Please add this email to the public record. Thank you. Joe
Fire Flow: Commercial and office occupancies will require a fire-flow consistent with International Fire Code Appendix B
to service the proposed project. Fire hydrants shall be placed per Appendix C.
Water Supply: Final Approval of the fire hydrant locations shall be by the Meridian Fire Department or their designee in
accordance with International Fire Code Section (IFC) 508.5.4 as follows:
a. Fire hydrants shall have a Storz LDH connection in place of the 4 ½” outlet. The Storz connection may be
integrated into the hydrant or an approved adapter may be used on the 4 1/2" outlet.
b. Fire hydrants shall have the Storz outlet face the main street or parking lot drive aisle.
c. Fire hydrants shall be placed on corners when spacing permits.
d. Fire hydrants shall not have any vertical obstructions to outlets within 10’.
e. Fire hydrants shall be placed 18” above finished grade to the center of the Storz outlet.
f. Fire hydrants shall be provided to meet the requirements of the Meridian Water Dept. Standards.
g. Show all proposed or existing hydrants for all new construction or additions to existing buildings within 1,000
feet of the project.
Roadways: All entrances, internal roads, drive aisles, and alleys shall have a turning radius of 28’ inside and 48’ outside,
per International Fire Code Section 503.2.4.
Roadways: Emergency response routes and fire lanes shall not be allowed to have traffic calming devices installed
without prior approval of the Fire Code Official. National Fire Protection IFC 503.4.1.
Access: Operational fire hydrants, temporary or permanent street signs, and access roads with an all-weather surface
are required to be installed before combustible construction material is brought onto the site, as set forth in
International Fire Code Section (IFC) 501.4.
Access: Provide a Fire Department Key box entry system for the complex prior to occupancy as set forth in International
Fire Code Section 506.
Addressing: The applicant shall work with Public Works and Planning Department staff to provide an address
identification plan and a sign which meets the requirements of the City of Meridian sign ordinance and is placed in a
position that is plainly legible and visible from the street or road fronting the property, as set forth in International Fire
Code Section 505.1 and Meridian Amendment 104-4-1.
Joe Bongiorno CFI, CFEI
Deputy Chief – Fire Marshal
Meridian Fire
33 E. Broadway Ave., Ste. 210, Meridian, ID 83642
(Direct) 208-489-0458 (Cell) 208-936-9554
1
Dedication-Loyalty-Tradition
All e-mail messages sent to or received by City of Meridian e-mail accounts are subject to the Idaho law,
in regards to both release and retention, and may be released upon request, unless exempt from disclosure by law.
2