HomeMy WebLinkAbout2685 W Chinden Blvd Mike Myers( >
E IDIAN�--
October 23, 2013
Mr. Mike Myers
2685 W. Chinden Blvd.
Meridian, Idaho 83642
Mayor Tammy de Weerd
City Council Members:
Keith Bird Joe Borton
Luke Cavener Genesis Milam
Charlie Rountree David Zaremba
Re: Municipal Sanitary Sewer and Water Service Availability to Parcel #50426212600
Dear Mr. Myers,
This letter is a follow up to our phone conversation regarding feasibility and timing of municipal sanitary
sewer and water service availability to your parcel referenced above. As we discussed, a new phase of
the Irvine Subdivision (shown on the attached map as "Future Phase") will be extending sanitary sewer
and water mainlines to the end of the stub street along your west boundary. Unfortunately though, the
sewer in this immediate vicinity all flows to the Silver Leaf Lift Station (shown on the attached map as
"Lift Station"). When this Lift Station was designed its design service area did not include your parcel. I
have included a copy of the approved calculations for the lift station for your reference. We also
discussed that with the development of the Bainbridge Subdivision to the west of Ten Mile Road, they
will be constructing the trunk sewer that will eventually negate the need for the Silver Leaf lift Station.
The progression of this trunk sewer is subject to the developer's schedule, and therefore I can't give you
a timeframe for when that will happen.
All that being said, it may be possible for your parcel to obtain service to the sanitary sewer system,
however you would be responsible to provide an engineering analysis demonstrating the feasibility of
upgrading the lift station, as well as the full cost of those upgrades.
As for the domestic water supply, your parcel will be served from the existing 8 -inch water main in the
stub street along your east boundary, and the future 8 -inch water main in the stub street along the west
boundary.
Please let me know if you should have
Sincerel
ruce Frec eton, Development Service Manager
Cc Mike Reno, Central District Health Department
alley Engonee ng,Inc.
CIVIL ENGINEERINGIPLANNINGICADD
PRESSURE SEWER LIFT STATION
CALCULATIONS
e
State 0MaboaNpartmeneo6`IEaevecrsaerezertc�IB o9lsg
norm Regional Office
FLMS & SP ECMO j °d0NS M' VMS°
"bhm dens e7a &Of EPCeilications have eta aeviewed for ceurqtlwee
'All, Deparaartent'of Environmental Qpailiry reales. 'fl7ais review dDes not
relieve the Owner, engineer, or the contractor of the respeasibifeay to
design or construct these raei.itles in compliance with all-uttmt appli=
cable federal, state and local laws orales, tegnlations; or oiiinances,
Plans andtor spm®fredtions must b a�m6tliaw icor rev! o�
'a ' nodcta0* wi ina to Gro oa vel da3e<
ateY[EV8'Aa9�' g,,,,.„„V6St Vii^,
km appmamP �a�iatms�
PROJECT NO 024046
DATE: July 6 2005 Revised
OWNER:
,Toler A. Laude, Sr.; President
Liberty Development, Inc.
114 E. Idaho St., Suite 230
Meridian, ID 83642
1500 E. Iron Eagle Drive o Eagle, Idaho 83616 * Tel,: 208-938-0013 o Fax_ 208-938-0516
v m-baileyengineers.com
SILVERLEAF SUBDIVISION
SEWER LIFT STATION CALCULATIONS
vo
Single Family Lot From Silverleaf Subdivision
L�,200 Ingle Family Lots From Proposed Future Subdivisions
ture Elementary School - 660 Students
* Mike Meyers Property Not Included In These Calculations
Assume 250 gpd/house
Assume 23 gpd/student
250 gpolhouse * 143 = 35,750 gpd
200 gpd/house * 200 = 50;000 gpd
660 Students * 23 gpd = 15,180 gpd
Daily Average Flow = 100,930 gpd
Assume 2.5 people per lot
Population = (2._5 * 343) + 660 Students - 1,518 people
= 808 Single family residents
Peak Hourly Flow Factor = 3.80 Front Fig. 1 — 10 STATE STANDARDS
Peak Hourly Flow = 100,930 * 3.80 = 383,534 gpd
383,534 gpd * Id/24 hr* 1 hr/60 rain = 266 qpm
Use 266 pgm = 0.59 cfs
Average Daily Flow 100,930 gpd * Id/24• hr * 1 hr/60 min = 70.09 gpm
WET WELL SIZE:
Required Volume_ V = t * Q/4
t = pump cycle time (on/on)
minimum cycle time is 6. min
Pumps work alternately, therefore use 6 min
Assume Min. Velocity = 2ft/s
Pump Capacity = 266 gpm = 0.59 cfs
Volume = Required storage volume, gallons
= 6.0 min * 266 gpm/4 = 399 gal
WET WELL VOLUME
Use 8 It diameter well
Storage = 375.8 gal/ft of depth .
A=3.14(4)"2' = 50.24 cf
STORAGE/FT OF WET WELL
_ (50.24 cf)"7.4805 GAL/1 cf = 375.82 gal/ft
SEWER PUMP STATION DESIGN:
Approximate Working Depth (AWD)
AWD = Required Storage Volume I Wet Well Volume Per Foot
AWD 399 gal / 375.8ga1/ft = 1,06 ft
Use 2.0 ft (Plus Emergency Storage Capacity)
FILLING TIME (T)
T = Storage Volume / AGPM
T = 375.8 gal/ft 170.09 gal/min = 5.36 min/ft
PRESSURE SEWER PIPE SIZE:
Assume 6" PVC Pipe
V =Q/A
V= 0.59cfs/3.14 = r"2
V=3.00 ftfs OK
PUMP HORSEPOWER:
Minimum Elevation of Wet Well Bottom
= Inlet Pipe Invert Elev. - Working Depth - Mm Submergence
= 2541:92 -3.0 -2.50
= 2536.42 ft
ELEVATION HEAD:
H = Elevation at PS High Point- Elevation of Wet Well Invert
= 2552.48 ft — 2525.5 ft
= 26.98 ft
EQUIVALENT LENGTH OF PRESSURE SEWER PIPE
Length of Pressure Sewer Pipe = 977 ft
Length of Lift Station Piping = 21 ft
Horizontal Bends
4 - 90 degree 4 = 10 = 40 ft
1 — Thru Run Tee = 8.3 ft
1 — 4" Check Valve = 31 If
2 — 4" Gate Valves = 2.9 ft
TOTAL =1080 ft
SEWER PUMP STATION DESIGN:
Friction Hea.dloss
G--120 max
(1 00/c) "1.852 = 0.7134
f = 0.2083 * (100/0 "1.852 � QA1 .852/dA4.8655
0.2083 + (100/c) A1,852 i 266^1.852/6"4.8655
= 0.75 ft per 100 ft of pipe
HL = 0.75 ` Total Equivalent pipe length/ 100 ft
=0.75+10801100 = 8J3 ft
TOTAL DYNAMIC HEAD (TDH):
(Total System Head) + (Elevation Head + Friction Head Loss)
TDH =26.98 + 8.13
TDH = 35:1 ft
Brake Horsepower (Hp)
Hp = Q '-TDH/ 3960 * 0.55
Hp = 266 * 35.1 13960 * 0.55
Hp = 4.28 Hp Use 5 Hp Pump
Emergency Storage:
15 min x 0.59 cfs x 60s/min = 265.5 cf
265.5 cf r 7.48 gal/ 1 cf = 1,986.00 gal
1,986.0 gal/375.8 gal/ft= 5.28 ft
SEVt/ER PUMP STATION INFORMATION:
WET W ELL:
Rim Elevation
Gravity Sewer Inlet Elev
Emergency Storage
Highwater Alarm Elev.
Second Pump On Elev.
Pump On Elev.
Pump Off Elev.
Floor Elevation
Height
GRAVITY SEWER:
Inlet Pipe Diameter
PRESSURE SEWER PIPE:
= 2554,86
= 2541.92
= 10.61 ft
= 25320 ft
= 2531.50 ft
= 2530,0 fit
2528.0 ft
2525.5 ft
29.36 ft Use 29.5 ft
= 8 inch
Pipe Diameter = 6.inch
Flow Velocity = 3.00 ftls
Pipe Length = 1080 ft
Pipe Discharge Dev. at Wet Well = 2549:02
Pipe High Point Elev. = 2552.4.8
Pipe Final Discharge Efev. = 2550.94
FLOW DA -TA:
Population of Developments = 1,518 people
Average Daily Flow = 100,930 gpd
Peak Flow Factor = 3.80
Peak Design Flow = 3.83,534 gpd
Peak Design Flow = 266 gpm
PUMP DATA:
Pump Capacity
= 266 gpm
Elevation Head
= 26.98 ft
Friction Headloss
= 8.13 ft
Total Dynamic System Headloss
= 35.1 ft
Horse Power
= 5.0 hp