PZ - Geotech ReportZ
E Post Office Box 190537 - Boise, Idaho 83719
site.consulting.idaho@gmail.com - 208-440-6276
LTING, LLC
Mr. Dan Lardie May 16, 2019
Leavitt & Associates Engineers, Inc. Page 1 of 19
1324 1St Street South File 19213-A
Nampa, Idaho 83651
Re: Geotechnical Recommendation Report
Goddard Creek Townhomes
2780 West McMillan Road
Meridian, Idaho
Dan:
As per your authorization, on April 13, 2019, SITE personnel observed the excavation of
four test pits on the referenced property. Soil samples were gathered and submitted for
laboratory analysis. Based on the observed and reported conditions and compliance
with the recommendations provided herein, the referenced lot is acceptable for
construction of the planned development for multi -family structures. The planned
buildings can be constructed using standard construction methods. Conventional strip
foundations with slab on grade floors or a conventional crawlspace are acceptable.
Foundations can be designed to exert bearing pressures of up to 1500 psf on the
existing soils or upon approved structural fill. Based upon this bearing pressure and the
recommendations of this report being followed, we anticipate total settlements of less
than one inch, with differential settlements less than half of this value. If these values
are unacceptable, please contact SITE for additional recommendations.
Recommendations are also included herein for design of the proposed development.
We appreciate this opportunity to be of service. Please contact our office if additional
information or services are required.
Respectfully submitted,
Bob J. Arnold, PE
SITE Consulting, L
QLISTER
B0etF OF �p�o�0
J.
AR
Geotechnical Services / Soil Testing & Inspection Services
Z
E Post Office Box 190537 - Boise, Idaho 83719
site.consulting.idaho@gmaii.com - 208-440-6276
LTING., LLC
GEOTECHNICAL RECOMMENDATION REPORT
Goddard Creek Townhomes
2780 West McMillan Road - Meridian, Idaho
PURPOSE AND SCOPE
This report presents the results of a Geotechnical Evaluation performed for a proposed
multi -family residential development to be constructed on a single parcel located on the
north side of West McMillan Road, south side of Selway Rapids Way, and west side of
Goddard Creek Drive in Meridian, Idaho. As per the client supplied Conceptual Plan,
access to the property will be gained from two locations along Selway Rapids Lane.
Parcel information from the Ada County Assessor's website is as follows:
#
I Ada County # I Address
I Acres
1
1 R 3182130041 1 2780 West McMillan Road
1 4.62
The field investigation included subsurface exploration by means of a rubber tire
mounted backhoe operated by an independent contractor. During excavation of the test
pits, logs were generated, and soil samples were gathered. Soil samples were returned
to our in-house soil laboratory for testing. After the field investigation and laboratory
testing was completed, all available field and laboratory test data was reviewed, the
provided design information was evaluated, and this report was prepared. This report
summarizes our findings and recommendations regarding the geotechnical aspects of
the project.
AUTHORIZATION
Email authorization to proceed with this geotechnical investigation was received on April
15, 2019 from the client. Authorization to proceed and the use of the recommendations
provided herein indicate the client's acceptance of the scope of work, warranty,
limitations, and general conditions provided herein and within the submitted proposal. N
a
Geotechnical Services / Sof/ Testing & Inspection Services
SITE Post Office Box 190537 - Boise, Idaho 83719
site.consulting.idaho@gmaii.com - 208-440-6276
COI SULT t
RESEARCH & BACKGROUND
There were no homes or outbuildings on the subject property at the time of our field
investigation. Historical aerial photos available on Google Earth reveal no former
building structures or improvements to the property but did reveal the property was
previously covered with rows of trees. It is assumed it was nursery or orchard in the
early 2000. Since then, the property appeared to have been used as pastureland.
FIELD INVESTIGATION
Four test pits were advanced to depths of approximately ten to eleven feet below the
existing ground surface. Sloughing soils prevented deeper exploration. During
excavation, samples were recovered from the spoil piles as excavation was performed.
These samples were sealed in plastic bags, labeled, and returned to the laboratory for
evaluation and analysis. In the laboratory, sieve analysis, moisture content, and Liquid
Limit, Plastic Limit and Plasticity Index testing were performed on selected samples.
Tests were performed in general accordance with the cited ASTM test methods. All test
results are included in the Test Pit Logs located in the Appendix.
OBSERVED CONDITIONS
All four test pits were similar with approximately five to six feet of sandy lean clay or
sandy silt that grades to silty sand atop the deeper Whitney Terrace sand and gravel
soils. Gravel and sand were contacted at five to six feet deep in all test pits. These sand
and gravel materials were clean (free draining) by seven feet deep. Groundwater was
encountered in all four both test pits at ten feet deep when excavated on April 13, 2019.
Groundwater has since risen to eight feet deep.
",
Geotechnical Services / Soll Testing & Inspection Services
SITE Post Office Box 190537 - Boise, Idaho 83719
site.consulting.idaho@gmaii.com - 208-440-6276
CONSULTING, LLC
Since groundwater is critical to civil design, the Idaho Department of Water Resources
website provided the four well logs included in the Appendix. These logs indicate the
static groundwater on the subject site is 10 feet deep. In a well southwest of the subject
property the static water level is reported as six feet deep and in two wells just east of
the property the static water level is 12 & 13 feet deep.
Monitoring wells were installed in all four test pits. Monthly readings will continue until
design is approved for construction.
GROUNDWATER DATE TABLE
TP #
#1
#2
#3
#4
Hub Elevation
Height
3.0
3.0
3.0
3.0
.Casing
Casinq Elevation
Installed 4/13/2019
GW Elevation
-10.0
-10.0
-10.0
-10.0
4/23/2019 KA
11.0
11.5
11.5
11.6
GW Elevation
-8.0
-8.5
-8.5
-8.6
5/16/2019 BA
11.1
11.3
11.3
11.7
GW Elevation
-8.1
-8.3
-8.3
-8.7
Geotechnical Services / Soil Testing B Inspection Services
ZCONSULTING.,
E Post Office Box 190537 - Boise, Idaho 83719
G site.consulting.idaho@gmail.com - 208-440-6276
LLC
DESIGN & CONSTRUCTION RECOMMENDATIONS
General Earthwork
All native soils that are free of organic matter and expansive clays can be used as fill.
After proper grubbing, the native lean silty sand or sandy silt, soils can be utilized as
structural fill to fill building pads or street section subgrade .
Removal of the majority of the organic materials will require grubbing of 4-6 inches of
surface soils. This is required in all areas to receive structural fill. Deeper excavation
may be required along irrigation ditches and where large trees and soft wet areas are
present. The depth of grubbing is to be confirmed during construction to ensure that
organic materials are properly removed from beneath future pavements and structural
fills. Inspection by the project geotechnical engineer should confirm that all organic
material and demolition debris is removed. Inspection must confirm complete removal of
previously demolished structures including slab on grade floors.
Rutting caused by the contactor using rubber -tired equipment on a wet subgrade can be
expected and should be repaired at contractor expense. This information is to be
supplied to earthwork contractors prior to construction.
Structural fills less than three feet deep are to be compacted to 95 % of the maximum
dry density by ASTM D698, Standard Proctor. For deeper fills, such as ditch backfill,
basement backfill, and fill intended to contain rerouted irrigation canals, ditches, or
storm water runoff, fill materials are to be compacted to 100 % of the Standard Proctor
maximum dry density. If structural fill is to be placed on the building pads, the fill is to
extend laterally outside foundations a distance equal to the depth of structural fill.
Compaction testing of all structural fill is required. Visual inspection is also required to
confirm stability and the lack of soft, deflecting, or rutting areas. Fill can pass
compaction tests and still be rejected if it fails visual inspection.
N'
Geotechnical Services / Soil Testing & inspection Services
S 1 t C Post Office Box 190537 - Boise, Idaho 83719
Z1 ` site.consulting.idaho@gmail.com - 208-440-6276
CC�I:SULTING, LLC
Excavations
Shallow excavations and trenches that do not exceed four feet in depth may be
constructed with side slopes approaching vertical. The ability of soils to maintain a
vertical or near vertical slope over any extended period can be quite variable.
This information is provided for planning purposes. It is our opinion that maintaining safe
working conditions is the responsibility of the contractor. Jobsite conditions such as soil
moisture content, weather condition, earth movements and equipment type and
operation can all affect slope stability. All excavations should be sloped or braced as
required by applicable local, state, and federal requirements.
Pavement Section
It is assumed that an R -Value of greater than R=20, would be obtained if the native
surface soils were tested. Pavement sections have been calculated based upon an R -
Value of R=20 and Traffic Index of T1=6. The results are shown in the table below.
Materials meeting the requirements of ISPWC & / or ACHD are required for all work
within this project. For this project, it is recommended that the subgrade be inspected
(proof -rolled) prior to the placement of subbase materials.
HMA
2.5"
%" Base
4.0"
Subbase
10.0"
Subgrade
Inspected
Storm Water
Free draining sand and gravel material were present at seven feet deep in all test pits.
Based upon free draining conditions, a percolation rate of P=8 in/hr. is to be assumed
for design of facilities that extend seven feet below the existing ground surface. Over
excavation and backfilling with free draining materials may be required. Confirmation of
perc rate and clearance above groundwater at the time of construction by field testing is
recommended.
Geotechnical Services / Soil Testing A Inspection Services
ME
SITE Post Office Box 190537 - Boise, Idaho 83719
G site.consulting.idaho@gmaii.com - 208-440-6276
CONSULTING, LLC
Building Foundation System
The proposed multi -family residential structures may be supported on conventional,
continuous, and isolated pad foundations founded upon the native soils or upon
structural fill extending to these soils. Based upon proper placement and compaction of
structural fill, bearing pressures of up to 1500 psf are allowed for foundations founded
on the native soils or upon properly placed and compacted structural fill. Either
crawlspaces or slab on grade floors are acceptable but slab on grade floors will
eliminate the possibility of water accumulating in crawlspaces. Basements are not
allowed without a lot / building specific geotechnical evaluation.
If clay soil, wet soil, or deflecting soil is present at the foundation support elevation a
geotechnical engineer should be retained for site specific recommendations. Foundation
drains are required within this development. Roof runoff is not to route through
foundation drains. Foundation embedment depth is to be at least 24 inches below
outside adjacent grade. Foundations that are outside crawlspaces are to be sealed /
waterproofed with brush or spray on foundation mastic.
Slab on Grade Concrete
Care must be taken so that all excavations below both interior and exterior slab on
grade concrete are properly backfilled in accordance with the structural fill
recommendations. Trenches and wall backfill areas are to be filled in lifts and benched
each lift so that fill is not placed against a vertical soil face greater than three feet tall.
Testing is to confirm that compaction has been achieved. Areas of excessive yielding
should be excavated and backfilled with structural fill. Any fill used to increase the
elevation of slab on grade concrete should meet the requirement for structural fill.
Concrete pavements should be placed atop a mat of at least six inches of granular
structural fill materials. Mat material should all pass a 3/4 -inch sieve and should contain
less than seven percent passing the # 200 sieve. The mat shall be compacted to the
requirement for structural fill.
a
U0
a
Geotechnical Services / Soil resting & Inspection Services
SITE Post Office Box 190537 - Boise, Idaho 83719
site.consulting.idaho@gmail.com - 208-440-6276
ZCONS�U_LTING,.LLC
Underground Utilities
It is not anticipated that large excavators or small backhoes will experience any
difficulties excavating the onsite materials encountered on the property. No bedrock
formation was encountered on the subject property. Well logs from IDWR indicate the
high static water level may be as high as six feet below the existing ground surface.
Inspection & Testing
A qualified engineer or his representative should monitor fill placement to ensure the
work is performed in accordance with these recommendations. For mass filling, field
nuclear moisture - density testing shall be performed on each lift of compacted fill, one
each filled residential lot or building pad. Trench backfill and right of ways are to be
tested to ACHD and / or ISPWC requirements. It is noted that structural fill can pass
compaction tests and still be unacceptable if pumping, rutting, or deflecting under
vehicle or foot traffic.
Contractor Inspections
This report has been prepared with the intent to provide specific design information to
the developer and the civil engineering consultant. It is not intended to act as any
contractors "Due Diligence" or subsurface inspection prior to estimating construction
costs or actual construction. Contractors may use the onsite monitoring wells to assess
the groundwater prior to proposing on or beginning construction. Wells are to be
protected during construction and can only be removed with permission from the client
and SITE.
General Comments
After the plans and specifications for construction are completed, it is recommended
that this consultant be provided the opportunity to review the final design and
specifications. This review will confirm that the earthwork recommendations have been
properly interpreted and implemented. At that time, it may be necessary to submit 00
a
Geotechnical Services / Soil Testing & Inspection Services
S ITE Post Office Box 190537 - Boise, Idaho 83719
G site.consulting.idaho@gmail.com - 208-440-6276
CONSULTING, LLC
supplementary recommendations. This review is a part of this service and will not result
in additional invoicing unless additional research and recommendations are needed.
Testing and inspection services are recommended herein. Proper quality control during
construction is required to confirm materials and methods and thereby obtain a
desirable finished product. Monitoring and testing should also be performed to verify
suitability of materials used for structural fills and to confirm proper demolition, subgrade
grubbing, subgrade stability, and proper placement and compaction of fills. Any
deviations from the herein described subsurface conditions must be brought to the
attention of this consultant.
This report has been prepared for the exclusive use of the client and their retained
design consultants. Findings and recommendations within this report are for specific
application to the proposed construction described herein and apply only to the property
identified. Client may duplicate this report as needed or additional copies will be
provided upon proper client authorization.
Appendix Follows
-91
Geotechnical Services / $oil Testing & Inspection Services
S ITE Post Office Box 190537 - Boise, Idaho 83719
Lesite.consulting.idaho@gmaii.com - 208-440-6276
CiNSUiVii ,
VOJ 114 ,r•1►a
Preliminary Plat
Aerial Photo
Test Pit Logs (4)
Soil Log Legend
Abbreviations and Acronyms
Adjacent Well Logs (4)
P
Geotechnical Services / Soil Testing & inspection Services
SITE Post Office Box 190537 - Boise, Idaho 83719
site.consulting.idaho@gmail.com - 208-440-6276
CONSULTING, LLC
PRELIMINARY PLAT
Supplied by client
FS
Geotechnical Services / Soil Testing & Inspection Services
,max
✓NEAR 040" NNC
• 10
.l._._
ME
2
- Q
�. WIIN
V
n�r
r
1R
--ti1R•-- -
lzy y
i N
ey
i.
rr�v
f�
wY
IIr�Y
041
1 f0Y
•E!T MAAR dRmC LOOP
S
(R
iY'
•¢rte
--
t
`
'
1
t
NE;i NCIAUAN ROAO
-- -- -
Supplied by client
FS
Geotechnical Services / Soil Testing & Inspection Services
SITE Post Office Box 190537 - Boise, Idaho 83719
site.consulting.idaho@gmaii.com - 208-440-6276
CONSULTING, LLC
AERIAL PHOTO
2780 West McMillan Road - Meridian, Idaho
from landprodata-com
I
bb
Geotechnical Services / Soil Testing & inspection Services
SITE Post Office Box 190537 - Boise, Idaho 83719
site.consulting.idaho@gmail.com - 208-440.6276
CONSULTING, LLC
TEST PIT LOG
Test Pit:
TP -1
File #:
19213-A
Client:
Leavitt & Associates
Date Excavated:
04/18/19
Project:
Goddard Creek
Excavated By:
Wood Brothers
Location:
NW Corner
Logged By:
J. Meusch, PM - SITE
DEPTH
SOILS DESCRIPTION
feet
1:0" 1 314" 1 112" 1 3/8" 1 #4
#10 #40 #100 I
` #200' %M LL PI
0.0-1.0
Brown, Moist, Firm, Sand, Clay, Silt
With Root Zone / Organic Layer 6-8"
1.0-3.0
Brown/Tan, Moist Firm, Sandy, Silt ML
2.0
1 1 1 100
99 88 65
53.8 20.0 NP NP
3.0-5.0
Red Moist Firm Silty, Sand SM
4.0
1 1 100 1 97 1 88
80 50 27
18.8 13.3 NP NP
Red Moist Firm Sand Gravel Cobble
M
Bottom of Excavation
Ground Water Encountered @ 10.0
Monitoring Well Installed
TEST PIT LOG
Test Pit:
TP -2
File #:
19213-A
Client:
Leavitt & Associates
Date Excavated:
04/18/19
Project:
Goddard Creek
Excavated By:
Wood Brothers
Location:
SW Corner
Logged By:
J. Meusch, PM - SITE
DEPTH
SOILS DESCRIPTION
feet
1.0" 3/4" 1 1/2" 1 3/8" 1 # 4
#10 #40 1 #100
#200 1 %M I LL I PI
0.0-1.0
Brown, Moist, Firm, Sand, Clay, Silt
With Root Zone / Or anic Layer 6.8"
1.0-6.0
Brown/Tan Moist, Firm Sand Gravel Silt
6.0-10.0
Red Moist Firm Sand Gravel Cobble
10.0
Bottom of Excavation
Ground Water Encountered @ 10.0
Monitoring Well installed
Geotechnical Services / Soil Testing & Inspection Services
'�` Post Office Box 190537 - Boise, Idaho 83719
/ site.consulting.idaho@gmail.com - 208-440-6276
CONSULTING, LLC
TEST PIT LOG
Test Pit:
TP -3
File #:
19213-A
Client:
Leavitt & Associates
Date Excavated:
04/18/19
Project:
Goddard Creek
Excavated By:
Wood Brothers
Location:
SE Corner
Logged By:
J. Meusch, PM - SITE
DEPTH
SOILS DESCRIPTION
feet
1.0" 314" 1 1/2" 1 3/8" 1 # 4 #10 1 #40 ' ' #100
#200 %M ` LL
0.0-1.0
Brown, Moist, Firm, Sand, Clay, Silt
With Root Zone I Organic Layer 6-8"
Brown, Moist, Firm, Sand, Clay, Slit
With Root Zone / Organic Layer 6-8"
1.0-4.0
Brown/Red, Moist, Firm, Sand, Gravel Silt
Brown Moist, Firm Sandg, Lean Clay CL
4.0-6.0
Brown/Tan Moist Firm Cemented, Sand, Clay,
Silt
99 94 86
6.0-10.0
Brown/Red Moist Firm Sand Gravel Cobble
Brown/Tan Moist Firm Silt Sand SM
10.0
Bottom of Excavation
Ground Water Encountered @ 10.0
Monitoring Well Installed
1 1
89 66 45
TEST PIT LOG
Test Pit:
TP -4
File #:
19213-A
Client:
Leavitt & Associates
Date Excavated:
04/18/19
Project:
Goddard Creek
Excavated By:
Wood Brothers
Location:
NE Corner
Logged By:
J. Meusch, PM - SITE
DEPTH
SOILS DESCRIPTION
feet
1!0" 1 3/4" 1 1/2" 1 3/8" 1 # 4
#10 #40 ' #100
#200) %M - LL
0.0-1.0
Brown, Moist, Firm, Sand, Clay, Slit
With Root Zone / Organic Layer 6-8"
1.0-3.0
Brown Moist, Firm Sandg, Lean Clay CL
2.0
1 1 1 1 100
99 94 86
77.6 24.6 33 13
3.0-5.0
Brown/Tan Moist Firm Silt Sand SM
4.0
1 1
89 66 45
32.9 22.2 NP NP
5.0-10.0
Brown/Red, Moist Firm Sand Gravel, Cobble
10.0
Bottom of Excavation
Ground Water Encountered @ 10.0
Monitoring Well installed
Geotechnical Services / Soil Testing & Inspection Services
SITE Post Office Box 190537 - Boise, Idaho 83719
G site.consulting.idaho@gmaii.com - 208-440-6276
CONSULTING, LLC
SOIL LOG LEGEND
UNIFIED SOIL CLASSIFICATION SYSTEM
iAQTM QTAMnAOn TFCT MFTFInn n 9ds7 FOR CLASSIFICATION OF SOIL FOR ENGINEERING PURPOSES
MAJOR DIVISIONS
TYPICAL
DESCRIPTIONS
COARSE
GRAINED
SOILS
50% - #200
GRAVEL &
GRAVELLY
SOILS
50% - #4
< 5% - #200
GW ell- raded gravel, gravel -sand mixture little or no fines.
GP Poorly graded gravel, gravel sand mixture, little or no
fines
5-12% 4200
12% - #200
lty gravel, gravel -sand -silt mixtures
GMlilty
GC ayey gravel, gravel -sand -clay mixtures
AND & SANDY
OILS
50%-#4
< 5%, - #200
SWell-graded sand, gravelly sand, little or no fines.
SP oorly graded sand, gravelly sand, little or no fines
12% - #200
SM sand, sand -silt mixtures
SC Clayey sand, sand -clay mixtures
FINE
GRAINED
SOILS
50% - #200
SILTS AND
CLAYS
LL < 50%
INORGANIC
ML Inorganic silt and very fine sand, rock flour, silty or
clavev fine sand or clayey silt with slight plasticity
CL Lean clay -low to medium plasticity, gravelly clay, sandy
clay, silty clay
ORGANIC
OL Organic silt and organic silty clay of low plasticity
SILTS AND
CLAYS
LL > 50%
INORGANIC
MH Elastic silt, micaceous or diatomaceous fine sand or silty
soil.
CH Fat cls - high plasticity
ORGANIC
OH rganic clay -mod. or high plasticity: organic silt
HIGHLY ORGANIC SOILS
PT Peat, humus, swamp soil with high organic content
ABBREVIATIONS AND ACRONYMS
STM
American Society for Testing and Materials
IBC
International Building Code
ISPWC
Idaho Standard for Public Works Construction
IDWR
Idaho Department of Water Resources
NP
Non -Plastic
PCC
Portland Cement Concrete
P
Test Pit
USCS
Unified Soil Classification System
pcf
Pounds per Cubic Foot
psf
Pounds per Square Foot
sf
Tons per Square Foot
psf/f
Pounds per Square Foot / Foot
I
C
Q_
Geotechnical Services / Soll Testing & Inspection Services
S1 T E Post Office Box 190537 - Boise, Idaho 83719
site.consulting.idaho@gmail.com - 208-440-6276
CONSULTING, LLC
SU-)
of
JesQ�}r�
Adjacent Well Logs
Form 23qq..�� STATE OF IDAHO USE TYPEWRIrFit OR
9/82. DEPARTMENT OF WATER RESOURCES BALLPOINT PEN
WELL DRILLER'S REPORT
State law rapulres that this report be filed with the Olmtor, Department of Water Remrca
wlddn 30 deva after the eornDHtfon pr aWndonmant of the well.
1. WELL OWNER
elms
�(QpW�_.
7. WATER LEVEL
Sulk Wier laud Mt below lam) wrl•n.
FlgMny7 U Ya G.P.M. flowAddrea
Artedanclo-dInpr•swre P*I•
Controlled by: UVrie ❑Cap ❑Plug
Owners PermitNo.Temperature
OF. Guelity
dane� anerrewn w leleae'erwe Mea Nser.
2. NATU 6BF WORK
S. WELL TEST DATA
aw welt Cl DNpanad D Replacement
D Pump ❑ 8a15er ❑ Ab D Other
❑ Abandoned Id—Aba •b•ndonmem pnacadufea such as
materials, plug dopms. ete. In iltholople log)
ONx Lewl --
" 0J
OZ V4
3. PROPO�SED USE
9. LITHOLOGIC LOO0a. 95
W2. ❑ Inigatfon ❑ Tat ❑ M.Ndpal
ClIndustdM U Stock ❑ Wasn Diapocal m Injection
❑ Other (rpecify type)
gore 0a th Wam
Dl— From To MatariY Yea No
s m
L MET/ROD DRILLED
[7 Ro4ry Q -A1, E3 Nydaau)ic ❑ Rewrrrotry
O Cable 13 No❑ Omer
S
_
36
& WELL CONSTRUCI`ION
Caing.hedule: Pl5uai ❑ Cone fie, ❑Olhr
TNcanaN dAYav F To
%SO ineha _ ira:ha Haat GO has,
kltlta iia feet _feet
Inch" Inches feet —fee
_
_`MARs ~
Inch �br3sN _ feat __fast
cng drive shoe used? P a ❑ Nom
Wad
Was o pseaw orNal uud7 D YN B'IVo
Perlaatad7 ❑ Ya
E Mrnl W Wa:u apuna
WfilaRl a
How Worsted? ❑ Factory D Knife U Tach
Site o1 perforation _ Indln by — Indra
N. -w .Fmm To_
psrforatiaR feet_—f
pwforations IM
peritlntlone fog
-
WeR se— MC•nd7 D Ya WIND
ralsinem
Marwl"oue
D S0 REAgfG�-`
Type Model NO.
Dlametar_Slotelze _fiat from_I•at to
Diamater _Slot sUs _ 7_fast Id _fast
G'WI pskd7 ❑Yn BTIo DSlasofgrMl
Plamd from fast to feat
Surface Nal depth _Me usedlnaeel: ❑Cerasrttgralt
D Bentonka lingelay 0 -
Seating procedure used: ❑ Sherry pit ❑ Tamp. wrfacs casing
❑ Qft,. to sell depth
Methd o1 pining c i g: ❑ Threaded - -GAWald4d ❑ Solvpe
- Wald
10.
Wak stand nhhd
❑ Cemented between Strata
D—dtw octose port f
9. LOCATION OF WELL
Sketch mop location must ogee with W1171en location.
N �f At r1n a•
stlbdidslal �r�l fj�' t•�'���.�aj
�T
(�
11. DRILLERS CERTIFICATION CIL
(Aye certify mat ail minimum well ea ovi den et+Mada wen
complied wim at the dme tM rfg wa ramoad.
Flrm Nwne9�z-osFkm No.�WJUN
2addrmLot
tj,,Block No.
9f--
(Sgnad W (Firm O1fidM)
'^^ -
andC°"nq'
(Operator).
_�
. T. � N* R. e NW.
USE ADDITIONAL SHEETS IF NECESSARY - FORWARD r rte W car r u Cur. — r
Geotechnical Services / Sol/ Testing & Inspection Services
d)
q0
(0
CL
SITE Post Office Box 190537 - Boise, Idaho 83719
site.consulting.idaho@gmail.com - 208-440-6276
CC►NSU LTI NG, LLC
/ Stete., Idebo M
S6 TyvEWRITE I,Deportment of Water Reeouroee
LOALL POINT YEN
WELL DRILLER'S REPORT �,1,JIC is telt
Sut.l.w r.wlrn Wt tN. report ba Illd wfU the Director, Dw.lw.d d 1VeM Re.errrtw tdlFR�
days site, the eompution or.bwdomtwnt of th. W. W mcn gar
rWELLOWNER. 7. WATER LEVEL0M n. �y/j /Y Suirc wnwl.vd �Iblow luM wrlm
SL4Q)L �',--u-`-' %�--7i�Y)ppFlowing) OYa ". O.P.M. ffow
A�''a_.---
P(tIIQ��(LTyf Addno I ' F. wlitr .-_----
'I 7 y0 .Ws /sJ N Tempanure_ O
Artedendasedinproaure 0.aL M
Deer "Permit N0. G 3 � 8 5 / rl Controlled by ❑ Vd.r ❑ CAP ❑ Plug
2 NATURE OF WORK 0, WELL TEST DATA Q
�en weft LIDetpmd 13RePI-M.1 ❑ Pump O Rail. ❑ Oth.r ArR
Did�w OJAI. Drw Dewn Narn
AbwAorud Idwcribe method of V"4CMIrrgl 3
V PROPOSED USE _/
❑ D. -- Drtrdedlw O Te.f ❑ 00 -b -w" bed A LITNOLOOICL00
O *.+rid O edHtrid O 0-0 ❑ Tlb.t. 01we.d Of Frew�Ts tirswY
l METHOD DRILLED
LYUbI. O Rot— O Dig nth.
0. WELL CONSTRUCTION
Diunet. of bole ! bldree ToW depth �- Mt
Codrp echedulo: f!'SiM O Conch
Teyrwr OMewtw Frew To
*. v lndr.e _L_ what .�_ Mt //O feet
kds Irtdtw _len
urAw brdrw
Yrdtw Inthw _ fiat --f.a
krhw
Ircht. feet _ten
VM tw'ry drive d— r.w 7 m-vw U No
Ww a p.ckr w W tnw77 O Yw @•RYo
01r-0 No
How pwfw.td) el-wtwY ❑ Knife O T.
Sixsolpwtwation at irchwby" lotlimi
N.etw Frew To
pwf—'Jws /_ fwt fwt
L I pwfontl.- fwl JJ. r feet
.._— pwfora l Cwt fret
1'; d1 sreon bwulld) ❑ Yee O No
hterul.nur.r s num
T—;--
ypo Model No.
Dismn. _ Slot site _ Sn from_ len to__ IM
Drwmtw_ Slot site _ Sin from__ feetw_Mt
Greed pXkd) frYn O No Sire of Weed '* M'
Noted from / V /.n W
&rhea s ,eve*-.i�.MO.W wd In —1 f9't.—t peel
O pwObq siry ❑ W.II to".
Sp*q /...&F ..w ❑ Slee! eH ❑ TW*-" -I— neeYF
❑ Owre.r. N w wPe
0. LOCATION OF WELL
Scndr mop 1—tion murf .gme with written mcnion.
N
lei No Oak N.
county Ail A _..
1 I0 -Work nand LJl D/jj_Zj7 Rnhhd
I L DRU"AS OM IMON � OW WEf
F.w Ifrre. Fie, H.—
MDDOpA, IDARO 'tM j
A.ewe
Swed M lFvm Offwfdfl tM • ..�. �" �
p►IrM.I �Rodr+.--a--�as�
FORWARD THE WHITE COFY TOTHE DEPARTMENT
a
L
Geotechnical Services / Soil Testing & Inspection Services
ZS
ITE Post Office Box 190537 - Boise, Idaho 83719
site.consulting.idaho@gmail.com - 208-440-6276
CONSULTING, LLC
Irr: uL- lV Eo
AUG 2 4 1999
39sr.9r T_ooRgeeoU_syead
Fam 238.7 IDAIIODEPARTMENTOl�RRESOURCES q-cdby a
---- —
--
WEILDRI--
,. I/4 I/4 _I/4
1. DRILLING PERMIT NO. 6
3 -ons 05 7 8 0O0 W:
11. WELL TESTS:
Other NWRNo. D0009804 — -- Railer Air Flowin Artceian
[U 2. OWNER �.
T14C Name Kelly Fulfer
Address 2350 W McMillan Rd
CA154- City Meridian State ID Zip 83642 WSW Temp. "I m hok: temp.
3. LOCATION OF WELL by legal description: War" Qwdity tmt or mnnnct";
Sketch map location must agrm with writtco location Depth first Water LnewNt'red 10'
N 12. LTfHOLOGIC I (11��e_ abimdonment)
'I'wp.4 North ® or South ❑
W E Rge. =East ❑ or West N
Sec. 26 1/4 SW 1/4 SE 1/4
— 111 m 7'65- ram
S Cadt lot County Ada
Long: _
Address of Well Site 2350 W McMillan
-----
Lt. Illk. Sub. Name
4. USE:
S Domestic ❑ Municipal ❑ Monitor ❑ Irrigation
❑ TThermnl ❑ fnjmtion ❑ Other
S. TYPE OF WORK check all that apply (Replacement ac.)
® Ncw Well ❑ ModiE , ❑ Abeodmmhent ❑ Other
6. DRILL METHOD
N Air Rotary ❑ Cable ❑ Mud Rotary ❑ Other
7. SEALING PROCEDURES
SFAMI,T: PACK ASIOUNI I MLTHOD
Material From To ..'r Q
Renu
Was drive shoe used? ® Y ❑ N Slap Depth($)
lyes drive alae seal teamed? ❑ Y R N How?
ii4M!I!!I',T�i71�DT!r!1iSRrR1
- 1'
II! .M.1—m
Length of Ifadpipc 12' Length of Tailpipe
9. PERFORATIONS/SCREENS
❑ Perforatiuns Method wash at
hR S.=. Screw Type
flomawn-IR.M
II! .M.1—m
I®li�lli�HOME
10. STATIC WATER LEVEL OR ARTESIAN
PRESSURE:
Ito. b6aYground Artesian Pressure Ib
Depth Dow—munered R. Describe access. port or carol
devices:
13. DRILLER'S Cr:H 11 r tr.n s wn
VWe conify that all minimum well ceartnKtion standards were
complied with at the time the rig eras rem cd.
Firm Name SOS Wclldrillina A RrraCo Finn No. 212
Pum Official Data ---- ` 9i
Supervisor or Opera- Date 040
(Sum one if 8 D{+nata)
Dau.: 01/16199 Ti -5:101'M
Geotechnical Services / Soil Testing & Inspection Services
I®li�lli�HOME
I►1
■
EMM�
�1
®�■�
►ZI
■
I31��■3■
' ■j►ZI
►Z/'■
_
■
i�l■I�Ilmi
. ,, ►�1�■
.. , ■►ZI
���
-_—
lyq+la'1 �1��■■
1
■�
III�7/`��
■I■�'
ti■'>r:lllwlw
■�■
10,71 M IFIU
FJ
13. DRILLER'S Cr:H 11 r tr.n s wn
VWe conify that all minimum well ceartnKtion standards were
complied with at the time the rig eras rem cd.
Firm Name SOS Wclldrillina A RrraCo Finn No. 212
Pum Official Data ---- ` 9i
Supervisor or Opera- Date 040
(Sum one if 8 D{+nata)
Dau.: 01/16199 Ti -5:101'M
Geotechnical Services / Soil Testing & Inspection Services
SITE Post Office Box 190537 - Boise, Idaho 83719
site.consulting.idaho@gmail.com - 208-440-6276
CONSULTING, LLC
Form 278-7
395 C96
19-7015 a X733 S 70
ccueomy
IDAHO DEPARTMENT OF WATER RESOURCES Inspect xlby
WELL DRILLER'S REPORT Twp—fie —see_
1l4 114 ll4
1. DRILLING PERMIT NO.
Other IDWR No. D0019418
2. OWNER:
Name _Randy Calkins
Address P.O. Box 99
City Meridien State ID Zip 83680
3. LOCATION OF WELL by legal dtamiptio■:
Sketch map location most agrx with written loadion
N
Twp.4 North N or South ❑
W L Rge. I East ❑ or West
Sec. 26 X1/4 SW-4rI!4 r I14
S Gov't lot County ADA
Lat: Long__..:—
Address of Well Site 2350 McMILLAN
City MERIDIAN _
� n awe e � ro a ice—
Lt. Blk. Sub. Name
d. USE:
N I)o mcstic ❑ Municipal ❑ Monitor ❑ Irrigation
❑ Thermal ❑ Injection ❑ Other
5. TYPE OF WORK chests all that upply (Reptuanrent cte.)
N New Well ❑ Modify ❑ Ahond0omcm ❑ Other.
6. DRILL METIIOD
N Air Rotary ❑ gable ❑ Mud Rotary ❑ Other
7. SEALING PROCEDIIRFS
6 ::I:OD
Matrriil From I To Sad:sur
Po"&
0 1 20 20
Was drive shoe used? ® Y ❑ N Shoe Dcpth(s) 120
Was drive shoe seal tested? ❑ Y 0 N Hmv7
��'�iQ4812'
Length of I leadpipc 12' 100 Length of Tnilpipe
9. PERFORATIONS/SCREENS
❑ 1'erforaiiens Method
N Screens Sween Type r^tcmoina
From I Tu I Sid Si. I Number I Di -met alat
126 1136 1 .016 It5' STST ❑ ❑
10. STATIC WATER LEVEL OR ARTESIAN
PRESSURE:
li 0. Inv ground Artesian Pres ntre�lb
Depot flow cuorrmiered. 0. Describe access Portorwntrol
I:L Luog
11. WELL TESTS:
Pum Railer Air Ilowin Art !SI
Water'femp. Ilnttoxn bole temp.
Water Quality test or ctontntents7
Ocpth first War" uncountacd 11
12. L1THOl.OGIC LOG: (l)"cribe "pain or abudoimceq
VWe certify Ihal all minimum well oTmtrwyion standards wcM
complied with at the time the rig was removed
Firm Nam AUAIII t 'Itino Rc P� n Co tint No. 212__
Firm 0Meid(7 '/ter—' ""`— Date `'
Supervisor or Openttor. 1)81e
(sip oroee if r'rm oflkw a'. Opaaror)
Dec 212IN2 Tior:3S2 PM
NOTHING FOLLOWS