Loading...
HomeMy WebLinkAboutG-1, Grounding Details V1APPROVED 022822 TO ANTENNA COAX COPPER/GALVANIZED GROUND BAR 0 001�101�100000000000000 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 000c+0000000000000000 Oo TWO HOLE LONG BARREL COMPRESSION LUG (TYP) NOTES: 1. DOUBLING UP "OR STACKING" OF CONNECTIONS IS NOT PERMITTED. 2. EXTERIOR ANTIOXIDANT JOINT COMPOUND TO BE USED ON ALL EXTERIOR CONNECTIONS. 3. GROUND BAR SHALL NOT BE ISOLATED FROM TOWER. MOUNT DIRECTLY TO ANTENNA MOUNT STEEL. ANTENNA SECTOR GROUND BAR DETAIL SCALE: NOT TO SCALE TO TOWER MOUNTED EQUIPMENT (TYP) TO ANTENNA MONOPOLE r ANTENNA GROUND BAR LOCATED AT MCL (BONDED TO TOWER STEEL) STANDARD COAX �;i 2 HOLE LUG (TYP) CABLE GROUND KIT (TYP) r #6 STRANDED CU WIRE WITH GREEN, 60OV, THWN INSULATION (OR AS PROVIDED WITH GROUND KIT) (TYP) TO ANTENNA COAX COPPER/GALVANIZED GROUND BAR 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 j:,1,0:0000000000000 0 (5 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 TWO HOLE LONG BARREL COMPRESSION LUG (TYP) #2 SOLID TINNED COPPER CONDUCTOR TO TOWER/SHELTER GROUND RING (2 TYP. FOR BOTTOM GROUND BAR ONLY) NOTES: 1. EXTERIOR ANTIOXIDANT JOINT COMPOUND TO BE USED ON ALL EXTERIOR CONNECTIONS. 2. GROUND BAR SHALL NOT BE ISOLATED FROM TOWER. MOUNT DIRECTLY TO TOWER STEEL (TOWER ONLY). 3. GROUND BAR SHALL BE ISOLATED FROM BUILDING OR SHELTER. TOWER/SHELTER GROUND BAR DETAIL SCALE: NOT TO SCALE 2-HOLE CRIMP/ COMPRESSION CONNECTOR STAINLESS STEEL BOLT TYP) STAINLESS STEEL FLAT WASHER (TYP) ] GROUND BAR - STAINLESS STEEL FLAT WASHER STAINLESS STEEL - — \ (TYP) BELLVILLE WASHER STAINLESS STEEL NUT (TYP) (TYP) SINGE CONNECTOR AT GROUND BARS STAINLESS STEEL BOLT MECHANICAL CONNECTION (TYP) STAINLESS STEEL FLAT WASHER / COAX GROUND BAR WITH COAX CABLE INSULAT(TYP \, / FOR ALL) DIRECTLOR 0 TOENBOTEOM DRAGON TOOTH WASHER _ \� OF MONOPOLE. SEE NOTE 1. (TYP) STEEL TO BTS EQUIPMENT VIA — 2/0 TINNED BARE TRAY OR ICE BRIDGE I I COPPER WIRE 2—HOLE CRIMP/ MONOPOLE PIER COMPRESSION / STAINLESS STEEL FLAT WASHER GROUND WIRE CONNECTOR _ — (TYP) 1 SEE NOTE 3 STAINLESS STEEL �/ STAINLESS STEEL NUT GROUND WIRE NOTE 3 BELLVILLE WASHER (TYP) (TYR) - --�--� i-�� SINGLE CONNECTOR AT STEEL OBJECTS INSPECTION WELL i ` EXOTHERMIC WELD (TYP) NOTES: STAINLESS STEEL SELF —DRILLING STAINLESS STEEL 1. NUMBER OF GROUNDING BARS MAY VARY DEPENDING ON THE TYPE OF TOWER, ANTENNA METAL SCREW FLAT WASHER LOCATIONS AND CONNECTION ORIENTATION. COAXIAL CABLES EXCEEDING 200 FEET ON THE (TYP) (TYP) TOWER SHALL HAVE GROUND KITS AT THE MIDPOINT. PROVIDE AS REQUIRED. 2. ONLY MECHANICAL CONNECTIONS ARE ALLOWED TO BE MADE TO CROWN CASTLE USA INC. 2—HOLE CRIMP/ TOWERS. ALL MECHANICAL CONNECTIONS SHALL BE TREATED WITH AN ANTI —OXIDANT COATING. COMPRESSION CONNECTOR — 3. ALL TOWER GROUNDING SYSTEMS SHALL COMPLY WITH THE REQUIREMENTS OF THE RECOGNIZED EDITION OF ANSI/TIA 222 AND NFPA 780. DRAGON TOOTH METALLIC OBJECT WASHER (TYP) SINGLE CONNECTOR AT METALLIC/STEEL OBJECTS TYPICAL ANTENNA CABLE GROUNDING SCALE: NOT TO SCALE �-�`� ALE: HARDWARE DETAIL FOR EXTERIOR CONNECTIONS SCNOT TO SCALE T/FINISH GRADE 00 8" PVC PLUG 8" PVC PLUG CPLG. (THIRD.) N SUBGRADE w o #2 SOLID (TEST LOOP) z z o NOTCH SIDES OF 8" PVC SCH 40 PIPE V5 7 TO ALLOW EXIT/ENTRANCE OF i w EXOTHERMIC WELD / GROUND RING WIRE o w f -- -- —-- —— 1I I T1 II 1— I— TRENCH BOTTOM 2/0 TINNED CU EXTERNAL CADWELD TEST LOOP TO TOWER GROUND RING WIRE GROUND RING WIRE NOTES: 5/8" 0 x 10'-0" LONG COPPER CLAD GROUND ROD 1. GROUND ROD SHALL BE DRIVEN VERTICALLY, NOT TO EXCEED 45 DEGREES FROM THE VERTICAL 2. GROUND WIRE SHALL BE MIN. 30" BELOW GRADE OR 6" BELOW FROST LINE. (WHICH EVER IS GREATER) AS PER N.E.C. ARTICLE 250-50(D) INSPECTION WELL DETAIL SCALE: NOT TO SCALE 6" WIDE METALLIC HTEL GRADE WARNING/LOCATOR TAPE AT 12" DEPTH N 0 0 0 0 0 0 0 0 w 0 z CD O Z w EXOTHERMIC WELD 0 w GROUND RING #2 COPPER WIRE SOLID, TINNED FOR CARRIER AND ICE BRIDGE GROUND LOOP GROUND RING 2/0 FOR TOWER GROUND LOOP GROUND ROD COPPER CLAD STEEL ROD W/MIN. 5/8 0 x 10'-0" LONG NOTES: 1. GROUND ROD SHALL BE DRIVEN VERTICALLY, NOT TO EXCEED 45 DEGREES FROM THE VERTICAL 2. GROUND WIRE SHALL BE MIN. 30" BELOW GRADE OR 6" BELOW FROST LINE. (WHICH EVER IS GREATER) AS PER N.E.C. ARTICLE 250-50(D) 1 GROUND ROD DETAIL � v SCALE: NOT TO SCALE verizonil 3245 158TH AVENUE MS 231 BELLEVUE, WA 98008 CROWN CASTLE 1505 WESTLAKE AVENUE NORTH, SUITE 800 SEATTLE, WA 98109 L ,4� TOWER ENGINEERING PROFESSIONALS 4710 E ELWOOD ST, STE 9 PHOENIX, AZ 85040 OFFICE: (480) 285-0036 www.tepgroup.net VERIZON SITE NUMBER: 167122 BU #: 822731 BOISE_CALL_CENTER 2100 S SILVERSTONE WAY MERIDIAN, ID 83642 EXISTING 110'-0" MONOPOLE ISSUED FOR: REV DATE DRWN DESCRIPTION DI?S./QA 0 01/19/22 ORG CONSTRUCTION HMM 01/19/22 Graham M. Andres, P.E. Professional I :ngineer license: #15814 IT IS A VIOLATION OF LAW FOR ANY PERSON, UN I .NSS THEY ARE ACTING UNDER THE DI RECTI ON OF A LICENSED PROFESSIONAL ENGINEER, TO ALTER THIS DOCUNlENT. SHEET NUMBER: REVISION: -1 0