Mr. Dan Lardie May 16, 2019
Leavitt & Associates Engineers, Inc. Page 1 of 19
1324 1st Street South File 19213-A
Nampa, Idaho 83651
Re: Geotechnical Recommendation Report
Goddard Creek Townhomes
2780 West McMillan Road
Meridian, Idaho
Dan:
As per your authorization, on April 13, 2019, SITE personnel observed the excavation of
four test pits on the referenced property. Soil samples were gathered and submitted for
laboratory analysis. Based on the observed and reported conditions and compliance
with the recommendations provided herein, the referenced lot is acceptable for
construction of the planned development for multi-family structures. The planned
buildings can be constructed using standard construction methods. Conventional strip
foundations with slab on grade floors or a conventional crawlspace are acceptable.
Foundations can be designed to exert bearing pressures of up to 1500 psf on the
existing soils or upon approved structural fill. Based upon this bearing pressure and the
recommendations of this report being followed, we anticipate total settlements of less
than one inch, with differential settlements less than half of this value. If these values
are unacceptable, please contact SITE for additional recommendations.
Recommendations are also included herein for design of the proposed development.
We appreciate this opportunity to be of service. Please contact our office if additional
information or services are required.
Respectfully submitted,
Bob J. Arnold, PE
SITE Consulting,
NAL FN
QO�� STE,
4
B�etF �F
d, pR
v
a
Geotechnicel Services/Soil Testing&Inspection Services
ZS
E Post Office Box 190537 - Boise, Idaho 83719
site.consulting.idaho@gmaii.com - 208-440-6276
LTiG� LLC
GEOTECHNICAL RECOMMENDATION REPORT
Goddard Creek Townhomes
2780 West McMillan Road - Meridian, Idaho
PURPOSE AND SCOPE
This report presents the results of a Geotechnical Evaluation performed for a proposed
multi-family residential development to be constructed on a single parcel located on the
north side of West McMillan Road, south side of Selway Rapids Way, and west side of
Goddard Creek Drive in Meridian, Idaho. As per the client supplied Conceptual Plan,
access to the property will be gained from two locations along Selway Rapids Lane.
Parcel information from the Ada County Assessor's website is as follows:
I
I # I Ada Count _#___1 Address Acres
1 R 3182130041 2780 West McMillan Road 4.62
The field investigation included subsurface exploration by means of a rubber tire
mounted backhoe operated by an independent contractor. During excavation of the test
pits, logs were generated, and soil samples were gathered. Soil samples were returned
to our in-house soil laboratory for testing. After the field investigation and laboratory
testing was completed, all available field and laboratory test data was reviewed, the
provided design information was evaluated, and this report was prepared. This report
summarizes our findings and recommendations regarding the geotechnical aspects of
the project.
AUTHORIZATION
Email authorization to proceed with this geotechnical investigation was received on April
15, 2019 from the client. Authorization to proceed and the use of the recommendations
provided herein indicate the client's acceptance of the scope of work, warranty,
limitations, and general conditions provided herein and within the submitted proposal. N
a
Geotechnical Services/soil Testing&Inspection services
SS SITE
E Post Office Box 190537 - Boise, Idaho 83719
ZC/O/NSULTING..
! ! site.consulting.idaho@gmaii.com - 208-440-6276
LLC
RESEARCH & BACKGROUND
GENERAL
There were no homes or outbuildings on the subject property at the time of our field
investigation. Historical aerial photos available on Google Earth reveal no former
building structures or improvements to the property but did reveal the property was
previously covered with rows of trees. It is assumed it was nursery or orchard in the
early 2000. Since then, the property appeared to have been used as pastureland.
FIELD INVESTIGATION
4
Four test pits were advanced to depths of approximately ten to eleven feet below the
existing ground surface. Sloughing soils prevented deeper exploration. During
excavation, samples were recovered from the spoil piles as excavation was performed.
These samples were sealed in plastic bags, labeled, and returned to the laboratory for
evaluation and analysis. In the laboratory, sieve analysis, moisture content, and Liquid
Limit, Plastic Limit and Plasticity Index testing were performed on selected samples.
Tests were performed in general accordance with the cited ASTM test methods. All test
results are included in the Test Pit Logs located in the Appendix.
OBSERVED CONDITIONS
All four test pits were similar with approximately five to six feet of sandy lean clay or
sandy silt that grades to silty sand atop the deeper Whitney Terrace sand and gravel
soils. Gravel and sand were contacted at five to six feet deep in all test pits. These sand
and gravel materials were clean (free draining) by seven feet deep. Groundwater was
encountered in all four both test pits at ten feet deep when excavated on April 13, 2019.
Groundwater has since risen to eight feet deep.
m
Geotechnical Services/Soll Testing&Inspection Services
51 T E Post Office Box 190537 - Boise,Idaho 83719
site.consulting.idaho@gmaii.com - 208-440-6276
ZCQNSULTING, LLC
Since groundwater is critical to civil design, the Idaho Department of Water Resources
website provided the four well logs included in the Appendix. These logs indicate the
static groundwater on the subject site is 10 feet deep. In a well southwest of the subject
property the static water level is reported as six feet deep and in two wells just east of
the property the static water level is 12 & 13 feet deep.
Monitoring wells were installed in all four test pits. Monthly readings will continue until
design is approved for construction.
GROUNDWATER DATE TABLE
TP # #1 #2 #3 #4
Hub Elevation
Casing Height 3.0 3.0 3.0 3.0
Casinq Elevation
Installed 4/13/2019
GW Elevation -10.0 -10.0 -10.0 -10.0
4/23/2019 KA 11 .0 11 .5 11 .5 11 .6
GW Elevation -8.0 -8.5 -8.5 -8.6
5/16/2019 BA 11 .1 11 .3 11.3 11.7
GW Elevation -8.1 1 -8.3 1 -8.3 1 -8.7
d-
v
Geotechnica/Services/Soil Testing&inspection Services
SSITE Post Office Box 190537 - Boise,Idaho 83719
1 site.consulting.idaho@gmail.com - 208-440-6276
COsLT 1T
DESIGN & CONSTRUCTION RECOMMENDATIONS
General Earthwork
All native soils that are free of organic matter and expansive clays can be used as fill
After proper grubbing, the native lean silty sand or sandy silt, soils can be utilized as
structural fill to fill building pads or street section subgrade .
Removal of the majority of the organic materials will require grubbing of 4-6 inches of
surface soils. This is required in all areas to receive structural fill. Deeper excavation
may be required along irrigation ditches and where large trees and soft wet areas are
present. The depth of grubbing is to be confirmed during construction to ensure that
organic materials are properly removed from beneath future pavements and structural
fills. Inspection by the project geotechnical engineer should confirm that all organic
material and demolition debris is removed. Inspection must confirm complete removal of
previously demolished structures including slab on grade floors.
Rutting caused by the contactor using rubber-tired equipment on a wet subgrade can be
i
expected and should be repaired at contractor expense. This information is to be
E supplied to earthwork contractors prior to construction.
Structural fills less than three feet deep are to be compacted to 95 % of the maximum
dry density by ASTM D698, Standard Proctor. For deeper fills, such as ditch backfill,
basement backfill, and fill intended to contain rerouted irrigation canals, ditches, or
storm water runoff, fill materials are to be compacted to 100 % of the Standard Proctor
maximum dry density. If structural fill is to be placed on the building pads, the fill is to
E` extend laterally outside foundations a distance equal to the depth of structural fill.
Compaction testing of all structural fill is required. Visual inspection is also required to
confirm stability and the lack of soft, deflecting, or rutting areas. Fill can pass
compaction tests and still be rejected if it fails visual inspection.
Ln
a
Geotechnica/Services/Soil Testing&Inspection Serv/ces
SITE Post Office Box 190537 - Boise, Idaho 83719
site.consulting.idaho@gmail.com - 208-440-6276
ZCC)I :SULTING, LLC
Excavations
Shallow excavations and trenches that do not exceed four feet in depth may be
constructed with side slopes approaching vertical. The ability of soils to maintain a
vertical or near vertical slope over any extended period can be quite variable.
This information is provided for planning purposes. It is our opinion that maintaining safe
working conditions is the responsibility of the contractor. Jobsite conditions such as soil
moisture content, weather condition, earth movements and equipment type and
operation can all affect slope stability. All excavations should be sloped or braced as
required by applicable local, state, and federal requirements.
r
Pavement Section
It is assumed that an R-Value of greater than R=20, would be obtained if the native
surface soils were tested. Pavement sections have been calculated based upon an R-
Value of R=20 and Traffic Index of TI=6. The results are shown in the table below.
Materials meeting the requirements of ISPWC & /or ACHD are required for all work
within this project. For this project, it is recommended that the subgrade be inspected
(proof-rolled) prior to the placement of subbase materials.
HMA 2.5"
%"Base 4.0"
Subbase 10.0"
Subgrade Inspected
Storm Water
Free draining sand and gravel material were present at seven feet deep in all test pits.
Based upon free draining conditions, a percolation rate of P=8 in/hr. is to be assumed
for design of facilities that extend seven feet below the existing ground surface. Over
excavation and backfilling with free draining materials may be required. Confirmation of
perc rate and clearance above groundwater at the time of construction by field testing is
recommended.
v
aA
cL
a
Geotechnical Services/Soil Testing A Inspection Services
SITE Post Office Box 190537 - Boise,Idaho 83719
site.consulting.idaho@gmaii.com - 208440-6276
CONSULTING, LLC
Building Foundation System
The proposed multi-family residential structures may be supported on conventional,
continuous, and isolated pad foundations founded upon the native soils or upon
structural fill extending to these soils. Based upon proper placement and compaction of
structural fill, bearing pressures of up to 1500 psf are allowed for foundations founded
on the native soils or upon properly placed and compacted structural fill. Either
crawlspaces or slab on grade floors are acceptable but slab on grade floors will
eliminate the possibility of water accumulating in crawlspaces. Basements are not
allowed without a lot/ building specific geotechnical evaluation.
If clay soil, wet soil, or deflecting soil is present at the foundation support elevation a
geotechnical engineer should be retained for site specific recommendations. Foundation
drains are required within this development. Roof runoff is not to route through
foundation drains. Foundation embedment depth is to be at least 24 inches below
outside adjacent grade. Foundations that are outside crawlspaces are to be sealed /
waterproofed with brush or spray on foundation mastic.
Slab on Grade Concrete
Care must be taken so that all excavations below both interior and exterior slab on
grade concrete are properly backfilled in accordance with the structural fill
recommendations. Trenches and wall backfill areas are to be filled in lifts and benched
each lift so that fill is not placed against a vertical soil face greater than three feet tall.
Testing is to confirm that compaction has been achieved. Areas of excessive yielding
should be excavated and backfilled with structural fill. Any fill used to increase the
elevation of slab on grade concrete should meet the requirement for structural fill.
Concrete pavements should be placed atop a mat of at least six inches of granular
structural fill materials. Mat material should all pass a 3/4-inch sieve and should contain
less than seven percent passing the # 200 sieve. The mat shall be compacted to the
requirement for structural fill.
U0
a
Geotechnical Services/Soil Testing&Inspection Services
SITE Post Office Box 190537 - Boise,Idaho 83719
site.consulting.idaho@gmaiLcom - 208-440-6276
CONSULTING, LLC
Underground Utilities
It is not anticipated that large excavators or small backhoes will experience any
difficulties excavating the onsite materials encountered on the property. No bedrock
formation was encountered on the subject property. Well logs from IDWR indicate the
high static water level may be as high as six feet below the existing ground surface.
Inspection & Testing
A qualified engineer or his representative should monitor fill placement to ensure the
work is performed in accordance with these recommendations. For mass filling, field
nuclear moisture - density testing shall be performed on each lift of compacted fill, one
each filled residential lot or building pad. Trench backfill and right of ways are to be
tested to ACHD and / or ISPWC requirements. It is noted that structural fill can pass
compaction tests and still be unacceptable if pumping, rutting, or deflecting under
vehicle or foot traffic.
Contractor Inspections
This report has been prepared with the intent to provide specific design information to
the developer and the civil engineering consultant. It is not intended to act as any
contractors "Due Diligence" or subsurface inspection prior to estimating construction
costs or actual construction. Contractors may use the onsite monitoring wells to assess
the groundwater prior to proposing on or beginning construction. Wells are to be
protected during construction and can only be removed with permission from the client
and SITE.
General Comments
After the plans and specifications for construction are completed, it is recommended
that this consultant be provided the opportunity to review the final design and
specifications. This review will confirm that the earthwork recommendations have been
properly interpreted and implemented. At that time, it may be necessary to submit 00
a
Geotechnical Services/soil Testing&Inspection Services
SITE Post Office Box 190537 - Boise,Idaho 83719
site.consulting.idaho@gmail.com - 208-440-6276
CONSULTING, LLC
supplementary recommendations. This review is a part of this service and will not result
in additional invoicing unless additional research and recommendations are needed.
Testing and inspection services are recommended herein. Proper quality control during
construction is required to confirm materials and methods and thereby obtain a
desirable finished product. Monitoring and testing should also be performed to verify
suitability of materials used for structural fills and to confirm proper demolition, subgrade
grubbing, subgrade stability, and proper placement and compaction of fills. Any
deviations from the herein described subsurface conditions must be brought to the
attention of this consultant.
This report has been prepared for the exclusive use of the client and their retained
design consultants. Findings and recommendations within this report are for specific
application to the proposed construction described herein and apply only to the property
identified. Client may duplicate this report as needed or additional copies will be
f provided upon proper client authorization.
i
4
I
i
Appendix Follows
E
I'
II
i
0)
n)
on
a
Qeotechnical Services/Soil Testing&Inspection Services
SITE Post Office Box 190537 - Boise,Idaho 83719
site.consulting.idaho@gmaii.com - 208-440-6276
C NSU Lei , LLC
APPENDIX
Preliminary Plat
Aerial Photo
Test Pit Logs (4)
Soil Log Legend
Abbreviations and Acronyms
Adjacent Well Logs (4)
f
0
v
a
Geotechnicai Services/Soil Testing&inspection Services
SITE Post Office Box 190537 - Boise,Idaho 83719
site.consulting.idaho@gmail.com - 208-440-6276
CONSULTING, LLC
PRELIMINARY PLAT
YICSY 1ASAR CRttK ORAE
�� � 'r.�l �� f�► lff
'---�•-M f1+3 U lyq yf i'�N
rQ
- � wlYr '4Sfr PPl
�� ar
I au v ri y
nui lfa -
1 icy Lry4 c ni�y rti• I�O1 Np1Y lli�
'- _..off_. -' � � " _ .r.fJ✓ f�P� h s
BEST M_i4R CRCEK LOOP _
ill-- - •' / RY'
_ r
� by fi
l f1
19
1 ,�-
f..
Cif ffl�
er ,a qN
Y.
r
fro
%MT YCNUM RCaD -
Supplied by client
m
Geotechnical Services/Soil Testing&Inspection Services
SITE Post Office Box 190537 - Boise, Idaho 83719
site.consulting.idaho@gmaii.com - 208-440-6276
CONSULTING, LLC
AERIAL PHOTO
: . .
P-�
P-�
``llt!l1C4if ° r
2780 West McMillan Road - Meridian, Idaho
from landprodata.com
N
r-i
v
en
ro
a
Geotechnicel Services/Soil Testing&inspection Services
S[T E Post Office Box 190537 - Boise,Idaho 83719
1 site.consulting.idaho@gmail.com - 208-440.6276
05LTIia, LLc
TEST PIT LOG
Test Pit: TP-1 File#: 19213-A
Client: Leavitt&Associates Date Excavated: 04/18/19
Project: Goddard Creek Excavated By: Wood Brothers
Location: NW Corner Logged By: J. Meusch, PM -SITE
DEPTH SOILS DESCRIPTION
feet 1.0" 1 314" 1 1/2" 1 3/8" 1 #4 #10 #40 #100 I #200 %M LL PI
0.0-1.0 Brown,Moist,Firm,Sand,Clay,Silt
With Root Zone/Organic Layer 6-8"
1.0-3.0 Brown/Tan,Moist Firm,Sandy,Silt ML
2.0 100 99 88 65 53.8 20.0 NP NP
3.0-5.0 Red Moist Firm Silty,Sand SM
4.0 100 97 88 80 50 27 18.8 13.3 NP NP
5.0-10.0 Red Moist Firm Sand Gravel Cobble
Bottom of Excavation
10.0 Ground Water Encountered @ 10.0
Monitoring Well Installed
i
TEST PIT LOG
Test Pit: TP-2 File#: 19213-A
Client: Leavitt&Associates Date Excavated: 04/18/19
Project: Goddard Creek Excavated By: Wood Brothers
Location: SW Corner Logged By: J.Meusch, PM -SITE
DEPTH SOILS DESCRIPTION
feet 1.0" 3/4" 1/2" -3/8" #4 #10 #40 #100 #200 %M LL PI
0.0-1.0 Brown,Moist,Firm,Sand,Clay,Silt
With Root Zone/Organic Layer 6.8"
1.0-6.0 Brown/Tan Moist,Firm Sand Gravel Slit
6.0-10.0 Red Moist Firm Sand Gravel Cobble
Bottom of Excavation
10.0 Ground Water Encountered @ 10.0
Monitoring Well installed
I
S
m
M
a
Geotechn/cal Services/Soil Testing&Inspection Services
Post Office Box 190537 - Boise,Idaho 83719
site.consulting.idaho@gmail.com - 208-440-6276
ZCON2SULTING.. CLC
TEST PIT LOG
Test Pit: TP-3 File#: 19213-A
Client: Leavitt&Associates Date Excavated: 04/18/19
Project: Goddard Creek Excavated By: Wood Brothers
Location: SE Corner Logged By: J. Meusch, PM -SITE
DEPTH SOILS DESCRIPTION
feet 1'.0" 314" 1 1/2" 1 3/8" 1 #4 #10 1 #40 ' #100 #200 %M ` LL
0.0-1.0 Brown,Moist,Firm,Sand,Clay,Silt
With Root Zone/Organic Layer 6-8"
1.0-4.0 Brown/Red,Moist,Firm,Sand,Gravel Silt
4.0-6.0 Brown/Tan Moist Firm Cemented,Sand,Clay,Silt
s
6.0-10.0 Brown/Red Moist Firm Sand Gravel Cobble
Bottom of Excavation
10.0 Ground Water Encountered @ 10.0
Monitoring Well Installed
TEST PIT LOG
Test Pit: TP-4 File#: 19213-A
Client: Leavitt&Associates Date Excavated: 04/18/19
Project: Goddard Creek Excavated By: Wood Brothers
Location: NE Corner Logged By: J.Meusch, PM -SITE
DEPTH SOILS DESCRIPTION
feet 1.0" 1 3/4" 1 1/2" 1 3/8" 1 #4 #10 #40 #100 #200 )1 %M I LL
0.0-1.0 Brown,Moist,Firm,Sand,Clay,Silt
With Root Zone/Organic Layer 6-8"
1.0-3.0 Brown Moist,Firm Sand Lean Clay CL
2.0 100 99 94 86 77.6 24.6 33 13
3.0-5.0 Brown/Tan Moist Firm SII!X,SandISM)
4.0 1 1 100 89 66 45 32.9 22.2 NP NP
5.0-10.0 Brown/Red Moist Firm Sand Gravel,Cobble
Bottom of Excavation
10.0 Ground Water Encountered @ 10.0
Monitoring Well installed
r-I
v
on
co
a
Geotechnical Services/Soil Testing&inspection Services
SITE Post Office Box 190537 - Boise,Idaho 83719
G site.consulting.idaho@gmaii.com - 208-440-6276
CONSULTING, LLC
SOIL LOG LEGEND
UNIFIED SOIL CLASSIFICATION SYSTEM
(ASTM STANDARD TEST METHOD D 2487 FOR CLASSIFICATION OF SOIL FOR ENGINEERING PURPOSES
MAJOR DIVISIONS TYPICAL
DESCRIPTIONS
COARSE GRAVEL& <5%-#200 GW ell- raded gravel,gravel-sand mixture little or no fines.
GRAINED GRAVELLY GP Poorly graded gravel,gravel sand mixture,little or no
SOILS SOILS fines
50%-#200 50%-#4 5-12%4200 GM lilty
lty gravel,gravel-sand-silt mixtures
12%-#200 GC ayey gravel,gravel-sand-clay mixtures
i
AND&SANDY <5%-#200 SWell-graded sand,gravelly sand,little or no fines.
OILS SP oorly graded sand,gravelly sand,little or no fines
50%-#4
12%-#200 SM sand,sand-silt mixtures
SC Clayey sand,sand-clay mixtures
FINE SILTS AND INORGANIC ML Inorganic silt and very fine sand,rock flour,silty or
GRAINED CLAYS la a fine sand or clayey silt with slight plasticity
SOILS LL<50% CL Lean clay-low to medium plasticity,gravelly clay,sandy
50%-#200 clay,silty clay
ORGANIC OL Organic silt and organic silty clay of low plasticity
SILTS AND INORGANIC MH Elastic silt,micaceous or diatomaceous fine sand or silty
CLAYS soil.
LL>50% CH Fat cla -high Elasticity
ORGANIC OH rganic clay-mod.or high plasticity:organic silt
HIGHLY ORGANIC SOILS I PT jPeat,humus,swamp soil with high or anic content
ABBREVIATIONS AND ACRONYMS
STM American Society for Testing and Materials
IBC International Building Code
ISPWC Idaho Standard for Public Works Construction
IDWR Idaho Department of Water Resources
NP Non-Plastic
PCC Portland Cement Concrete
P Test Pit
USCS Unified Soil Classification System
pcf Pounds per Cubic Foot
psf Pounds per Square Foot
sf Tons per Square Foot
psf/f jPounds per Square Foot/ Foot
Ln
CU
C
Geotechnical Services/Soll Testing&Inspection Services
S1 T E Post Office Box 190537 - Boise, Idaho 83719
site.consulting.idaho@gmaii.com - 208-"0-6276
CC►NSULTING, LLC
Adjacent Well Logs
Form 23g-� STATE OF IDAHO USE TYPEWRITER OR
9/02. DEPARTMENT OF WATER RESOURCES OALLPOIN7 PEN
WELL DRILLER'S REPORT
State Im rMites that thD report be filed with the Okector.Department of Water Resources
within 30 days alter the c«npletfon or abandonment of the well.
t.WELL OWNER 7.WATER LEVEL
Name _ � 5uttc wsiw level feet below laml s«lace. —
/Q Flowing? U Ya o
Add— W/ v(/ Artedanclos+d I-prM
� Ds.i.
/1'�a2A G i Conudld M: ❑Vane 0 cep ❑Plug
Owner'. No. — Trmp.rawra oF. OuditV
dle•ia arlewnwlerne[raluH rsnel Mrw.
S 2.NATU F WORK S.WELL TEST DATA
OF ew wall Cl Deepened ❑Replacement ❑Pmnp ❑eeliw ❑Air O other
C aay ❑Abandoned(describe eberulcm ent Woe duree such as Oft" dIJA Lnw1 t/owa Punpd
Y.i�3lL� notarial.,plug geprh0,ate.In Wholegic log) 0
3.PROPOSED USE
B'6omrtic ❑Irriytlon ❑Test O Muddpal 9.LITHOLOGIC LOG 103595
p Industrial 0 5tock ❑Waste Disposal nr Injeconn Bore Do ih Warta
ClOther (rpecily tyi-I Diarrr.From To MatwW Y No
4.METHOD DRILLED S
[I RotW CYAir ❑Hydraulic ❑Rave try 36
0 cable ❑Dug ❑Other
S.WELL CONSTRUCTION
Caring idraduN:11 St.6 0 Concrete OOthr
TMdprr mamsrr F To _
Ineha_(F_ IKhes. natfrt
_ inches h hos _fast_fest
_ In her Inches Mt__fart
Inchw _Inches V fast__fast ~
W w eating drive shoe ured? D-ra 0 Now Dap@nmart of Ws'u eswrra
Was.pecker or sot used? 0 Yes B'No - ytomm et Iflq
Derf..led? ❑Yes W
How perloratd? ❑Factory 0 KnHa 0 Torch
Sire of part«atfn_ tithestM Inches
Neraer From TO
perforations Zees__.(atii yyC
perforations fee ( E
part«atlom last — �
wen sorasn innand? a Yn B�FIo
MrallseWrer'srtanrs
TVpa Model No. —�
Diameter_Blest elze_Set from_last to Iset
Dfamster_Slot :_ am,fast to_last
G,Wel Picked? Oyes B?lo OSluof greed
Placed from fast to fast
Su,feea sW dpth_Mau' us�d In aesd: O Ce ndelt lFwl
0 B.monha Iingdry O
Sealing Wmadur.used: 0 SI«ry pit O Tamp•turfaeeesaing
❑ n.to rW depth
Ahdrpd of pining casing:O Threaded aided❑S.W.' - part
Wald
❑Cemntd behyasrr strau
Dacr'ibe access port _ _ 10.
Work strict Inishd
S.LOCATION OF WELL it. DRILLERS CERTIFICATION �L
Sketch map location must agree with warI?ten locedon. I/W.certify that ell minimum well c«ntruction strdrds were
N ■���1n�� complied with m the time the rig war rwnwsd•
SutMivis7on 1
__ __ l-� r•sLL/ Firm Name ��c� f6>atiF{rm No.�
W E JUN 22�g1— Addreae �£— . ✓✓✓�bau 1�
.... ..... 0bek No.
Slprr d by(Firm Offtciel)
S k... and r
C-Irty (Operator)
USE ADDITIONAL WEFTS IF NECESSARY—FORWARD THE WHITE COPY TO THE DEPARTMENT
W
tt
t6
n.
Geotechn/cal Services/Sol/Testing&Inspection Services
SITE Post Office Box 190537 - Boise, Idaho 83719
site.consulting.idaho@gmail.com - 208-440-6276
CONSULTING, LLC
..0,Idaho
Sfi Jf,
Department Of Water Resources u��
State law r.a,iro mat W E�,�.�R44 with the Direct.,LLER'S RDEPO+R of WOW 3.ewate$.it �lo15 left
Mvt Htv the eomprtlon or abrdomm~nt olof tfvwtl'. Pa @ ra
1.WELL OW/NEERR 7.WATER LEVEL 6 t
Nont__ Static wet<r Iwd_/0_fan below l".Macs
SL):Q�L� --FltYipp Flowing) O Vas @rNo O.P.M.
PcTaP��(Lz Adar,s A 140 (y Ian/y/L AN Tempernura_F. Gu`nty
Artnian domd-in Wawn (>•al M
owner's Pwmit N0. li 3 " 54 I _ Controlled by ❑vwa ❑Cap ❑PI.3
2 NATURE OF WORK 8.WELL TEST DATA g a/nl°l6�
�iw welt ❑Datpaned ❑Reprctment ❑Pump O -if.
❑Other Al
DbdwerDJAI. Drew Dew=— w��J
❑AbarAond Idecrib.method of eWrMonirgl
3.PROPOSED USE c.
❑Daa.tlit M'VH@Mim O- ❑00-bl"db h* A LITHOLOOIC LOG
Death,❑Neccyd O lneaehid ❑3bd ❑wnr DItpWN OfD- Frew T. WrY V.I Ne
ktl•cro.
4.METHOD DRILLED
�� o G? v
f4'r'+ble O Roiory ❑Dry ❑Other / 6 ' LAM JfryF'C S 4
/ S 6
S.WELL fpNSTRUCTION / i`1
/ c v
Diametn of hole irrltee Total depth 15 fear 1 6A A.
C lq rhedulr. 0-j" ❑Concrete It O G.
Tin Arr 01—' frwn Ta (2 Q _ h f^
0.�0 inch..II.inch.t__L feet J1.P-I..r
ham, feet _Irt
--mehet {r lees leer _feet
kche'a�IrchR 1Nt __lest
inch, 'nhaa fen _lest
m Nye azy drive rw.-W 7 6'`, 13 No
Wet•packr w sW usd7 O Y. M-WO
0 NO
How wfatsted) t�twy ❑Knife ❑Torch
size of perlwn{on ithhasby-9—inthe
Nwryw faew To
perforations 10 fen fart
(./_t 4 perfornbna 6,17_feet if fe.t
Perforations fart fen
1';d1 acres,katallad) ❑Var O No
hWtufacurra a name
Type Model No.
.1-1.—5t.,tic.—Set— fan to—feet
u—ter_Slot Nze_Set from__fan to�_,� fart
Gtnol pecked? eryw ❑No 511a of Wwd t
3� •—••
Placed from /a feet to
Srleae era death Mehow na4 r Net ♦ Plea
O PdarAS allq Cl wall MR.ar
S.+q p—el re-d ❑f"14 11 SOON aartrte,+•3
0 umbers is ad dodr
10.
S.LOCATION OF WELL Work nytedl,/s ems, flnieMd y�/S 77
Sk..h map 1—t{.n mwt agree with written i.catlns
N
j IL R3RE1fA0 OW WEI Firer Na 314
flab&.-tkna
w r a Aataw sTln. .aai. twrl��.M�L—rZl
,,,1,,. __!_. ale—
La la__EttA Ir
j sew a(rem offlHr) F
ad
county A A A �► ) .f.n�_ /�
- E><.G�'K Se- G .T. L_NfR R. UW
USE ADDITIONAL SHEETS IF NECUURV FORWARD THE WHITE WX TOTHE DEPARTMENT
I
OD
r6
a.
Geoteehnical Services/Soil Testing 81 Inspection Services
SITE Post Office Box 190537 - Boise,Idaho 83719
site.consulting.idaho@gmail.com - 208-440-6276
CONSULTING, LLC
rr�L%L-IVED
AUG ?4 1999 odKeuseady
Form 238.7 IDAHO DEPARTMENT O�R RESOUItC-;S Inspected by --
T%p_Rg0__ ----
39u9r WELL DRILLF. I` If aaas 1/4_I/4_—_1/4
b3 °l
1.DRILLING PERMIT NO. 9--o 0.578-000 11.WELL TESTS:
Other IDWR No.D0009904 —— --- Pnml Railer Air Fbwin Artesian
[b 2.OWNER: 5'
THe Name Kelly Fuller
Address 2350 W McMillan Rd
� —City Meridian State ID Zip 83647 W&W Tamp, lie loin hole tmmp.
3.LOCATION OF WELL by legal description: Wale Quality tat or mumeds:
Skach map location ant sgtm with written location Depth rust Water FilcouNerrd 10'
N 1t LrMOLOGIC LOU.(D r }Aj-qF abandonment)
'I'wp.M1 North ® or South ❑ Water
w E Rge. East ❑ or West N Oaa Frvu To Rrm■rlocl.lt6.l.as,W.1—Q-.ltyt:Te-p. Y N
Sec. 26 ��/4 SSW�114 SSE1/4 IU" 0' 2' fillrmtmal
l0" 2'In I 4' brown t soil
Gov't lot County Ada IV; 4' 7- b mm s clay
S 101 6' 10' brown sand k gm'd
Lat: Long: to- to, Ig' hman sud dt gravel
Address RWell Site 2350 W McMllan 6. P120'
man s pave
City Meridian 6 30' man sandy ny
6 2 mesa c ey
Lt. Iilk. Sub.Name 6" 88' bmwn sand%/clay strips
0 roanc sy% mps
4.USE: " 130 brown Sand
N Domestic ❑Municipal ❑Monitor ❑loigation I 132' brown day
❑Thermal ❑Injection ❑Other
S.TYPE OF WORK check all that apply (Raplacemmt etc.)
0 New Well❑Modify❑Abandonment❑Other
6.DRILL METHOD
N Air Rotary❑Cable❑Mud Rotary❑Other
_ FtEeEIVEB
7.SEALING PROCEDURES
E 'I. : PACK AMOUNI I ME1I10
hwe'u] Frorn To Sect Q
Rwnis
llentonile A' IR, is
WEsTEM OENON
Wes drive sboa used?®Y❑N Slap Depth(s)
was drive shoe seal tested?❑Y H N How?
'4G
- C-8 him Wddcd Thredal
❑ ❑ ❑ ❑ r..
Length of Readpipc 12' Length of Tailpipe Completed Depth: 132 OMeasurablo)
9.PERFORATIONS/SCREENS Dale:Started Cmpletd7/23/99
❑ Perforatiuns Method ll"sh m 13. )RILLEWS CERTIFICATION
t*Saays Sacco Type UWe certify that ell minimum wv:0 comouKtiot standards were
Frwr To sa s' ba 1 1)ia 1 c I. ca"+Plied with at the time the rig%as remorod.
120' 130' .U16 5" StS ❑ ❑ SOS Weud.:Illnat4 PumpFirm No.212
Firm Nape- Co-
Firm ODLcial
Dale
10.STATIC WATER LEVEL OR ARTESIAN Supmisor or Operator Date
PRESSURE: (Sym mce it 80paata)
110 below grand Artesian Preserve 16
Depth flow enuarotcred 0. Describe access port or cortns4 Dal.:Dal1N99 Time 5:10 PM
deices:
00
l—1
tD
hU
to
d
Geotechnicel Services/Soil Test/ng&Inspection Services
SITE Post Office Box 190537 - Boise, Idaho 83719
site.consulting.idaho@gmail.com - 208-440-6276
CONSULTING, LLC
19-7 01 S a 70)3 3 S Ottioc Use Only
rorm 238-7 IDAHO DEPARNMENT OF WATER RESOURCES nsptxicdby,__^Sao-
3195L96 WELL DRILLER'S REPORT p v4_�v4_ee ll4
ILL Loag
1,DRILLING PERMIT NO. 11.WELL TESTS:
Other IDWR No.D0019418 ——— rTnt!ir;]
m i
2.OWNER:
Name Randy Calkins
Address P O Box 99
City Meridian Slate ID Zip 83680 Water Temp. Bottom bole temp.
i 3.LOCATION OF WELL by legal deseriptlon: Water Quality test Of comments;
Sketch Trust,locution muss ag-c with wriunt loadim Depth first Ware,Enaxmtcred 11
N 12.LITHOLOGIC LOG:(Describe rep■in or abudo■mr■1)
Twp.4 North or South ❑ w■ter(
p1
W E Rge. I East [] or West Bore hum l'a Rroarks:I3lYoloey,Water(2p1lly!('reop. N
Sec. 26 SE 1/4 SW 1/4 SE 1/4
,M-- -tom rm-_, 12 0 2 BROWNTOPSOII.
E' 12 2 9 DROWN CLAY
Gov't la County ADA 12 9 11 BROWN SAND&GRAVEL
Lat: Long__ 10 11 19 BROWN SAND&GRAVEL
F.
Address of Well Site 2350 McM1LLAN 6 19 28 BROWN SAND&GRAVEL
City MERIDIAN 6 28 40 BROWNCI.AY HA
n amee ro alad�— 40 ROWNSA D
Lt. Blk. Sub.Nano 6 6 68 BRO CLAY
6 68 75 BROWN SAND (DIRTY)
4.USE: 6 7 BO EBSTICKZYCAY
® Domestic ❑Municipal ❑ Maribor ❑ Irrigttlon 6 80 90 TY)
❑ Thermal [I Injection ❑Odwr 6 90 95
5.TYPE OF WORK click all that apply (Repluccmenl cle.) 6 95 112 IRTY)
®New Well❑Modify❑AMndonmem❑O(her 6 112 125 Y
6.DRILL METHOD 6 5 140 BROWN&WHITE SAND
0 Air Rotary❑(able❑Mud Rotary❑Other
7.SEALING PROCEDURES
7R PAC AMOUNIMETHOD
ALteriil From To Sarl:sar
Pauodo
Was drive shoe used?®Y ❑N Shoe Ikplh(s)120 _
Was drive shoe seal tested?❑ Y®N How?
asna 1.vrn WaWad Tlreadd
❑ ❑ ❑ ❑
Lengthnt'lleadpipc12'low LeagthofTailpipe Completed Depth' Izy (Measurable)
9.PERFORATIONS/SCREF.NS Corn letol 12
❑ Perforations Method Nate:StangI n)tt1(J0�
N Screens Screen Type lelescooina 13.DRILLER'S CERTIFICATION
VWe certify that all minimum well construction stmdards`vac
From Tu Ia S- —W Uisrod ALt (' Lmrr canplied with at the time the rig was removed
126 136 .016 5' STSf
O d Firm Nam' w uA'Ilion k P�myn Co _ Fimt No.21.2__
i it
❑ ❑ �, z ,�s
F'Irm ORicitd�- r+'�`— Date
10.STATIC WATER LEVEL OR ARTESIAN
PRESSURE: Supervisor tr Opentor Dole
ILL.jxImv ground Artesian Pressure lb (Sign o■ce irFirm Otrtrisl k oper"W)
Depth flow encountered_ R. Describe acros"or oontrO
devices: Dste:212IN2 Ti=352 PM
NOTHING FOLLOWS