HomeMy WebLinkAboutFire Dept CommentsMeridian Fire Department Joseph Silva Depu~/Chief Meridian Fire Department 540 E. Franklin Rd. Meridian, Id 83642 (208) 888-1234 Fax (208) 895~0390 March 18, 2002 TO: Honorable Mayor and City Council ~ FROM: Joseph Silva, Deputy Ch/el, Fire Prevcntiony SUBJECT: Request to Amend Silverstone Developrne~at Agreement The following are the requirements to provide minimum fire protection: 1. Provide a fire.flow as required by the 1997 Uuiform Fire Code Appendix III-A- Please show all prox/mity hydrants within 500' of the project on the resubm/tted plat. 2. All internal & external roads shall have a 28' inside radius and 48' outside radius. The proposed buildings, uses and storage of flammable liquids shall comply with the 1997 Uniform Fire Code. 4. Acceptance of water supply for fire protection is contingent upon acceptance of the water system by the City of Meridian for water quality. 5. Final approval of fire hydrant locations shall by the Fire Department. 6. Thc roadways shall built to Ada County Highway Standards and arc a minimum of 37' wide. UFC 902.2.1 Sincerely, Joseph Silva Deputy Fire Chief Fire Prevention RECEIVED MAR 1 2002 City Of Meridian City Clerk Office Test Smoke Detectors Monthly