HomeMy WebLinkAboutG-1, Grounding Details V1APPROVED �._ 02128,22 TO ANTENNA COAX _. •.vna: a n � � i COPPER/GALVANIZED GROUND BAR 0 0 0 1:1 0:0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 o 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 o a o 0 o o o o o o o o o o o o o o Oo TWO HOLE LONG BARREL COMPRESSION LUG (TYP) NOTES: 1. DOUBLING UP "OR STACKING" OF CONNECTIONS IS NOT PERMITTED. 2. EXTERIOR ANTIOXIDANT JOINT COMPOUND TO BE USED ON ALL EXTERIOR CONNECTIONS. 3. GROUND BAR SHALL NOT BE ISOLATED FROM TOWER. MOUNT DIRECTLY TO ANTENNA MOUNT STEEL. ANTENNA SECTOR GROUND BAR DETAIL SCALE: NOT TO SCALE TO TOWER MOUNTED EQUIPMENT (TYP) TO ANTENNA MONOPOLE r ANTENNA GROUND BAR LOCATED AT MCL (BONDED TO TOWER STEEL) STANDARD COAX �;i 2 HOLE LUG (TYP) CABLE GROUND KIT (TYP) #6 STRANDED CU WIRE WITH GREEN, 60OV, THWN INSULATION (OR AS PROVIDED WITH GROUND KIT) (TYP) TO ANTENNA COAX COPPER/GALVANIZED GROUND BAR o o 0 o o o o o o o o o o o o o 0 0 0 o o 0 o o o o o o o o o o o o o 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 TWO HOLE LONG BARREL COMPRESSION LUG (TYP) #2 SOLID TINNED COPPER CONDUCTOR TO TOWER/SHELTER GROUND RING (2 TYP. FOR BOTTOM GROUND BAR ONLY) NOTES: 1. EXTERIOR ANTIOXIDANT JOINT COMPOUND TO BE USED ON ALL EXTERIOR CONNECTIONS. 2. GROUND BAR SHALL NOT BE ISOLATED FROM TOWER. MOUNT DIRECTLY TO TOWER STEEL (TOWER ONLY). 3. GROUND BAR SHALL BE ISOLATED FROM BUILDING OR SHELTER. TOWER/SHELTER GROUND BAR DETAIL SCALE: NOT TO SCALE 2-HOLE CRIMP/ COMPRESSION CONNECTOR STAINLESS STEEL BOLT TYP) STAINLESS STEEL FLAT WASHER (TYP) ] GROUND BAR - STAINLESS STEEL FLAT WASHER STAINLESS STEEL - — \ (TYP) BELLVILLE WASHER STAINLESS STEEL NUT (TYP) (TYP) SINGE CONNECTOR AT GROUND BARS STAINLESS STEEL BOLT MECHANICAL CONNECTION (TYP) STAINLESS STEEL FLAT WASHER / COAX GROUND BAR WITH COAX CABLE \, / INSULATOR, CONNECTED (TYP FOR ALL) \ DRAGON TOOTH WASHERDIRECTL_ \� OF MONOPOLE. SEE NOTE 1. (TYP) STEEL TO BTS EQUIPMENT VIA - 2/0 TINNED BARE TRAY OR ICE BRIDGE I I COPPER WIRE 2-HOLE CRIMP/ MONOPOLE PIER COMPRESSION STAINLESS STEEL FLAT WASHER GROUND WIRE CONNECTOR _ — (TYP) 1 SEE NOTE 3 STAINLESS STEEL �/ STAINLESS STEEL NUT GROUND WIRE NOTE 3 BELLVILLE WASHER (TYP) (TYP) - --�--� i-�� SINGLE CONNECTOR AT STEEL OBJECTS INSPECTION WELL ` i ` EXOTHERMIC WELD (TYP) NOTES: STAINLESS STEEL SELF -DRILLING STAINLESS STEEL 1. NUMBER OF GROUNDING BARS MAY VARY DEPENDING ON THE TYPE OF TOWER, ANTENNA METAL SCREW FLAT WASHER LOCATIONS AND CONNECTION ORIENTATION. COAXIAL CABLES EXCEEDING 200 FEET ON THE (TYP) (TYP) TOWER SHALL HAVE GROUND KITS AT THE MIDPOINT. PROVIDE AS REQUIRED. 2. ONLY MECHANICAL CONNECTIONS ARE ALLOWED TO BE MADE TO CROWN CASTLE USA INC. 2-HOLE CRIMP/ TOWERS. ALL MECHANICAL CONNECTIONS SHALL BE TREATED WITH AN ANTI -OXIDANT COATING. COMPRESSION - CONNECTOR 3. ALL TOWER GROUNDING SYSTEMS SHALL COMPLY WITH THE REQUIREMENTS OF THE RECOGNIZED EDITION OF ANSI/TIA 222 AND NFPA 780. DRAGON TOOTH METALLIC OBJECT WASHER (TYP) SINGLE CONNECTOR AT METALLIC/STEEL OBJECTS TYPICAL ANTENNA CABLE GROUNDING SCALE: NOT TO SCALE �-�`� ALE: HARDWARE DETAIL FOR EXTERIOR CONNECTIONS SCNOT TO SCALE T/FINISH GRADE n So z o 0 V) 00 8" PVC PLUG 8" PVC PLUG CPLG. (THIRD.) SUBGRADE #2 SOLID (TEST LOOP) NOTCH SIDES OF 8" PVC SCH 40 PIPE TO ALLOW EXIT/ENTRANCE OF EXOTHERMIC WELD GROUND RING WIRE II II II 1 I I � I — TRENCH BOTTOM 2/0 TINNED CU EXTERNAL CADWELD TEST LOOP TO TOWER GROUND RING WIRE GROUND RING WIRE NOTES: 5/8" 0 x 10'-0" LONG COPPER CLAD GROUND ROD 1. GROUND ROD SHALL BE DRIVEN VERTICALLY, NOT TO EXCEED 45 DEGREES FROM THE VERTICAL 2. GROUND WIRE SHALL BE MIN. 30" BELOW GRADE OR 6" BELOW FROST LINE. (WHICH EVER IS GREATER) AS PER N.E.C. ARTICLE 250-50(D) INSPECTION WELL DETAIL SCALE: NOT TO SCALE 6" WIDE METALLIC HTEL GRADE WARNING/LOCATOR TAPE AT \ 12" DEPTH N w 0 z CD O Z w EXOTHERMIC WELD 0 w GROUND RING #2 COPPER WIRE SOLID, TINNED FOR CARRIER AND ICE BRIDGE GROUND LOOP GROUND RING 2/0 FOR TOWER GROUND LOOP GROUND ROD COPPER CLAD STEEL ROD W/MIN. 5/8 0 x 10'-0" LONG NOTES: 1. GROUND ROD SHALL BE DRIVEN VERTICALLY, NOT TO EXCEED 45 DEGREES FROM THE VERTICAL 2. GROUND WIRE SHALL BE MIN. 30" BELOW GRADE OR 6" BELOW FROST LINE. (WHICH EVER IS GREATER) AS PER N.E.C. ARTICLE 250-50(D) 1 GROUND ROD DETAIL � v SCALE: NOT TO SCALE verizonN/ 180 WASHINGTON VALLEY ROAD BEDMINSTER, NJ 07921 CROWN CASTLE 1200 MACARTHUR BLVD, SUITE 200 MAHWAH, NJ 07430 • T r y I o n 1825 W. WALNUT HILL LANE, SUITE 120 IRVING, TEXAS 75038 VERIZON SITE NUMBER: 269916 BU #: 825952 MERIDIAN_RETAIL 3100 E. FLORENCE STREET, SUITE 100 MERIDIAN, ID 83642 EXISTING 50'-0" MONOPOLE ISSUED FOR: REV DATE DRWN DESCRIPTION DES./QA 0 01/13/22 PSK PINAI. AMC 1 02/08/22 HAM FINAL AMC S\ONAL &,v ��\GENSFQ 2FF i r fw Al Off/ 9TF OF OP1� \F ABEi: N IT IS A VIOLATION OF LAW FOR ANY PERSON, UN I .NSS THEY ARE ACTING UNDER THE DI RECTI ON OF A LICENSED PROFESSIONAL ENGINEER, TO ALTER THIS DOCUMENT. SHEET NUMBER: REVISION: -1 1