement shall be 600 feet (183).
a. For Group R-3 and Group U occupancies, the distance requirement shall be 600 feet
(183 m).
b. For buildings equipped throughout with an approved automatic sprinkler system
installed in accordance with Section 903.3.1.1 or 903.3.1.2, the distance requirement
Page 4 of 9
(E IDIAN —
APPROVED
DATE: 04/27/22
FILE NUMBER:N D21oM
shall be 600 feet (183 m).
Water Supply: There shall be a fire hydrant within 100' of all fire department connections as
set forth in local amendment to the International Fire Code 10-4-1. Over 100 apartment
units without an approved sprinkler system or over 200 apartment units with an approved
sprinkler system will require a secondary access per International Fire Code Section
D104.3. The access roads shall be placed a distance apart equal to not less than one half of
the length of the overall diagonal dimension of the property or area to be served, measured
in a straight line as set forth in International Fire Code Appendix D 104.1.
6. Water Supply: All R-2 occupancies with 3 or more units shall be required to be fire
sprinkled as set forth in International Fire Code Section 903.2.8.
ACCESSIBILITY - Fire Department Roadways, Access and Addressing:
Roadways: In accordance with International Fire Code Section 503.2.5 and Appendix D,
Dead-end fire apparatus access roads in excess of 150 feet (45 720 mm) in length shall be
provided with an approved area for turning around fire apparatus. Phasing of the project
may require a temporary approved turn around on streets greater than 150' in length with
no outlet. Cul-D-Sacs shall be 96' in diameter minimum and shall be signed "No Parking
Fire Lane" per International Fire Code Sections 503.3 & D103.6 and ACHD sign
standards. There shall be two no parking fire lane signs on each side of the entrance to the
Cul-D-Sac and one sign at the head.
96'
28' R
TY R'
26'
96' DIAMETER
CUL-DE-SAC
8. Roadways: When required by the Fire Marshall, "No Parking Fire Lane" signs shall be
used per appendix D of the 2018 IFC. Signs shall be installed per ACHD standards. The
bottom of the sign(s) should be 7' above the road/sidewalk surface shall not be in the
travel way. The sign(s) shall be installed about 6" —1' behind the curbing or edge of
pavement on a Telspar post. No other signs shall be approved:
Page 5 of 9
(E IDIAN -
APPROVED
DATE 04/27/22
FILE NUMBER: "-�1oM
D103.6 Signs. where required by the fire code official, fire
apparatus access roads shall be marked with permanent NO
PARKING —FIRE LANE signs complying with Figure
D103.6. Signs shall have a minimum dimension of 12 inches
(305 mm) wide by 18 inches (457 mm) high and have red let-
ters on a white reflective background. Signs shall be posted
on one or both sides of the fire apparatus road as required by
Section D103.6.1 or D103.6.2.
SIGN TYPE "A" SIGN TYPE "C" SIGN TYPED"
NO NO NO
PARKING PARKING PARKING
FIRE LANE FIRE LANE FIRE LANE 18"
�12"� �12"— ^12"� —
FIGURE D103.6
FIRE LANE SIGNS
9. Roadways: All entrances, internal roads, drive aisles, and alleys shall have a turning radius
of 28' inside and 48' outside, per International Fire Code Section 503.2.4.
10. Roadways: All common driveways shall be straight or have a turning radius of 28' inside
and 48' outside and have a clear driving surface of 20' in width capable of supporting an
imposed weight of 80,000 GVW, per International Fire Code Section 503.2.
11. Roadways: All common driveways and alleys shall be maintained at all times for access
by fire, police and EMS at all times of the year.
12. Roadways: Private Alleys and Fire Lanes shall have a 20' wide improved surface
capable of supporting an imposed load of 80,000 lbs. All roadways shall be marked "No
Parking Fire Lane" per International Fire Code Sections 503.3 & D103.6 and ACHD sign
standards.
13. Roadways: Requirements for dead-end fire apparatus access roads that are between 500'-
750' in length are as follows: 1) Roadways shall be built to Ada County Highway District
cross section standards and have a clear driving surface of 26-feet in width available at all
times and shall have no parking. Both sides of the street shall be signed "No Parking Fire
Lane" per appendix D of the IFC; 2) Streets less than 32-feet in width shall have no parking
on one side. One side of the street shall be signed "No Parking Fire Lane" per appendix D of
the IFC and ACHD sign standards; and 3) Streets more than 39-feet in width shall be
allowed to have parking on both sides. These measurements shall be based on the drivable
surface dimension. Special approval is required for access roads over 750' in length per
International Fire Code Section D 103.6.1 and D 103.6.2. The roadway shall be able to
accommodate an imposed load of 80,000 GVW.
14. Roadways: To increase emergency access to the site a minimum of two points of access
will be required for any portion of the project which serves more than 30 homes, as set
forth in International Fire Code Section D107.1. The two entrances should be separated by
no less than %2 the diagonal measurement of the full development as set forth in International
Fire Code Section D 104.3. The applicant shall provide an additional stub street to the
property.
15. Roadways: Buildings over 30' in height are required to have access roads 26' in width
Page 6 of 9
(E IDS IAN,_
APPROVED
DAM: 04/27/22
FILE NUMBER: "-�1oM
minimum in accordance with the International Fire Code Appendix D Section D105.
Roadways: The roadways shall be built to Ada County Highway District cross section
standards and have a clear driving surface. Streets less than 26' in width shall have no on -
street parking. Both sides of the street shall be signed "No Parking Fire Lane" per appendix D
of the IFC and ACHD sign standards; streets less than 32' in width shall have parking only
on one side. One side of the street shall be signed "No Parking Fire Lane" per appendix D of
the IFC and ACHD sign standards. These measurements shall be based on the drivable
surface dimension exclusive of shoulders. The roadway shall be able to accommodate an
imposed load of 80,000 GVW as set forth in International Fire Code Section 503.2.1 and
D 103.6.1 and D 103.6.2.
17. Roadways: ALLEY — In all cases, right of ways shall be a minimum of 20' in width. The
entrance to the alley from the public street shall provide a minimum twenty-eight foot (28')
inside and forty-eight foot (48') outside turning radius. No parking shall be allowed on
either side of the street. Both sides of the alley shall be signed "No Parking Fire Lane" per
appendix D of the IFC and ACHD sign standards. The minimum distance for alley accessed
properties shall be 20' from the face of a garage to the property line. (International Fire Code
Section 503.4)
18. Roadways: Traffic calming devices. Traffic calming devices shall be prohibited unless
approved by the fire code official. National Fire P r o t e c t i o n IFC 503.4.1.
BUMP tea.
GURiR fT(SEE TABLE)
z �sEE
Mile TABLE)
X (SEE TAME)
oaErnan OF TR+vn
fOFY
—I LsSM Two
_M ri I
—
DY MTM OF TRAVEL : H
LLSEE TABLE) _E➢GE OF PMiLENT
BUMP �.
SPEED CL04ONS - FLAN VIEW
LOCAL ROAD
19. Access: Fire lanes, streets, and structures (including the canopy height of mature trees) shall
have a vertical clearance of 13'6 asset forth in International Fire Code Section 503.2.1.
20. Access: Where fire apparatus access roads or a water supply for fire protection are required to
be installed, such protection shall be installed and made serviceable prior to and during the time
of construction except where approved alternative methods of protection are provided.
Temporary street signs shall be installed at each street intersection where construction of new
roadways allows passage by vehicles in accordance with Section 505.2., as set forth in
International Fire Code Section (IFC) 501.4.
Page 7 of 9
CUEIDR IAN
APPROVED
DATE 04/27/22
FILE NUMBER: "-z 1z D95
1. Access: Provide a Fire Department Key box entry system for the complex prior to
occupancy as set forth in International Fire Code Section 506. Knox Boxes can be ordered
from www.knoxbox.com.
I3-
i w,c;e
r dM
KnoxBoxCC 3200 KnoxVaultO 4400
Standard Capacity 9 Maximum Capacity 9
22. Access: Based on the size of new construction and the location of the sprinkler room in
relation to the address side of the structure, the AHJ may require separate Fire
Department key box locations. One being at the main, address side entrance and the other
at the entrance to the sprinkler riser room. Knox Boxes can be ordered from
www.knoxbox.com.
23. Access: The Fire Department will require Fire Department locking Connection caps on all
FDC inlets. IFC 102.9. Caps can be ordered at www.knoxbox.com.
24. Access: All portions of the buildings located on this project must be within 150' of a
paved surface as measured around the perimeter of the building as set forth in International
Fire Code Section 503.1.1.
Page 8 of 9
(E IDS IAN,_
APPROVED
DAB: 04/27/22
FILE NUMBER: "-�1oM
Access: Multiple -family residential projects having more than 100 dwelling units shall be
equipped throughout with two separate and approved fire apparatus access roads.
a. Exception: Projects having up to 200 dwelling units may have a single approved
fire apparatus access road when all buildings, including nonresidential
occupancies, are equipped throughout with approved automatic sprinkler systems
installed in accordance with Section 903.3.1.1 or 903.3.1.2
26. Access: As set forth in International Fire Code Section 504.1, multi -family and
commercial projects shall be required to provide an additional sixty inches (60") wide access
point to the building from the fire lane to allow for the movement of manual fire suppression
equipment and gurney operations. The unobstructed breaks in the parking stalls shall be
provided so that building access is provided in such a manner that the most remote part of a
building can be reached with a length of 150' fire hose as measured around the perimeter of
the building from the fire lane. Code compliant handicap parking stalls may be included to
assist meeting this requirement. Contact the Meridian Fire Department for details.
27. Addressing: The first digit of the Apartment/Office Suite shall correspond to the floor level
as set forth in International Fire Code Section 505.1 and Meridian Amendment 10-4-1.
28. Addressing: The applicant shall work with Public Works and Planning Department staff to
provide an address identification plan and a sign which meets the requirements of the City
of Meridian sign ordinance and is placed in a position that is plainly legible and visible from
the street or road fronting the property, as set forth in International Fire Code Section 505.1
and Meridian Amendment 104-4-1.
ALL residences having two frontages (the street and an alleyway behind it) shall have address
numbers on the front of the building and on the backside facing the alley as well.
29. Addressing: If required by the Fire Code Official, the complex shall have a lighted
map at the entrance showing the layout of the complex. All building
numbers shall be backlit or frontlit for Police, Fire or EMS to easily see
them from dusk to dawn.